22 en | Installation Fire Alarm Control Panels44.14.1.14.1.24.1.3InstallationInstallation guide for UL Listed systemsFPD‐7024 UL ListingsThe FPD‐7024 is UL Listed for the following:– Commercial Fire Alarm (UL Standard UL864)– Type Service: Auxiliary, Local, Central Station, and Remote Station– Type Initiating: Automatic, Manual, Sprinkler Supervisory, and WaterflowInstall the control panel according to NFPA 72 for Commercial Fire installations.Installation considerationsFailure to install and program the control panel according to the requirements in this sectionvoids the listing mark of Underwriters Laboratories.– The standby battery capacity is 40 Ah at 24 VDC.– The total nominal existing must not exceed 1.25 A in standby or 4 A when in alarm.– The control panel must be mounted indoors and within the protected area.– Grounding must be according to article 250 of the NEC (NFPA 70).– Points must be connected to UL Listed, compatible devices.– The ground wire provided with the enclosure must be connected between the door andthe enclosure using the supplied nuts.– Do not program the ground start feature.– Select Phone Monitoring if the digital alarm communicator transmitter (DACT) feature isused.UL requirementsiNotice!The system must be tested after installation and after any re-programming, including programmingperformed by downloading.When used in UL Listed installations, the control panel must conform to certain programmingrequirements. For a list of the required program entries specific UL Listed installations, seethe Programming features for UL864 table, 49.Commercial Fire Alarm (Central Station [DACT] and Local)Required Accessories– At least one Bosch Security Systems, Inc. Model F220‐P Smoke Detector with an F220Family Base; or another UL Listed compatible smoke detector.– At least one Horn Strobe or Bell (provides 85 dB for UL985 and NFPA 72 requirements;other UL Listed compatible devices listed for regulated 24 V can be used) is required forthis application and must be installed inside the protected area.– Four-wire detectors must be used with UL Listed power supervision devices. Acompatible UL Listed four-wire detector is the Bosch Security Systems, Inc. F220‐P in anF220‐B6 Family Base. A compatible UL Listed relay is the Bosch Security Systems, Inc.D275.– All points must be used with the resistor provided.Report Programming– Program non-supervisory and supervisory reports for those points used.– Program trouble reports.– Set AC Failure Report Delay for a delay of 1 hour to 3 hours.– Set automatic test report frequency to occur at least every 24 hours.2012.08 | 04 | F01U008458 Installation and Operation Manual Bosch Security System, Inc.

Fire Alarm Control Panels Installation | en 23Timer Programming– Program Auto Silence Time for not less than five minutes, or to “0” to disable auto-silenceoperation.Point Programming– For fire points: open = trouble, latching.Alarm Output Programming– Program notification appliance circuits to activate from the appropriate input points.Communications Programming– If used for Central Station Service, select a communication format compatible with thecentral station. Enable monitoring of both phone lines.UL Listed Accessory DevicesD132B Multi-use Reversing Relay ModuleThe D132B is a multi-purpose, fully configurable, smoke power-reversing module for activatingdetectors with local annunciation. The D132B operates both two-wire and four-wire circuitsand also works with Class A or Class B initiating circuits. An alarm latch connection isprovided to allow an initiating loop to be held in alarm after the detector loop power isreversed to activate any sounders. The D132B does not affect compatibility between the FACPand detectors, or the FACP and Notification Appliance Circuits (NACs).See also the D132B Installation Guide for detailed installation instructions for the D132Bmodule. One of the installation options shown in the D132B Installation Guide is also shown inthe following figure:Bosch Security System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458

<strong>Fire</strong> <strong>Alarm</strong> <strong>Control</strong> <strong>Panels</strong> Installation | en 23Timer Programming– Program Auto Silence Time for not less than five minutes, or to “0” to disable auto-silenceoperation.Point Programming– For fire points: open = trouble, latching.<strong>Alarm</strong> Output Programming– Program notification appliance circuits to activate from the appropriate input points.Communications Programming– If used for Central Station Service, select a communication format compatible with thecentral station. Enable monitoring of both phone lines.UL Listed Accessory DevicesD132B Multi-use Reversing Relay ModuleThe D132B is a multi-purpose, fully configurable, smoke power-reversing module for activatingdetectors with local annunciation. The D132B operates both two-wire and four-wire circuitsand also works with Class A or Class B initiating circuits. An alarm latch connection isprovided to allow an initiating loop to be held in alarm after the detector loop power isreversed to activate any sounders. The D132B does not affect compatibility between the FACPand detectors, or the FACP and Notification Appliance Circuits (NACs).See also the D132B Installation Guide for detailed installation instructions for the D132Bmodule. One of the installation options shown in the D132B Installation Guide is also shown inthe following figure:<strong>Bosch</strong> <strong>Security</strong> System, Inc. Installation and Operation Manual 2012.08 | 04 | F01U008458

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!