Technische Information Technical information<br />

und Bedienungsanleitung and operating instruction<br />

Ausgabe: 1 Gültig ab: 13.09.2005 Version: 1 valid from: 13.09.2005<br />

N L<br />

<strong>STG</strong><br />

BEIKIRCH<br />

Netzmodul MZ2 NM16A<br />

Power supply unit MZ2 NM16A<br />

OK<br />

Batt. OUT<br />

F 1234567<br />

+<br />

-<br />

BUS<br />

Netzmodul MZ2 NM16A<br />

Power supply unit MZ2 NM16A<br />

Zur Spannungsversorgung der MZ2-Module und der dazugehörigen Antriebe<br />

Power supply for MZ2 modules and the corresponding drives<br />

Temp.<br />

Sensor<br />

Das Netzmodul dient als Komponente der<br />

Modulzentrale zur Versorgung der MZ2<br />

und der Aktorkreise mit max. 16 A Nennlast<br />

aus einem 230 V AC Versorgungsnetz.<br />

Zum Betrieb von Antrieben mit<br />

Abschaltung über Strommessung liefert<br />

das Netzteil kurzzeitig einen höheren<br />

Strom aus den angeschlossenen Akkus.<br />

Das Modul verfügt über eine<br />

temperaturgeführte Akkuladeschaltung<br />

und Überwachungs-funktionen für<br />

Ausgangsspannung, -strom, Temperatur,<br />

Akkutemperatur, Akku-spannung,<br />

Akkutiefentladung und Netz-versorgung.<br />

Bei Netzausfall wird die angeschlossene<br />

Modulzentrale unterbrechungsfrei<br />

versorgt. Das Netzmodul kann auch mit<br />

eingeschränktem Funktionsumfang ohne<br />

Akkus und ohne Akkutemperaturfühler<br />

betrieben werden.<br />

Jedes Modul erhält eine über einen<br />

Drehkodierschalter einstellbare Adresse<br />

zwischen 1 und 15. Somit können in einer<br />

MZ2 bis zu 15 Module dieses Typs<br />

betrieben werden.<br />

Zur Signalisierung von Fehlern und<br />

Betriebszuständen dienen zwei integrierte<br />

LEDs. Fehler wie Netz- oder Akkuausfall<br />

werden über den internen Anlagenbus an<br />

die MCU der Modulzentrale und darüber<br />

hinaus an die angeschlossenen RWA-<br />

Taster weitergeleitet und dort signalisiert.<br />

Das Modul ist mit einer Übertemperaturabschaltung<br />

ausgestattet und bedingt<br />

kurzschlussfest.<br />

Besonderheiten<br />

Schaltnetzteil 24 V, Stromabgabe 16 A<br />

kaskadierbar mit weiteren Netzmodulen<br />

mit je 16 A<br />

integrierter Adresswahlschalter<br />

temperaturüberwachte Akku Ladeeinrichtung<br />

kompakte Bauform<br />

Betriebsanzeige<br />

Schnapp Montage auf 35 mm Montageschiene<br />

Weiterleitungen von Meldungen auf<br />

den MZ2-Datenbus<br />

TÜV Bauart geprüft<br />

<strong>STG</strong><br />

BEIKIRCH<br />

Sicherheit auf<br />

höchstem Niveau<br />

Anwendung Application<br />

The power supply unit is the component of<br />

the module centre for supplying the MZ2<br />

and the actuator circuits with a maximum<br />

16 A rated load. The power supply unit<br />

momentarily supplies a higher power<br />

rating from the storage batteries that are<br />

connected to operate drives with load<br />

switch off. The module has a temperature<br />

guided battery load switch and monitoring<br />

function for output voltage, battery voltage,<br />

total battery discharge and power supply.<br />

In the event of a power outage, the<br />

module centre connected is supplied by<br />

the battery without interruption. The power<br />

supply unit can also be operated with a<br />

limited function scope without batteries<br />

and without battery temperature probe.<br />

Each module receives an address that can<br />

be set between 1 and 15 via a rotary<br />

coding switch. Consequently up to 15<br />

modules of this type can be operated in<br />

one MZ2.<br />

Two integrated LEDs are used for<br />

signalling errors and operating modes.<br />

Errors such as power or battery failure are<br />

passed onto the MCU in the module<br />

centre and also to the SHE-button<br />

connected and signalled there via the<br />

internal system bus.<br />

The module is fitted with an excess<br />

temperature cut off and conditional short<br />

circuit resistant.<br />

Special units<br />

24 V switch power pack, current delivery<br />

16 A<br />

can be daisy-chained with further<br />

power supply units 16 A each<br />

temperature monitored battery charging<br />

device<br />

operating indicator<br />

snap assembly on assembly rail<br />

compact design<br />

transmission of messages to the MZ2<br />

data bus<br />

TÜV type approved<br />

Diese Bedienungsanleitung für späteren Gebrauch bzw. Wartung aufbewahren. Please keep these operating instruction for future reference and maintance.<br />

Datei:<br />

Änderungen dienen dem technischen Fortschritt und bleiben vorbehalten. Abbildungen unverbindlich. Subject to technical modifications. Diagram is not binding.<br />

