SIL Policy 1-3• This manual over-ride circuit is shown <strong>in</strong> Figure 1.1. It is<strong>com</strong>posed of a hardwired set of contacts from a selector switchor push-button. One Normally Open contact provides for thebypass of power from the Controller output directly to theactuator. The other is a Normally closed contact to remove orisolate the controller output• An application program needs to be generated to monitor thediagnostic output modules for dangerous failures such asshorted or open output driver channels. Diagnostic outputmodules must be configured to hold last state <strong>in</strong> the event of afault.• A diagnostic alarm must be generated to <strong>in</strong>form the operatorthat manual control is required.• The faulted module must be replaced with<strong>in</strong> a reasonable timeframe.• Any time a fault is detected the user must annunciate the fault toan operator by some means (for example, an alarm light).Figure 1.1L1Manual OverrideActuatorL2 or Ground43379FaultAlarm to OperatorPublication <strong>1756</strong>-<strong>RM001B</strong>-<strong>EN</strong>-P - October 2003