<strong>F<strong>AN</strong></strong> <strong>COIL</strong> <strong>UNITS</strong>! 12 models available with cooling power ranging from 1 to11 kW! 6 construction versions:- F L wall-mounted, with cabinet, vertical air flow- F A wall-mounted, with cabinet, front inclined air flow- F U floor/ceiling mounted with cabinet- F C vertical/horizontal recess mounted- F B floor mounted with low cabinet- CLASSIC wall mounted with cabinet! Wide range of accessoires including microprocessor controlpanelsThe high-quality materials and the great care taken in theassembly of the main constructive components grant theperformance reliability and the acoustic comfort of thenew Galletti fan coils.www.galletti.it


Since 30 years in the fan coils production, GallettipresentsNew rounded shapes and newcolors that are perfectlyintegrated with currentinterior design criteria, fullycomplying with architecturalrequirements.New control panels forcontrolling and regulatingthe temperature by meansof a microprocessor-basedsystem, which adapts theoperation of the fan coilautomatically when roomconditions change.The construction concept allows to to standardize the models for vertical mounting and those forhorizontal mounting. The range consitsts of 5 versions for wall installation at sight, floor /cealing,recessed wall/cealing and floor recessed installation.Low body recessed models are available upon request.Constructive featuresFLWall-mounted, with cabinet,vertical air outletFAWall-mounted, with cabinet,inclined air outletFUFloor standing and ceilingmounted,with cabinetcomplete with air outlet grillesand air intake grilles with filterFCVertical and horizontalrecessed, bearing structuremade of thermally insulatedgalvanized steel sheet.FBLow-body floor standing,height 438 mm, cabinet withair outlet grilles and air intakegrilles with filter.üCover cabinet made of thick steel sheet panel, ABSside panels, air outlet grilles (orientable 180°) andair suction grilles (versions FU and FB) made of ABS.The side doors allow access to the technical spaceand to the control panel (accessory).üBearing structure made of thick galvanized steelsheet, insulated with self-extinguishing Class 1 heatinsulatingpanels.The models for horizontal-installation include a largetray for collecting the condensate.The models fitted with the cabinet come with aninstallation kit (wall-screws).üHigh-efficiency heat exchanger, made of copper pipeand aluminium fins fixed to the pipes by means ofmechanical expansion, equipped with brass manifoldsand air purge valve.The units normally come with water connection onleft side,but the heat exchanger, and can be turned,on the field, by 180°.ü3-speed electric motor installed on vibration-dampingsupports, complete with built-in capacitor and thermalprotection for the windings.üWashable air filter made of beehive polypropylene,installed on galvanized sheet frame with safety grille,easy to remove for maintenance.In the FU version the air filters are inserted in theintake grilles on the front panel of the cover cabinet.ü Double-intake centrifugal fans,statically and dynamically balancedand coupled directly to the electricmotor; made of:- antistatic ABS with staggeredblades and wing-shaped profile- aluminium (models 1, 5, 6, 10, 11and 12)


