<strong>ControlLogix</strong> I/O Modules 6-17Wir<strong>in</strong>g the S<strong>in</strong>gle-Ended Input Module <strong>in</strong> Current ModeIn addition to follow<strong>in</strong>g the General Considerations when us<strong>in</strong>g Any<strong>ControlLogix</strong> Analog Input Module on page 6-13, before wir<strong>in</strong>g themodule, consider the follow<strong>in</strong>g application guidel<strong>in</strong>e:• Placement of Other Devices <strong>in</strong> Current Loop: you can locateother devices <strong>in</strong> an <strong>in</strong>put channel’s current loop anywhere aslong as the current source can provide sufficient voltage toac<strong>com</strong>modate all of the voltage drops (each module <strong>in</strong>put is 250ohms)Figure 6.13 shows how to wire the <strong>1756</strong>-IF8 module for use <strong>in</strong> currentmode.Figure 6.13 <strong>ControlLogix</strong> Analog Input Module Wir<strong>in</strong>g <strong>in</strong> Current ModeCh0 +Ch0 +Ch0 – Ch0 –CurrentSource ACurrentSource B43369Publication <strong>1756</strong>-<strong>RM001B</strong>-<strong>EN</strong>-P - October 2003