Data SheetJanuary 2005ALPHATRAN <strong>Inverter</strong> <strong>System</strong>3.5 kVA - 21 kVA Scalable N+1 <strong>Inverter</strong><strong>System</strong> Overview and Components<strong>System</strong> OperationThe <strong>Inverter</strong> plantreceives 48 VDCfrom a DC powerplant of batterybank and convertsthe output toprecision regulatedAC power (userselectable voltageand frequency). Inthe event that theDC is not availableor out of tolerancedue to a dischargedbattery, or theinverters are notAC Distribution PanelMaintenanceBypass CabinetRedundantMicrocontrollers<strong>Inverter</strong><strong>Inverter</strong>Static Bypass Switch<strong>Inverter</strong><strong>Inverter</strong>able to maintain the critical load, the system willautomatically transfer to the static transfer switchand disconnect from the DC source. The statictransfer switch (standard) will make a seamlessly,uninterrupted transfer from the critical load to analternate AC power source where the inverterpower was synchronized to (utility power oranother protected AC source). The availability ofthe Alphatran N+1 on-line mode with a backupsource present is greater than 99.9999%.AC Distribution PanelThe AC distribution panel accommodates 20 (7KVA system) or 24 (14 and 21 KVA systems) singlepole circuit breaker positions and is available in120 and 240 Vac versions. Note: all recommendedbreakers include distribution alarm monitoringcontacts that take up an additional pole position.This limits the maximum number of circuit breakersif distribution alarm monitoring is to be used. Themaximum number of circuit breakers that can beinstalled, with and without the additional alarmmonitoring contact, is shown below.Maintenance Bypass CabinetSafely and seamless transfers the output toan alternate AC source (utility power orprotected AC power from another inverter orUPS system) allowing the inverter to be shutdown or removed without interrupting powerto the critical loads. The maintenance bypassassembly is factory wired to the invertermodule when ordered as a system.Dual Independent MicrocontrollerModulesIf the primary microcontroller module is evercompromised the secondary modulecontinues to provide uninterruptedperformance.Redundant 3.5 kVA “Hot Swappable” <strong>Inverter</strong>ModulesPermits power modules to go off line and bequickly replaced while keeping the load oninverter power.Integrated Electronic Static Transfer SwitchProvides six sigma reliability by rapidlytransferring the load to an alternate AC powersource if DC power to the inverters is not available.Rack Mount Receiver Cabinet with RapidChange Connector <strong>System</strong>Swap components on-line safely and rapidly withno wiring connections and without risking systemperformance.Telecom Grade FilteringThe Alphatran is equipped with a high grade noisefilter system limiting ripple current on the battery towell under required levels, as well as ensuring thatradiated and conducted EMI are kept to safelevels.With Alarm Contacts<strong>System</strong> Single-Pole Double-Pole Single-Pole Double-Pole7 KVA 20 10 10 614 / 21 KVA 24 12 12 8Maximum Number of Circuit Breakers per AC Panel2 Tyco Electronics Power <strong>System</strong>s, Inc.