Ti_MZ2_NM16A_dt_engl.cdr<br />

Art.Nr. 24999979<br />

D<br />

GB


2<br />

Netzanschluss<br />

mains supply<br />

230 V / 50 Hz<br />

OK<br />

N L<br />

A B C D E<br />

NM 16A<br />

Netzsicherung unterhalb<br />

der Gehäuseabdeckung<br />

mains fuse below<br />

housing<br />

OK<br />

Klemmblock 4<br />

Terminal block 4<br />

A B C D E<br />

(F1)<br />

+<br />

-<br />

12V Akku +<br />

12V Akku -<br />

12V Akku<br />

12 V Akku<br />

Klemmblock 2<br />

Terminal block 2<br />

A<br />

B<br />

C<br />

D<br />

E<br />

(F2)<br />

Klemmblock 3<br />

Terminal<br />

block 3<br />

+ Gruppe 4 (F6)<br />

- GND<br />

+ Gruppe 3 (F5)<br />

- GND<br />

+ Gruppe 2 (F4)<br />

- GND<br />

+ Gruppe 1 (F3)<br />

- GND<br />

24 V Versorgung der Motorkreise<br />

max.8AjeGruppe, pro Netzmodul<br />

max. 16 A<br />

24 V power supply of motor circuits<br />

max. 8 A per group, max. 16 A per<br />

power supply unit<br />

Anschlüsse<br />

Die Lage der Klemme und die<br />

Verdrahtung mit den MZ2-Modulen<br />

entnehmen Sie bitte dem Verdrahtungsund<br />

Klemmenplan.<br />

Achtung: Jede Klemme ist mit<br />

maximal 12 A belastbar!<br />

Um die MZ2 Modulversorgung<br />

abzuschalten, muss der Stecker von<br />

Klemmblock 4 MZ2-Bus oder die<br />

Sicherung F1 abgezogen werden.<br />

Das Modul darf nur als Netzversorgung<br />

einer MZ2 Modulzentrale verwendet<br />

werden.<br />

Sicherungen<br />

Die Lage der Sicherungen entnehmen Sie<br />

bitte dem Verdrahtungs- und Klemmenplan.<br />

F1: 20 A Akkusicherung<br />

F2: 3A MZ2 Modulversorgung<br />

F3 - F6: 7,5 A (max.)<br />

Aktorenkreise 1- 4 (angepasst an die<br />

Aktoren, in Summe =16 A)<br />

Achtung: Ist an einem Aktorenkreis<br />

keine Last angeschlossen, so ist die<br />

Sicherung zu entfernen, sonst wird ein<br />

Sicherungsfehler angezeigt (siehe<br />

Blinkcodes).<br />

Klemmblock Batt.|OUT<br />

Klemme 1: Akku Anschluss (+)<br />

Klemme 2: Ausgang Aktorkreis 1 (+)<br />

[Gruppe 1]<br />

Klemme 3: Ausgang Aktorkreis 2 (+)<br />

[Gruppe 2]<br />

Klemme 4: Ausgang Aktorkreis 3 (+)<br />

[Gruppe 3]<br />

Klemme 5: Ausgang Aktorkreis 4 (+)<br />

[Gruppe 4]<br />

Klemme 6: Akku Anschluss (-)<br />

Klemme 7: Ausgang Aktorkreis 1 (-)<br />

[Gruppe 1]<br />

Klemme 8: Ausgang Aktorkreis 2 (-)<br />

[Gruppe 2]<br />

Klemme 9: Ausgang Aktorkreis 3 (-)<br />

[Gruppe 3]<br />

Klemme 10: Ausgang Aktorkreis 4 (-)<br />

[Gruppe 4]<br />

Klemmblock 2<br />

Klemme L: Netz (L1)<br />

Klemme N: Netz (N)<br />