Fan coil éstro - AccessoriesOur wide range of accessoires completes these terminal units in order to suit all kind of installationrequirement.The standard units are supplied without the control panel.Control Panels and ThermostatsACCESSORY DESCRIPTIONCBIn-built speed selectorTBIn-built control with speed selector and electromechanical thermostatTIBIn-built control with speed selector, thermostat and summer-winter selectorMICRO Microprocessor in-built control for the automatic control of the fan coilMICROPRO Microprocessor in-built control for the automatic control of the fan coil, valves and electric heaterSWWater temperature electronic probe for MICRO, MICRO-D and MICROPRO-D controlsCSBIn-built control for the proportional opening and closing of the SM motor driven air louverTCFan stop thermostat: electromechanical thermostat for minimum water temperature during heating modeKPPower interface for connection of up to 4 fan coils to a single control panelCDFlush wall-mounted speed selectorCDE Wall-mounted speed selectorTDWall mounted control with speed selector, electromechanical thermostat and summer winter selectorTDCWall mounted control with speed selector and electromechanical thermostatTD4T Wall mounted control with speed selector , electromechanical thermostat and summer winter selector (heating/cooling)for 2-4 pipe systems with valvesMICRO-D Microprocessor wall mounted control for the automatic control of the fan coilMICROPRO-D Microprocessor wall mounted control for the automatic control of the fan coil,valves and electric heaterCSD Wall mounted control for proportional opening and closing of the motor driven air louverTAElectromechanical room thermostatTA2Electromechanical room thermostat with summer winter selectorFeet and Covering PanelsACCESSORY DESCRIPTIONZAPair of covering feetZAG Pair of covering feet with front grillesZLPair of covering feetZLGPair of covering feet with front grillesDSupporting bracketsPVLRear painted panel for vertical-mounting fan coils with cabinetPVA Rear painted panel for vertical-mounting fan coils with cabinetPVB Rear painted panel for vertical-mounting fan coils with cabinetPHRear painted panel for horizontal-mounting fan coils with cabinetAlluminium GrillesACCESSORY DESCRIPTIONGE+C Anodized aluminium grille for fresh air intake, complete with counter-frameGEF+C Anodized aluminium grille for air intake, complete with counter-frameGM+C Double row anodized aluminium air outlet grille, complete with counter-frameFresh Air Intake LouverACCESSORY DESCRIPTIONSManual fresh air intake air louverSMMotor driven fresh air intake louver3 Way Valves and Drip TraysACCESSORY DESCRIPTIONVK S 3-way valve with ON/OFF electro-thermal motor and hydraulic assembly kit for the standard heat exchangerVK DF 3-way valve with ON/OFF electro-thermal motor and hydraulic assembly kit for the DF heat exchangerBVAuxiliary condensate tray for vertical-mounting fan coilsBHAuxiliary condensate tray for horizontal-mounting fan coilsAdditional 1 Row Heat ExchangerACCESSORY DESCRIPTIONDF1-row additional heat exchanger for 4-pipe systems (hot water circuit)Additional Electric HeaterACCESSORY DESCRIPTIONREElectric heater with assembly kit, safety devices and power relay box


classicWall mounted with cabinet.9 models with cooling powersfrom 1 to 4,8 kW- sheet metal componentscolor RAL 9010- ABS components colorPantone “Warm Gray2U”Galletti, strong of the success of èstro line,introduces the version "classic".It is studied with pastel and soft degrading tonesof color in order to integrate with furnishings oftraditional type and in all those architectureswhere the warm colors and elegant shapes makeof "estro classic" a real furnishings complement.9 models (from C1L to C9L) proposed for wallmountingüThe unit base consist of galvanized steel frame stronglythickness and insulated with thermo-isolating panelsflame- retardants class 1üThe high efficiency heat exchanger is made of coppertubes and aluminium fins blocked to the tubes bymeans of mechanical expansion, it is equipped withbrass collectors and breather valve.The heat exchanger, normally mounted with lefthandconnection, can be turned on 180°.üThree speed electric motor mounted on antivibratingsupports, complete with in-built permanent condenserand winding thermal protection.