1756-RM001B-EN-P, Using ControlLogix in SIL2 ... - Tuv-fs.com
1756-RM001B-EN-P, Using ControlLogix in SIL2 ... - Tuv-fs.com 1756-RM001B-EN-P, Using ControlLogix in SIL2 ... - Tuv-fs.com
6-24 ControlLogix I/O ModulesWiring the Analog Output Module in Current ModeIn addition to following the General Considerations when using AnyControlLogix Analog Output Module on page 6-20, consider thefollowing application guideline before wiring the 1756-OF8 module incurrent mode:• Placement of Other Devices in Current Loop: you can locateother devices in an output channel’s current loop anywhere aslong as the current source can provide sufficient voltage toaccommodate all of the voltage drops (each module output is250 ohms)Figure 6.18 shows how to wire the 1756-OF8 module for use incurrent mode.Figure 6.18 ControlLogix Analog Output Module Wiring in Current ModeAnalog Output ModuleAnalog Input Module(+)(+)Actuator(–)(–)43376Publication 1756-RM001B-EN-P - October 2003
ControlLogix I/O Modules 6-25Checklist for SIL InputsThe following checklist is required for planning, programming andstart up of SIL inputs. It may be used as a planning guide as well asduring proof testing. If used as a planning guide, the checklist can besaved as a record of the plan.For programming or start-up, an individual checklist can be filled infor every single SIL input channel in a system. This is the only way tomake sure that the requirements were fully and clearly implemented.This checklist can also be used as documentation on the connectionof external wiring to the application program.Input Check List for ControlLogix SystemCompany:Site:Loop definition:SIL input channels in the:No. All Input Module Requirements (apply to both digital and analog input modules) Yes No Comment1 Is Exact Match selected as the electronic keying option for all modules?2 Is the RPI value set to an appropriate value for your application?3 Are all modules owned by the same controller?4 Have you performed proof tests on the system and modules?5 Have you set up the fault routines?6 Are control, diagnostics and alarming functions performed in sequence in application logic?No. Additional Digital Input Module-Only Requirements Yes No Comment1 When two digital input modules are wired in the same application, do the following conditions exist:• Both modules are owned by the same controller.• Sensors are wired to separate input points.• The operational state is ON.• The non-operational state is. OFF.• Configuration parameters (for example, RPI, filter values) are identical.2 For the standard input modules, is the Communication Format set to one of the Input Data choices?3 For the diagnostic input modules, is the Communication Format set to Full Diagnostics-Input Data?4 For the diagnostic input modules, are all diagnostics enabled on the module?5 For the diagnostic input modules, are enabled diagnostic bits monitored by fault routines?6 For the diagnostic input modules, is the connection to remote modules a direct connection?No. Additional Analog Input Module-Only Requirements Yes No Comment1 Is the Communication Format set to Float Data?2 Have you calibrated the modules as often as required by your application?3 Are you using ladder logic to compare the analog input data on two channels to make sure there isconcurrence within an acceptable range and that redundant data is used properly?4 Have you written application logic to examine bits for any condition that may cause a fault andappropriate fault routines to handle the fault condition?5 When wiring the 1756-IF8 in voltage mode, are transmitter grounds tied together?6 When wiring the 1756-IF8 in current mode, are loop devices placed properly?7 When wiring 1756-IT6I modules in parallel, have you wired to the same channel on each module asshown in Figure 6.14 on page 6-18?8 When wiring two 1756-IR6I modules, are two sensors used, as shown in Figure 6.15 on page 6-19?Publication 1756-RM001B-EN-P - October 2003
