11.07.2015 Views

POWERTRONIX MIZAR 10 ÷ 15 kVA DT 0386-E03 - Tools.Store

POWERTRONIX MIZAR 10 ÷ 15 kVA DT 0386-E03 - Tools.Store

POWERTRONIX MIZAR 10 ÷ 15 kVA DT 0386-E03 - Tools.Store

SHOW MORE
SHOW LESS
  • No tags were found...

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>POWERTRONIX</strong><strong>MIZAR</strong><strong>10</strong> <strong>÷</strong> <strong>15</strong> <strong>kVA</strong><strong>DT</strong> <strong>0386</strong>-<strong>E03</strong>Document : <strong>DT</strong><strong>0386</strong> PTX EnglishRevision Date Checked Approved00 <strong>15</strong>-06-2007 <strong>15</strong>-06-2007Ghezzi R.01 18-06-2007 18-06-2007Ghezzi R.02 29-06-2007 29-06-2007Ghezzi R.03 09-<strong>10</strong>-2008 09-<strong>10</strong>-2008Passoni A.<strong>15</strong>-06-2007Gorlani A.18-06-2007Gorlani A.29-06-2007Gorlani A.09-<strong>10</strong>-2008Gorlani A.Powertronix spa reserves the right to modify this document with any noticeR&D – TECHNICAL SPECIFICATION <strong>DT</strong><strong>0386</strong>-<strong>E03</strong>Page. 1 of 13


INTRODUCTIONPresent document defines technical specs of a three phase UPS named <strong>MIZAR</strong> coveringthe power range from <strong>10</strong> to <strong>15</strong> <strong>kVA</strong> ON-LINE DOUBLE CONVERSION UninterruptiblePower Supply Systems with forced ventilation cooling.These equipments are characterizedby reduced size and high efficiency, thanks to the conversion topology, which doesn’t needtransformers between mains, inverter and load.<strong>MIZAR</strong> UPS belongs to the “double conversion” equipments family, with all advantagesgiven by this topology and without any penalty in total efficiency.All sizes have the same cubicle.Following is shown the picture of the system :Powertronix spa reserves the right to modify this document with any noticeR&D – TECHNICAL SPECIFICATION <strong>DT</strong><strong>0386</strong>-<strong>E03</strong>Page. 2 of 13


GENERAL FEATURESDouble conversion, digital control, trafoless power module with IGBT HF switching,Cubicle arrangement as Powertronix styleAll the electronic mounted on the same removable power module Cables inlet from thebottomIP 20 protection degreeUPS control and signalling developed on the single boardCommunications Boards on the rear of the UPSModem remote supervision availableUPS diagnostic and management on teleservice from the factory through SNMPadapterControl panel with LCD display, EPO integratedRemote EPO facilityConnection to a PC availableRS 232 C serial port with DB9 connectorSNMP adapter availableSoftware development with the most popular operating systems (Windows, Novell,Unix, OS/2).Additional free contacts for main remote alarmsAs proposed for other <strong>POWERTRONIX</strong> products, suitable options are available to increasebehavioural level referred to power management and/or power quality as indicated in thefollowing items:Connection to PC or local line available.Isolation of the load through transformer.More UPS in parallel possibility.Isolation of the inverter line and\or reserve line.Powertronix spa reserves the right to modify this document with any noticeR&D – TECHNICAL SPECIFICATION <strong>DT</strong><strong>0386</strong>-<strong>E03</strong>Page. 3 of 13


ONE LINE DIAGRAM:Descriptions:1. IGBT power input2. Battery3. Inverter power IGBT4. Static Switch5. Manual By-PassPowertronix spa reserves the right to modify this document with any noticeR&D – TECHNICAL SPECIFICATION <strong>DT</strong><strong>0386</strong>-<strong>E03</strong>Page. 4 of 13


REGULATIONS AND STANDARDSThis UPS family is designed according to the following regulations and standards:Electromagnetic compatibility CEE 89/336CEI-EN 62040-1-1:Uninterruptible power systems (UPS)Part 1-1: General and safety requirements for UPS usedin operator access areaCEI EN 62040-1-2:Uninterruptible power systems (UPS)Part 1-2: General and safety requirements for UPS usedin restricted access locationsCEI EN 62040-2:Uninterruptible power systems (UPS)Part 2: Electromagnetic compatibility (EMC)requirementsCEI EN 62040-3:Uninterruptible power systems (UPS)Part 3: Method of specifying the performance and testrequirementsPowertronix spa reserves the right to modify this document with any noticeR&D – TECHNICAL SPECIFICATION <strong>DT</strong><strong>0386</strong>-<strong>E03</strong>Page. 5 of 13


GENERAL DATAUPS <strong>MIZAR</strong> <strong>10</strong>-<strong>15</strong> KVAGENERALConfigurationInputInverterS.SwitchCooling systemOn-Line Double conversionH.F. technology IGBT switching TrafoLessH.F. technology IGBT switching TrafoLessStatic Switch Relay technologyAir ForcedMECHANICALS CHARACTERISTICSLodgingDedicated CabinetColour RAL 7016Mechanical protection degree IP IP 20Positioning Pictures on pages 13 and 14Cables InputBottom on the rearMechanical Dimensions 900 x 390 x 900 mm (h x l x p)AMBIENT CONDITIONSOperating temp. range0-40° CBatteries temp. range +20 <strong>÷</strong> +30 °CRelative Humidity< 90% (without condenses)Maximum installation height without Until <strong>10</strong>00m uls (1% derating every <strong>10</strong>0m started from <strong>10</strong>00m up to 2000m)deratingTemperature range-20°<strong>÷</strong> + 70°C (UPS) +20°<strong>÷</strong> +30°C (Batteries)DISPLAYLCD-DisplayLighting AlarmsAcoustics AlarmsDisplay LCD 4 rows x 20 characters e 4 functions buttons + EPO localLed status green colour UPS OK/ Led status red alarmYesCOMMUNICATIONRS2321 standardFree contacts N° 4 contacts :UPS run / UPS on bypass / Mains OK / Battery end dischargeSNMP SLOTYesMaintenances SoftwareRS232Parallel communicationsRS232 OpticPowertronix spa reserves the right to modify this document with any noticeR&D – TECHNICAL SPECIFICATION <strong>DT</strong><strong>0386</strong>-<strong>E03</strong>Page. 6 of 13