üCentrifugal balanced fans with double aspirationstatically and dynamically coupled directly to theelectric motor; they are made of:-antistatic ABS with airfoil designed shovelsand offset modules;-aluminum (models 1,5,6).üHoneycomb regenerable air filter in polypropylene,it is mounted on a galvanized metal sheet frame withprotection net, easy to remove for maintenanceoperations.üControl panels are available as accessoire.A range of accessories is dedicated to the Estro Classic line, which is definited bythe paint “Classic”.CB-CTB-CTIB-CCSB-CTCKPDFBVZCZCGPVCVK SVK DFGE+CSCSM-CIn-built speed selectorControl Panels and ThermostatsIn-built control with speed selector and electromechanical thermostatIn-built control with speed selector, thermostat and summer-winter selectorIn-built control for the proportional opening and closing of the SM-C motor driven air louverFan stop thermostat: electromechanical thermostat for minimum water temperature during heating modePower interface for connection of up to 4 fan coils to a single control panelAdditional 1 Row Heat Exchanger1-row additional heat exchanger for 4-pipe systems (hot water circuit)Auxiliary condensate trayAuxiliary condensate tray for vertical-mounting fan coilsFeet and Covering PanelsPair of covering feetPair of covering feet with front grillesRear Painted PanelsRear painted panel for vertical-mounting fan coils with cabinet3 Way Valves ON/OFF Motorized3-way valve with ON/OFF electro-thermal motor and hydraulic assembly kit for the standard heat exchanger3-way valve with ON/OFF electro-thermal motor and hydraulic assembly kit for the DF heat exchangerAlluminium GrillesAnodized aluminium grille for fresh air intake, complete with counter-frameFresh Air Intake LouverManual fresh air intake air louverMotor driven fresh air intake louver


Fan coils éstro rated technical datafan coils éstro and classic Fan speed F 1 F 2 F 3 F 4 F 5 F 6 F 7 F 8 F 9 F 10 F 11 F 12Total cooling capacity (high) kW 1,15 1,54 1,74 2,09 2,42 2,93 3,51 4,33 4,77 6,71 8,71 10,95Sensible cooling capacity (high) kW 0,87 1,20 1,30 1,51 1,88 2,11 2,75 3,15 3,65 4,91 6,38 8,07Water flow l/h 197 264 298 359 415 503 602 743 818 1152 1494 1879Water pressure drop kPa 7 13 14 13 16 11 12 12 14 12 19 31Heating capacity (high) kW 2,68 3,71 4,11 4,76 5,47 6,46 8,21 9,57 10,85 14,45 18,83 24,67Water flow l/h 235 325 631 418 480 567 720 840 952 1268 1652 2164Water pressure drop kPa 8 15 15 13 16 11 13 12 14 11 17 30DF heating capacity (4 pipe) (high) kW 1,89 2,23 2,32 2,30 3,27 3,26 4,80 5,04 5,30 7,91 9,30 12,14Water flow l/h 166 196 204 202 287 286 421 442 465 694 816 1065Water pressure drop kPa 5 6 7 7 3 2 4 5 5 16 21 39Standard heat exchanger water connections in 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 3/4 3/4 3/4Standard heat exchanger water content dm 3 0,5 0,5 0,5 0,7 0,7 1,0 1,0 1,4 1,4 2,1 2,1 2,6DF heat exchanger water connections in 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2DF heat exchanger water content dm 3 0,2 0,2 0,2 0,2 0,3 0,3 0,4 0,4 0,4 0,6 0,6 0,9Power supply V - ph - Hz 230 - 1 50Maximum power input W 37 36 46 46 62 62 87 87 89 182 244 310Maximum current absorption A 0,16 0,16 0,21 0,21 0,27 0,27 0,39 0,39 0,38 0,80 1,12 1,52(high) m 3 /h 231 319 344 344 442 442 640 706 785 1011 1393 1850Air flow (med) m 3 /h 189 233 271 271 341 341 450 497 605 771 1022 1317(low) m 3 /h 149 178 211 211 241 241 320 361 470 570 642 1010(high) dB/A 44 47 52 52 50 50 54 55 59 59 66 71Sound power (med) dB/A 36 39 44 44 44 44 47 48 52 52 58 63(low) dB/A 30 34 36 36 38 38 38 40 44 44 48 57(high) dB/A 39 42 47 47 45 45 49 50 54 54 61 66Sound pressure (med) dB/A 31 34 39 39 39 39 42 43 47 47 53 58(low) dB/A 25 29 31 31 33 33 33 35 39 39 43 52Low body fan coils