Data SheetJanuary 2005ALPHATRAN <strong>Inverter</strong> <strong>System</strong>3.5 kVA - 21 kVA Scalable N+1 <strong>Inverter</strong><strong>System</strong> FeaturesDigital Calibration and Self DiagnosticsAny drift in settings is immediately self corrected,eliminating maintenance and calibrationrequirements.Field Replaceable Fan AssembliesFans can be swapped easily without systemdowntime.Open Frame Relay RackAll components are mounted on an industrystandard 26-inch width open frame relay rack withthe entire inverter plant certified for zone 4 seismicinstallations.Web Based Monitoring (future offering)The Alphatran monitoring system providesinverter, maintenance bypass and AC distributionstatus and alarms over a closed network or via theInternet serving up web pages that can be viewedwith a standard browser or via SNMP or dial-upaccess. Accessories include environmentalmonitoring modules and auxiliary inputs to monitorother devices such as leak detection system, roomsecurity or any other dry contact status points.Built to Meet Industry StandardsThe Alphatran inverter is designed to meet thestringent regulatory qualifications demanded bytelecommunications facilities. As well as meetingall major safety standards (including CE and UL),it is one of the only inverters designed to meetNetwork Equipment Building <strong>System</strong> (NEBS)standards - the industry benchmark for productquality and reliability.UL is a registered trademark of UnderwritersLaboratories, Inc.<strong>System</strong> Block DiagramACBypass InputMaintenance BypassDC InputAC DistributionPanel<strong>Inverter</strong> Modules(1 - 6 Modules)3.5 kVA <strong>Inverter</strong>3.5 kVA <strong>Inverter</strong>3.5 kVA <strong>Inverter</strong>3.5 kVA <strong>Inverter</strong>3.5 kVA <strong>Inverter</strong>Static TransferSwitchEMI FilterStatic Transfer Switch AssemblyDry Contact AlarmsRS-232 Comm. PortSNMP / WEBMonitor (optional)Tri-Layer RedundancyDC InputAC InputControllers<strong>Inverter</strong><strong>Inverter</strong><strong>Inverter</strong>Static SwitchAC Output1 Dual Redundant Microcontrollers2 N+1 Redundant <strong>Inverter</strong> Assemblies3 Redundant AC Bypass Source (Static Switch)1233.5 kVA <strong>Inverter</strong>Tyco Electronics Power <strong>System</strong>s, Inc. 3


Data SheetJanuary 2005ALPHATRAN <strong>Inverter</strong> <strong>System</strong>3.5 kVA - 21 kVA Scalable N+1 <strong>Inverter</strong>Alphatran Technical SpecificationsInput VoltageParameter-48 Vdc (40 - 60 Vdc operational range)DescriptionOutput Voltage100, 110, 115, 120, 200, 220, 230, 240 Vac (selectable via external PC configurationsoftware)Output Frequency50 or 60 Hz +/- 0.02% (selectable via external PC configuration software)Output WaveformHigh resolution PWM sine wave<strong>Inverter</strong> TechnologyIGBT PWMLoad/Line Voltage Regulation Less than +/- 1%Static Switch Transfer Time Less than 3 msEfficiency88% typical (on-line mode) to 97% typical (off-line eco mode)Transient Response5% deviation with 1 ms recovery from zero to full loadOverload Capability 120% of continuous rated VA/watts at 20°CShort Circuit Current (SCC) 300% for more than 4 cyclesAudible NoiseLess than 50 dBAEMI EmissionLess than 30 dBrncTotal Harmonic Distortion Less than 1% for linear loads, less than 3% for crest factor loads up to 3:1MonitoringCalibrationOperating TemperatureOperating HumidityOperating AltitudeAgency ApprovalsInstallationFinishLCD with true RMS metering, LED status display, dry contacts, RS-232, optionalSNMP / Web serverDigitally controlled / automatic0 to +55°C (-40 to +75°C shipping)0 to 90% relative, without condensationLess than 10,000 feet without deratingUL/CSA 60950 (listed) and European Standard EN60950, CE, TUV, FCC class Acertified26-inch rack, floor mountedRAL 902 off whiteReceiver<strong>System</strong>Height 1(inches)ReceiverCabinetCapacity(kVA)<strong>Inverter</strong>Capacity(kVA/KW)Number of<strong>Inverter</strong>s(min/max)1. <strong>System</strong> width and depth = 17.0 x 18.5 inches.Power(kVA/KW)DCInput(A max)Output(A at115Vac)Output(A at240Vac)Approx.<strong>System</strong>Weight(lb)MaxBTUSugg.DCBreaker(A)AC InputBreaker(A at 115Vac)AC InputBreaker(A at 240Vac)21.0 7.0 3.5/3.0 1 (1/2) 3.5/3.0 88 29 14.5 114 1807 200 80 4021.0 7.0 7.0/6.0 2 (1/2) 7.0/6.0 176 58 29 182 3614 200 80 4031.5 14.0 7.0/6.0 2 (2/4) 7.0/6.0 176 58 29 182 3614 400 150 8031.5 14.0 10.5/9.0 3 (2/4) 10.5/9.0 265 87 43.5 241 5421 400 150 8031.5 14.0 14.0/12.0 4 (2/4) 14.0/12.0 353 116 58 299 7227 400 150 8042.0 21.0 10.5/9.0 3 (3/6) 10.5/12.0 265 87 43.5 241 5421 600 225 12542.0 21.0 14.0/12.0 4 (3/6) 14.0/12.0 353 116 58 299 7227 600 225 12542.0 21.0 17.5/15.0 5 (3/6) 17.5/15.0 441 145 72.5 357 9034 600 225 12542.0 21.0 21.0/18.0 6 (3/6) 21.0/18.0 529 174 87 418 10,841 600 225 1254 Tyco Electronics Power <strong>System</strong>s, Inc.


