DSE 5xxx Configuration Software Manual4.1.4 ALARM STATUS TABIf the Status Display option is selected the display will show:ECU error messages (when available) aredisplayed on the alarms page as shown above.Examples of SPN / FMI numbers, takenfrom the Volvo Penta TAD12 manual are :SPN 110 – Engine coolant temperatureFMI 0 – Out of rangeFMI 3 – Above normalFMI 4 – Below normalNOTE:- ‘Hovering’ the mouse cursor over the SPN/FMI numbers wil display theJ1939 messages where appropriate.For further details on these code meanings, refer to the ECU instructions provided bythe engine manufacturer.68DSE 5xxx Configuration software ISSUE 2 02/07/04 AM