FT100-LV Auto-Detuned Filter banks - Gentec

FT100-LV Auto-Detuned Filter banks - Gentec

FT100-LV Auto-Detuned Filter banks - Gentec

SHOW MORE
SHOW LESS
  • No tags were found...

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

POWER FACTOR CORRECTION IN THEPRESENCE OF HARMONICS<strong>Gentec</strong> <strong>FT100</strong> <strong>Detuned</strong> filters are designedto be used for power factor correction insystems where harmonics are generated.Each step of a detuned filter consists of acapacitor and a reactor connected in series.These components form a series resonantcircuit tuned at a frequency below the lowestharmonic frequency present in the system,normally the 5 th (300Hz).Below the tuned frequency of the resonantcircuit, for example at fundamental frequency(60Hz), the detuned filter is capacitive,generating reactive power. Above the tunedfrequency the detuned filter is inductive, whichmeans that it cannot amplify any commonharmonics, including the 5 th , 7 th and 11 th . Adetuned filter also removes lower orderharmonics from the system to some extent.1324As in conventional capacitor <strong>banks</strong>, the stepsare switched on and off by power factorcontrollers according to the demand of reactivepower.1. DSHI CAPACITORS2. FILTER REACTOR3. CONTROL DEVICES4. SWITCHING DEVICESP.Q. ManagerPage 2 of 4