Data SheetJanuary 2005ALPHATRAN <strong>Inverter</strong> <strong>System</strong>3.5 kVA - 21 kVA Scalable N+1 <strong>Inverter</strong>Ordering InformationLine to Neutral Power <strong>System</strong>sReceiver <strong>Inverter</strong>Equipped Total Capacity 1Comcode Capacity (kVA) Output (kVA)7.0 / 3.5 kVA <strong>Inverter</strong> <strong>System</strong> 408518884 7 3.5 2 17.0 / 7.0 kVA <strong>Inverter</strong> <strong>System</strong> 408518892 7 7.0 2 214.0 / 7.0 kVA <strong>Inverter</strong> <strong>System</strong> 408518900 14 7.0 4 214.0 / 10.5 kVA <strong>Inverter</strong> <strong>System</strong> 408518918 14 10.5 4 314.0 / 14.0 kVA <strong>Inverter</strong> <strong>System</strong> 408518926 14 14.0 4 421.0 / 10.5 kVA <strong>Inverter</strong> <strong>System</strong> 408518934 21 10.5 6 321.0 / 14.0 kVA <strong>Inverter</strong> <strong>System</strong> 408518942 21 14.0 6 421.0 / 17.5 kVA <strong>Inverter</strong> <strong>System</strong> 408518959 21 17.5 6 521.0 / 21.0 kVA <strong>Inverter</strong> <strong>System</strong> 408518967 21 21.0 6 61. Rack-mounted system with Maintenance Bypass Switch, AC Distribution and 2nd <strong>System</strong> Controller CardLine to Neutral Power <strong>System</strong>s Spare PartsLine to Line Power <strong>System</strong>sLine to Line Power <strong>System</strong>s Spare PartsMax. Numberof <strong>Inverter</strong>s(x3.5 kVA)Spare Parts and Spare Parts Kits Comcode Description3.5 kVA <strong>Inverter</strong> Module 408518975 <strong>Inverter</strong> Module - 3.5 kVALevel 1 Spare Parts Kit 408518983 <strong>Inverter</strong> fan, static transfer switch fan and AC fusesLevel 2 Spare Parts Kit 408518991<strong>Inverter</strong>sIncludedSpare inverter module, inverter fan, static transfer switch fan andAC fusesLevel 3 Spare Parts Kit 408519007<strong>Inverter</strong> module, inverter fan, static transfer switch fan, controller,LCD display, AC fuses and static transfer switch PCBALCD Display 408519015 LCD display/control panel (spare)Static Switch Fan Assembly 408519023 Static switch fan assembly (includes front panel plate<strong>Inverter</strong> Module Fan Assembly 408519031 <strong>Inverter</strong> module fan assembly, (includes front panel plate)Maintenance Bypass Switch 408519049 Maintenance bypass switchMax. Numberof <strong>Inverter</strong>s(x3.5 kVA)Receiver <strong>Inverter</strong>Equipped Total Capacity 1Comcode Capacity (kVA) Output (kVA)7.0 / 3.5 kVA <strong>Inverter</strong> <strong>System</strong> 408533888 7 3.5 2 17.0 / 7.0 kVA <strong>Inverter</strong> <strong>System</strong> 408533896 7 7.0 2 214.0 / 7.0 kVA <strong>Inverter</strong> <strong>System</strong> 408533905 14 7.0 4 214.0 / 10.5 kVA <strong>Inverter</strong> <strong>System</strong> 408533913 14 10.5 4 