6-22 <strong>ControlLogix</strong> I/O ModulesFigure 6.16 Monitor<strong>in</strong>g an Analog Output with an Analog InputOutputs OKTimerMULTRangeTolerance %DeltaADDDeltaMonitor<strong>in</strong>g <strong>in</strong>putHigh LimitSUBDeltaMonitor<strong>in</strong>g <strong>in</strong>putLow LimitLIMLow LimitOutput EchoHigh LimitOutputs OKTimer doneOutputs FaultedOutputs FaultedAlarm to OperatorThe control, diagnostics and alarm<strong>in</strong>g functions must beperformed <strong>in</strong> sequence.• When wir<strong>in</strong>g two analog output modules <strong>in</strong> the sameapplication, make sure:– Both modules use identical configuration.– The same controller owns both modules.Publication <strong>1756</strong>-<strong>RM001B</strong>-<strong>EN</strong>-P - October 2003