Fire Alarm Control Panels - Bosch Security Systems

Fire Alarm Control Panels - Bosch Security Systems Fire Alarm Control Panels - Bosch Security Systems

boschsecurity.com
from boschsecurity.com More from this publisher
11.07.2015 Views

34 en | Connection Fire Alarm Control PanelsFigure 5.8: Transformer ConnectionsPrimary:YE yellowWH whiteBK black5.3Option bus wiring requirementsUse 18 AWG (1.2 mm) or larger wire to connect option bus devices to the FACP. The totallength of wire connected to the option bus terminals must not exceed 4 000 ft (1 219 m),regardless of the wire gauge wire used.iNotice!Shared cable is not recommended for option bus, addressable points bus, telephone, or NACwiring.iNotice!To comply with UL, do not share supplementary devices with primary device on the optionbus.Avoid shielded or twisted pair-wire except for special applications where a reduced length ofwiring (approximately 50%) is acceptable for tolerating a harsh electrical environment.The length of wire allowed between the control panel and the last device on a wiring rundepends on the existing current draw on that wiring run. Reducing the number of devices on awiring run allows the individual runs to be longer.2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.

Fire Alarm Control Panels Connection | en 35Add together the alarm existing current draw by all the devices on the wiring run to determinethe maximum allowed distance between the option bus terminals on the control panel and thelast device on the wire run (the device farthest from the control panel).To determine the maximum allowed length for the run, add up the total alarm load for optionbus devices on the wire run. For example, if the total load of option bus devices on aparticular run is 400 mA, the maximum length of the run can be up to 500 ft (152 m). No morethan 4 000 ft (1 219 m) of wire can be connected to the option bus terminals, even if theindividual lengths of the runs are all within limit.For the allowed lengths for18 AWG (1.2 mm) wire, see the following figure:Figure 5.9: 18 AWG cable length for existing current drawiNotice!The graph is for 18 AWG cable!For16 AWG (1.5 mm) wire, cable lengths can be 1.5 times longer. For14 AWG (1.8 mm) wire,cable lengths can be 2.5 times longer. The 4 000 ft (1 219 m) maximum length of connectedwire still applies.Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458

<strong>Fire</strong> <strong>Alarm</strong> <strong>Control</strong> <strong>Panels</strong> Connection | en 35Add together the alarm existing current draw by all the devices on the wiring run to determinethe maximum allowed distance between the option bus terminals on the control panel and thelast device on the wire run (the device farthest from the control panel).To determine the maximum allowed length for the run, add up the total alarm load for optionbus devices on the wire run. For example, if the total load of option bus devices on aparticular run is 400 mA, the maximum length of the run can be up to 500 ft (152 m). No morethan 4 000 ft (1 219 m) of wire can be connected to the option bus terminals, even if theindividual lengths of the runs are all within limit.For the allowed lengths for18 AWG (1.2 mm) wire, see the following figure:Figure 5.9: 18 AWG cable length for existing current drawiNotice!The graph is for 18 AWG cable!For16 AWG (1.5 mm) wire, cable lengths can be 1.5 times longer. For14 AWG (1.8 mm) wire,cable lengths can be 2.5 times longer. The 4 000 ft (1 219 m) maximum length of connectedwire still applies.<strong>Bosch</strong> <strong>Security</strong> System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!