11.07.2015 Views

Impact of EPA Drinking Water Stage 2 Disinfectant and Disinfectant ...

Impact of EPA Drinking Water Stage 2 Disinfectant and Disinfectant ...

Impact of EPA Drinking Water Stage 2 Disinfectant and Disinfectant ...

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Chemical Addition28• Goal: 5:1 weight ratio to producemonochloramines• Target chloramine residual: 3.0 mg/L• Requires dosing: 3.0 mg/L Cl 2 <strong>and</strong> 0.60 mg/L NH 3• Daily production: 10 MG• Weight <strong>of</strong> water: 8.34 lbs./gal• Chlorine: 100% strength gas• Ammonia: 100% strength gas• Add 250 lbs. <strong>of</strong> chlorine <strong>and</strong> 62 lbs. <strong>of</strong>ammonia to produce the target results.Disinfection

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!