11.07.2015 Views

DEEP SEA ELECTRONICS PLC - Home Mega Global Solution

DEEP SEA ELECTRONICS PLC - Home Mega Global Solution

DEEP SEA ELECTRONICS PLC - Home Mega Global Solution

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

DSE 5xxx Configuration Software Manual4.1.4 ALARM STATUS TABIf the Status Display option is selected the display will show:ECU error messages (when available) aredisplayed on the alarms page as shown above.Examples of SPN / FMI numbers, takenfrom the Volvo Penta TAD12 manual are :SPN 110 – Engine coolant temperatureFMI 0 – Out of rangeFMI 3 – Above normalFMI 4 – Below normalNOTE:- ‘Hovering’ the mouse cursor over the SPN/FMI numbers wil display theJ1939 messages where appropriate.For further details on these code meanings, refer to the ECU instructions provided bythe engine manufacturer.68DSE 5xxx Configuration software ISSUE 2 02/07/04 AM

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!