éstro FB rated technical dataFan coil éstro FB Fan speed F 1 B F 2 B F 3 B F 4 B F 5 B F 6 B F 7 B F 8 B F 9 BTotal cooling capacity (high) kW 1,07 1,43 1,62 1,94 2,25 2,72 3,26 4,03 4,44Sensible cooling capacity (high) kW 0,81 1,12 1,21 1,40 1,79 1,97 2,61 2,95 3,49Water flow l/h 184 245 278 333 386 467 559 692 762Water pressure drop kPa 7 12 13 12 14 10 11 11 13Heating capacity (high) kW 2,49 3,45 3,82 4,43 5,09 6,01 7,64 8,90 10,09Water flow l/h 218 303 335 388 447 527 670 781 885Water pressure drop kPa 7 13 13 12 14 9 11 10 13Heat exchanger water connections in 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2Heat exchanger water content liters 0,5 0,5 0,5 0,7 0,7 1,0 1,0 1,4 1,4Power supply V - ph - Hz 230 - 1 - 50Maximum power input W 37 36 46 46 62 62 87 87 89Maximum current absorption A 0,16 0,16 0,21 0,21 0,27 0,27 0,39 0,39 0,38(high) m3/h 231 319 344 344 442 442 640 706 785Air flow (med) m3/h 189 233 271 271 341 341 450 497 605(low) m3/h 149 178 211 211 241 241 320 361 470(high) dB/A 44 47 52 52 50 50 54 55 59Sound power (med) dB/A 36 39 44 44 44 44 47 48 52(low) dB/A 30 34 36 36 38 38 38 40 44(high) dB/A 39 42 47 47 45 45 49 50 54Sound pressure (med) dB/A 31 34 39 39 39 39 42 43 47(low) dB/A 25 29 31 31 33 33 33 35 39The aforesaid performance is related to the following conditions:- cooling: water temperature 7/12°C, air temperature 27°C dry bulb, 19°C wet bulb.(corresponding to 47% relative humidity)- heating: water temperature 70-60°C, air temperature 20°C.- sound power measured according to EN 23741 and EN 23742.- sound pressure calculated at a distance of 1 m, directional factor 4.


Fan coil éstro - Overall dimensionsclassic / F Lwall-mounted with cabinet,vertical air outletLEGEND1 Space for hydraulic connections4 Standard heat exchanger hydraulic connections2 Slots for wall-mounting4DF DF 1-row additional heat exchanger hydraulic connections3 Space for electrical connections5 Condensate dischargeMAP= C=D4 DF44 DF12391 308564RENGH45FLBCLASSIC F L A B C D E F G H L M N P R1 - 4 1 - 4 774 226 498 51 458 163 263 149 198 187 335 99 4865 - 6 5 - 6 984 226 708 51 458 163 263 149 198 187 335 99 4867 - 9 7 - 9 1194 226 918 51 458 163 263 149 198 187 335 99 48610 - 11 1404 251 1128 48 497 185 259 155 220 195 348 120 47812 1614 251 1338 48 497 185 259 155 220 195 348 120 478F A wall-mounting with cabinet, inclined air outletLEGEND1 Space for hydraulic connections4 Standard heat exchanger hydraulic connections2 slots for wall-mounting4DF DF 1-row additional heat exchanger hydraulic connections3 Space for electrical connections5 Condensate dischargeMKAP= C=D4 DF44 DF12391 308556RENGH45FLBF A A B C D E F G H K L M N P R1 - 4 774 228 498 53 458 166 263 149 145 201 189 334 102 4865 - 6 984 228 708 53 458 166 263 149 145 201 189 334 102 4867 - 9 1194 228 918 53 458 166 263 149 145 201 189 334 102 48610 - 11 1404 253 1128 50 497 188 259 155 170 223 196 348 121 47812 1614 253 1338 50 497 188 259 155 170 223 196 348 121 478F B Low body fan coilsLEGEND1 Space for hydraulic connections2 slots for wall-mounting3 Space for electrical connections4 Standard heat exchangerhydraulic connections5 Condensate dischargeA251=C=38134235 270438370227219621127112445F B A C1 - 4 774 4985 - 6 984 7087 - 9 1194 918


