7-2 Faults <strong>in</strong> the <strong>ControlLogix</strong> SystemFigure 7.1GSVClass: CONTROLLERDEVICEAttribute: STATUSDest<strong>in</strong>ation: KEYSTATEKEYSTATE.13FaultFaultAlarm to OperatorIn this example, the Get System Value (GSV) <strong>in</strong>struction <strong>in</strong>terrogatesthe STATUS attribute of the CONTROLLERDEVICE object and storesthe result <strong>in</strong> a word called KEYSTATE, where bits 12 and 13 def<strong>in</strong>e thestate of the keyswitch as shown <strong>in</strong> Table 7.1.Table 7.1Bit 13: Bit 12: Description:0 1 Keyswitch <strong>in</strong> Run position1 0 Keyswitch <strong>in</strong> Program position1 1 Keyswitch <strong>in</strong> Remote positionIf bit 13 is ever ON, then the keyswitch is not <strong>in</strong> the RUN position.Exam<strong>in</strong><strong>in</strong>g bit 13 of KEYSTATE for an ON state will generate a fault.For more <strong>in</strong>formation on the access<strong>in</strong>g the CONTROLLERDEVICEobject, see the Logix5000 Controllers General Instructions ReferenceManual, publication <strong>1756</strong>-RM003.Publication <strong>1756</strong>-<strong>RM001B</strong>-<strong>EN</strong>-P - October 2003