314.0 / 14.0 kVA <strong>Inverter</strong> <strong>System</strong> 408533921 14 14.0 4 421.0 / 10.5 kVA <strong>Inverter</strong> <strong>System</strong> 408533938 21 10.5 6 321.0 / 14.0 kVA <strong>Inverter</strong> <strong>System</strong> 408533946 21 14.0 6 421.0 / 17.5 kVA <strong>Inverter</strong> <strong>System</strong> 408533954 21 17.5 6 521.0 / 21.0 kVA <strong>Inverter</strong> <strong>System</strong> 408533962 21 21.0 6 61. Rack-mounted system with Maintenance Bypass Switch, AC Distribution and 2nd <strong>System</strong> Controller Card<strong>Inverter</strong>sIncludedSpare Parts and Spare Parts Kits Comcode DescriptionLevel 3 Spare Parts Kit 408533970Includes: Level 2 spares, alarm relay card, LCD display panel,system controller, L-L static switch PCBTyco Electronics Power <strong>System</strong>s, Inc. 5


Data SheetJanuary 2005ALPHATRAN <strong>Inverter</strong> <strong>System</strong>3.5 kVA - 21 kVA Scalable N+1 <strong>Inverter</strong>Ordering Information (continued)Circuit BreakersAll circuit breakers listed here are equipped with alarm contacts.Circuit Breakers (10,000 AIR) Comcode15A Single Pole 40693868820A Single Pole 40693869625A Single Pole 40693870430A Single Pole 40693871240A Single Pole 40693873850A Single Pole 40693875320A Double Pole 406938779Circuit Breakers (22,000 AIR) Comcode15A Single Pole 40724733725A Single Pole 40724738630A Single Pole 40724739415A Double Pole 40725003420A Double Pole 40725004225A Double Pole 40725005930A Double Pole 40725006740A Double Pole 40725008350A Double Pole 40725010970A Double Pole 408519631100A Double Pole 408519601125A Double Pole 408519627Europe, Middle-East and Africa HeadquartersTyco Electronics (UK) LtdTel: +44 1344 469 300, Fax: +44 1344 469 301World Wide HeadquartersTyco Electronics Power <strong>System</strong>s, Inc.3000 Skyline Drive, Mesquite, TX 75149, USA+1-800-843-1797(Outside U.S.A.: +1-972-284-2626)power.tycoelectronics.come-mail: techsupport1@tycoelectronics.comCaribbean-Latin America-Brazil HeadquartersTyco Electronics Power <strong>System</strong>sTel: +56 2 209 8211, Fax: +56 2 223 1477Asia-Pacific HeadquartersTyco Electronics Singapore Pte LtdTel: +65 6416 4283, Fax: +65 6416 4299IndiaTyco Electronics <strong>System</strong>s India Pte LtdTel: +91 80 841 1633 x3001Tyco Electronics Corporation reserves the right to make changes to the product(s) or information contained herein without notice. No liability is assumed as a result of their use orapplication. No rights under any patent accompany the sale of any such product(s) or information.©2005 Tyco Electronics Power <strong>System</strong>s, Inc., (Mesquite, Texas) All International Rights Reserved.Printed in U.S.A.January 2005DS03-004 Rev 56 Tyco Electronics Power <strong>System</strong>s, Inc.