Fan coil éstro - Overall dimensionsF Ufloor/ceilingwith cabinetLEGEND1 Space for hydraulicconnections2 Slots for wall-mounting3 Space for electricalconnections4 Standard heat exchangerhydraulic connections4DF DF 1-row additional heatexchanger hydraulicconnections5 Condensate dischargeA= C=1391 30822564RENGPDMH4 DF44 DF45FLBZS5TF U A B C D E F G H L M N P R S T Z1 - 4 774 226 498 51 458 163 263 149 198 187 335 99 486 208 198 2465 - 6 984 226 708 51 458 163 263 149 198 187 335 99 486 208 198 2467 - 9 1194 226 918 51 458 163 263 149 198 187 335 99 486 208 198 24610 - 11 1404 251 1128 48 497 185 259 155 220 195 348 120 478 234 208 27112 1614 251 1338 48 497 185 259 155 220 195 348 120 478 234 208 271F C -vertical/horizontalconcealed installationULEGEND2 Slots for wall-mounting4 Standard heat exchanger hydraulicconnections4DF DF 1-row additional heat exchangerhydraulic connections5 Condensate discharge6 Air outletQ7A= C=291 308535VY20DPBM7 Air intake4 DF44 DFRENGH4525FL1136S5TF C A B C D E F G H L M N P Q R S T U V W1 - 4 584 224 498 51 458 163 263 149 198 187 335 99 189 486 208 198 436 464 615 - 6 794 224 708 51 458 163 263 149 198 187 335 99 189 486 208 198 646 674 617 - 9 1004 224 918 51 458 163 263 149 198 187 335 99 189 486 208 198 856 884 6110 - 111214 249 1128 48 497 185 259 155 220 195 348 120 215 478 234 208 1066 1094 6712 1424 249 1338 48 497 185 259 155 220 195 348 120 215 478 234 208 1276 1304 67


Microprocessor control panelsIn-built or wall installationMICROMICROPROManufactured in 4 versions, the controls of the MICRO series make the estro fan coilsa completely automatic unit that controls and regulates the room temperature by simplysetting the desired comfort temperature.The numerous possible functions allow its use in any plant-engineering solution complyingwith the requirements of designers and installers.AUTOAUTOMATIC <strong>F<strong>AN</strong></strong> SPEED SELECTIONThe fan speed is changed automatically according to the difference between theset temperature and the real room temperature so that the desired comfortconditions are attained and maintained.COOLING/HEATING MODE SELECTIONThe cooling/heating mode selection can be set in 3 different way:manual, directly on the panelthe operating mode is selected by the end user directly by means of the selectionbuttonremote controlthe control panels may be connected to a remote-control selection system(centralized)automaticthe microprocessor selects the heating or cooling operating mode automatically,according to the water or air temperature, with no other operation.COMBINED OPERATION WITH BOILER <strong>AN</strong>D CHILLERThe water probe relates the operation of the fan coil to that of the boiler andchiller, according to the water temperature, in order to simplify the control ofthe whole system and limit consumption.TIMER FUNCTIONThe timer function ensures the real detection of the air room temperature and starts up the fan, only in cooling mode, at regularintervals when the room temperature has reached the level set on the thermostat.VALVES CONTROLCombining the control both of the regulating valves on water side (ON-OFF) and the fan, the control panel ensures optimal roomtemperature setting and energy saving.ELECTRIC HEATER CONTROLThe control panel can control the electric heater installed on the fan coil both for substitution and integration operation.The stopping of the fan is delayed to prevent overheating problem.INPUT FOR EXTERNAL CONTACTSThe control is equipped with an input for signals coming from external contacts (reed contact, remote ON/OFF, etc.) that may eitherenable or disable the unit’s operation.MICRO MICRO - D MICROPRO MICROPRO - DInstallation on board wall mounted on board wall mountedCode EYMICRO EYMICROD EYMICROPRO EYMICROPROD2 pipe X X X X4 pipe X XFan speed control manual X X X Xautomatic X X X XMode selection manual on board X X X Xremote X Xautomatic X X X XValves control (2 and 4 pipe) X XElectric heater control X XWinter and summer enabling X X X XTimer function X XInput for external contacts X XSelectable neutral zone X XVia Romagnoli 12/a 40010 Bentivoglio (BO)Tel. 051 8908111 - Fax 051 8908122E U R O V E N TCERTIFIED PERFORM<strong>AN</strong>CEGalletti is partecipatingto the Euroventcertification programme1115FC66000825 - rev 03