Klemme PE: Netz (PE)<br />

Klemmblock 3:<br />

Akku Temperaturfühler [Temp. Sensor]<br />

Klemmblock 4:<br />

MZ2 BUS Anschluss [BUS]<br />

Klemme A: + 27 V [A]<br />

Klemme B: GND [Gnd]<br />

Klemme C: Reset [Bus1]<br />

Klemme D: Data [Bus2]<br />

Klemme E: Clock [Bus3]<br />

Adresswahlschalter<br />

Stellung 0: Modul abgeschaltet.<br />

Stellung 1-F(Hex.): Moduladressen 1 bis<br />

15 eingestellt (siehe PC Software<br />

Beschreibung) .<br />

Connections<br />

Please see the wiring and terminal plan for<br />

the position of the terminals and the wiring<br />

with the MZ2 modules.<br />

Warning: Each terminal can be<br />

loaded with a maximum of 12 A!<br />

To switch the MZ2 module supply off the<br />

plug must be removed from the terminal<br />

block 4 MZ3-bus or the F2 fuse. The<br />

module may only be used as power<br />

supply for a MZ2 module centre.<br />

Fuses<br />

Please see the wiring and terminal plan for<br />

the fuse positions.<br />

F1: 20 A Battery fuse<br />

F2: 3 A MZ2 module supply<br />

F3 - F6: 7.5 A (max.)<br />

Actuator circuits 1-4( adjusted to the<br />

actuators, in total =16 A)<br />

Warning:<br />

If no load is connected to<br />

an actuator circuit, the fuse is to be<br />

removed;<br />

otherwise a fuse error is<br />

displayed ( see<br />

flashing codes).<br />

Terminal block Batt.|OUT<br />

Terminal 1: Battery connection (+)<br />

Terminal 2: Output actuator circuit 1 (+)<br />

[Group 1]<br />

Terminal 3: Output actuator circuit 2 (+)<br />

[Group 2]<br />

Terminal 4: Output actuator circuit 3 (+)<br />

[Group 3]<br />

Terminal 5: Output actuator circuit 4 (+)<br />

[Group 4]<br />

Terminal 6: Battery connection (-)<br />

Terminal 7: Output actuator circuit 1 (-)<br />

[Group 1]<br />

Terminal 8: Output actuator circuit 2 (-)<br />

[Group 2]<br />

Terminal 9: Output actuator circuit 3 (-)<br />

[Group 3]<br />

Terminal 10: Output actuator circuit 4 (-)<br />

[Group 4]<br />

Terminal block 2<br />

Terminal L: Mains supply (L1)<br />

Terminal N: Mains supply (N)<br />

Terminal PE: Mains supply (PE)<br />

Terminal block 3:<br />

Battery temperature probe [Temp. Sensor]<br />

Terminal block 4:<br />

MZ2 BUS connection [BUS]<br />

Terminal A: + 27 V [A]<br />

Terminal B: GND [Gnd]<br />

Terminal C: Reset [Bus1]<br />

Terminal D: Data [Bus2]<br />

Terminal E: Clock [Bus3]<br />

Address selector switch<br />

Position 0: Module switched off.<br />

Position 1-F(Hex.): Module addresses 1<br />

to 15 set (see: PC Software description).