GENERAL DATAUPS <strong>MIZAR</strong> <strong>10</strong>-<strong>15</strong> KVABATTERIESNominal Voltages720 VDCFloating Voltage8<strong>10</strong> VDCN° of elements 360Periodic battery testSi / programmableInternal batteries5Ah/7Ah/9AhWEIGHTSUPS without batteries (Kg)UPS with batteries (Kg)65 Kg230 KgAMBIENT CONDITIONSExchanged Air 500 m 3 /h (massima )Noise58 dB (A)OPTIONALBattery extensionTransformersShutdownSoftware for diagnosticsSNMP-AdapterRemote PanelSeparate cabinet 2 x 60 x (5Ah/7Ah/9Ah)Galvanic insulation (Separate cabinet)Powershut PlusGenerex PTXConnect the UPS to the netFor indications about UPS status at distancePowertronix spa reserves the right to modify this document with any noticeR&D – TECHNICAL SPECIFICATION <strong>DT</strong><strong>0386</strong>-<strong>E03</strong>Page. 7 of 13


UPS <strong>MIZAR</strong> <strong>10</strong> – <strong>15</strong> KVATYPE KVA <strong>10</strong> <strong>15</strong>Power KVA <strong>10</strong> <strong>15</strong>Power factor Cos φ 0,8 Cos φ 0,8INPUTN° of phases 3 Ph+N1Ph+N3 Ph+N1Ph+NNominal input voltage 3ph + N 380/400/4<strong>15</strong> VAC ±<strong>10</strong>%1ph + N 220/230/240 VAC ±<strong>10</strong>%Nominal voltage (reserve line) 3ph + N 380/400/4<strong>15</strong> VAC ±20%1ph + N 220/230/240 VAC ±20%Nominal Frequency50/60 HzAdmitted variation40/70 HzMax current absorbed20A20A(Vin = -20% 400V )Cos φ1 1Power factorInput distortion


UPS <strong>MIZAR</strong> <strong>10</strong> – <strong>15</strong> KVAType KVA <strong>10</strong> <strong>15</strong>BypassNominal voltage 3ph + N 380/400/4<strong>15</strong> VAC ±20%1ph + N 220/230/240 VAC ±20%Voltage tolerance ±<strong>10</strong>%Frequency50/60 HzAdmitted current overload<strong>10</strong> I n per <strong>10</strong>0 ms.Commutation times (max)Inverter-Bypass


UPS CONFIGURATIONSAll the sizes are available in the following configurations :Single phase input / single phase outputThree phases input / single phase outputThree phases input / three phases outputStand aloneHot stand-byParallel mode or power parallelThe parallel configuration is type bypass distributed.It is possible to have maximum n°8 unit in parallel.The communications between the unit of the parallel system is ring type by optical fibres.Powertronix spa reserves the right to modify this document with any noticeR&D – TECHNICAL SPECIFICATION <strong>DT</strong><strong>0386</strong>-<strong>E03</strong>Page. <strong>10</strong> of 13


UPS USER INTERFACELCD display 4 rows x 20 characters and 4 functions buttons + local EPOThe display is divided in the following 6 menus :MENU N° NOTEUPS Status and alarms 1 Default menuMeasurements 2 It show all the measure of the UPSCommand UPS 3 ON-OFF inverter, switching load, battery testPanel setup 4 Date-Time setting, battery test setting displaylanguages settingHistorical events 5 It store the last <strong>10</strong>24 events happens with date and timeService Mode 6 Only for service dept.Measures:- Input mains voltages - Input currents- Output voltages - Output currents- Output frequency - Output power <strong>kVA</strong>- Battery voltage - Battery current (with sign)- Battery autonomy - Cooling system temperatureUPS REMOTE PANELThe signals transferred are the following :Inverter RunOn automatic BypassMains PresentBattery LowSerial Interface:CS121 SNMP ADAPTER per il collegamento in rete dell’UPS.RS 232 port to be connected to a local PC, which has to be equipped with UPSMANsoftware.Powertronix spa reserves the right to modify this document with any noticeR&D – TECHNICAL SPECIFICATION <strong>DT</strong><strong>0386</strong>-<strong>E03</strong>Page. 11 of 13


DIMENSIONS AND POSITIONINGPowertronix spa reserves the right to modify this document with any noticeR&D – TECHNICAL SPECIFICATION <strong>DT</strong><strong>0386</strong>-<strong>E03</strong>Page. 12 of 13


DIMENSIONS AND POSITIONINGPowertronix spa reserves the right to modify this document with any noticeR&D – TECHNICAL SPECIFICATION <strong>DT</strong><strong>0386</strong>-<strong>E03</strong>Page. 13 of 13