The <strong>ControlLogix</strong> System 2-5Figure 2.2 Output Module Behavior <strong>in</strong> the <strong>ControlLogix</strong> SystemOutput Commands from ControllerStandard<strong>ControlLogix</strong> I/OInformationData Echo validation from system-sideAdditional Field-SideInformation provided byDiagnostic Output modulesField-side Output Verification, PulseTest status plus No Load detectionActuatorPulse TestA diagnostic output module feature called a Pulse Test can verifyoutput circuit functionality without actually chang<strong>in</strong>g the state of theactuator connected to the output. Under user program control, anextremely short-duration pulse is directed to a particular output on themodule. The output circuitry will momentarily change its current statelong enough to verify that it CAN change state when requested, butshort enough <strong>in</strong> duration (the actual pulse is measured <strong>in</strong>milliseconds) not to effect the actuator connected to the output. Thispowerful feature allows a user to perform a preemptive diagnosis ofpossible future module conditions before they occur.Publication <strong>1756</strong>-<strong>RM001B</strong>-<strong>EN</strong>-P - October 2003