- Page 20 and 21: 1-10 SIL PolicyCatalogNumberDescrip
- Page 22 and 23: 1-12 SIL PolicyCatalogNumberDescrip
- Page 24 and 25: 1-14 SIL PolicySIL ComplianceDistri
- Page 26 and 27: 1-16 SIL PolicyProgram Watchdog Tim
- Page 28 and 29: 2-2 The ControlLogix SystemIf an an
- Page 30 and 31: 2-4 The ControlLogix SystemData Ech
- Page 32 and 33: 2-6 The ControlLogix SystemSoftware
- Page 34 and 35: 2-8 The ControlLogix SystemNotes:Pu
- Page 36 and 37: 3-2 ControlLogix System HardwareCon
- Page 38 and 39: 3-4 ControlLogix System HardwareRec
- Page 40 and 41: 3-6 ControlLogix System HardwareNot
- Page 42 and 43: 4-2 ControlLogix ControllerRecommen
- Page 44 and 45: 5-2 ControlLogix Communications Mod
- Page 46 and 47: 5-4 ControlLogix Communications Mod
- Page 48 and 49: 6-2 ControlLogix I/O ModulesFigure
- Page 50 and 51: 6-4 ControlLogix I/O ModulesModule
- Page 52 and 53: 6-6 ControlLogix I/O ModulesWiring
- Page 54 and 55: 6-8 ControlLogix I/O ModulesGeneral
- Page 56 and 57: 6-10 ControlLogix I/O ModulesWiring
- Page 58 and 59: 6-12 ControlLogix I/O ModulesApplic
- Page 60 and 61: 6-14 ControlLogix I/O Modules• Ch
- Page 62 and 63: 6-16 ControlLogix I/O ModulesWiring
- Page 64 and 65: 6-18 ControlLogix I/O ModulesWiring
- Page 66 and 67: 6-20 ControlLogix I/O ModulesUsing
- Page 68 and 69: 6-22 ControlLogix I/O ModulesFigure
- Page 72 and 73: 6-26 ControlLogix I/O ModulesCheckl
- Page 74 and 75: 7-2 Faults in the ControlLogix Syst
- Page 76 and 77: 7-4 Faults in the ControlLogix Syst
- Page 78 and 79: 8-2 General Requirements for Applic
- Page 80 and 81: 8-4 General Requirements for Applic
- Page 82 and 83: 8-6 General Requirements for Applic
- Page 84 and 85: 9-2 Technical SIL2 Requirements for
- Page 86 and 87: 9-4 Technical SIL2 Requirements for
- Page 88 and 89: 9-6 Technical SIL2 Requirements for
- Page 90 and 91: 9-8 Technical SIL2 Requirements for
- Page 92 and 93: 10-2 Use and Application of Human t
- Page 94 and 95: 10-4 Use and Application of Human t
- Page 96 and 97: A-2 Response Times in ControlLogixE
- Page 98 and 99: A-4 Response Times in ControlLogixR
- Page 100 and 101: B-2 System Self-Testing and User-Pr
- Page 102 and 103: C-2 Additional Information on Handl
- Page 104 and 105: D-2 Spurious Failure EstimatesNotes
- Page 106 and 107: E-2 Sample Probability of Failure o
- Page 108 and 109: E-4 Sample Probability of Failure o
- Page 110: 2 IndexMMean time between failures
6-24 <strong>ControlLogix</strong> I/O ModulesWir<strong>in</strong>g the Analog Output Module <strong>in</strong> Current ModeIn addition to follow<strong>in</strong>g the General Considerations when us<strong>in</strong>g Any<strong>ControlLogix</strong> Analog Output Module on page 6-20, consider thefollow<strong>in</strong>g application guidel<strong>in</strong>e before wir<strong>in</strong>g the <strong>1756</strong>-OF8 module <strong>in</strong>current mode:• Placement of Other Devices <strong>in</strong> Current Loop: you can locateother devices <strong>in</strong> an output channel’s current loop anywhere aslong as the current source can provide sufficient voltage toac<strong>com</strong>modate all of the voltage drops (each module output is250 ohms)Figure 6.18 shows how to wire the <strong>1756</strong>-OF8 module for use <strong>in</strong>current mode.Figure 6.18 <strong>ControlLogix</strong> Analog Output Module Wir<strong>in</strong>g <strong>in</strong> Current ModeAnalog Output ModuleAnalog Input Module(+)(+)Actuator(–)(–)43376Publication <strong>1756</strong>-<strong>RM001B</strong>-<strong>EN</strong>-P - October 2003