N L<br />

NM 16A<br />

OK<br />

OK<br />

Address<br />

F 1 2 3 4 5 6<br />

Batt. Out<br />

+<br />

Bus -<br />

Temp.<br />

Sensor<br />

Klemmblock 1<br />

Terminal block 1<br />

+ Gruppe 4 (F6)<br />

- GND<br />

+ Gruppe 3 (F5)<br />

- GND<br />

+ Gruppe 2 (F4)<br />

- GND<br />

+ Gruppe 1 (F3)<br />

- GND<br />

24 V Versorgung der Motorkreise<br />

max.8AjeGruppe, pro Netzmodul<br />

max. 16 A<br />

24 V power supply of motor circuits<br />

max. 8 A per group, max. 16 A per<br />

power supply unit<br />

Bedien- & Anzeigeelemente Control-a.indicator panels<br />

LED „OK“ OK LED “OK” OK<br />

Farbe: Grün, Funktion: Betriebsanzeige, Colour: Green, function: Operating display,<br />

Netzversorgung ist angeschaltet.<br />

power supply is switched on.<br />

LED leuchtet, wenn das Modul im System LED alight, when the module is connected<br />

eingebunden ist und über eine gültige in the system and has a valid initiation.<br />

Initialisierung verfügt.<br />

LED flashes (short pulses), when the<br />

LED blinkt (kurze Pulse), wenn sich das module is in emergency mode. The<br />

Modul im Notbetrieb befindet. Die Anlage system is supplied by the batteries<br />

wird aus den angeschlossenen Akkus<br />

versorgt.<br />

connected.<br />

LED !<br />

Farbe: Gelb, Funktion: Störung.<br />

LED leuchtet, wenn Modul nicht initialisiert<br />

ist, oder der Prozessor nicht arbeitet.<br />

LED blinkt, wenn eine Störung vorliegt.<br />

Aus dem Blinkrythmus kann der<br />

bestehende Fehler ermittelt werden (siehe<br />

Tabelle Binkcodes).<br />

Funktionen MZ2<br />

Das Modul stellt folgende Funktionen<br />

bereit, welche im Einzelnen durch die PC<br />

Software konfiguriert und durch das MCU-<br />

Modul gesteuert werden. Die beim Selbsttest<br />

und den Testfunktionen erkannten<br />

Fehler werden über die LED ! signalisiert<br />

und an das MCU-Modul und das GM-<br />

Module übertragen.<br />

Selbsttestfunktionen<br />

Das Modul verfügt über folgende<br />

Selbsttestfunktionen:<br />

- Überwachung der Versorgungsspannung<br />

- Gültigkeit der Initialisierungsdaten<br />

- Statuskontrolle<br />

- RAM-Test bei Start<br />

- Fehlerfreiheit des Betriebsprogramms<br />

Versorgung der Aktorkreise<br />

Das Modul versorgt bis zu 4 Aktorenkreise.<br />

Die Gesamtstromaufnahme aller<br />

versorgten Kreise darf zusammen nicht<br />

über 16 Ampere betragen. Dabei sind 3<br />

Minuten Betrieb, gefolgt von 7 Minuten<br />

Ruhephase zulässig (ED30).<br />

Je Aktorkreis stehen maximal 8Azur<br />

Verfügung. Der Anschluss erfolgt über<br />

Klemmblock 1.<br />

Werden Aktoren mit ED100 betrieben, z. B.<br />

Haftmagnetkreise, so ist der Strom auf<br />

2,4 A pro Kreis zu begrenzen.<br />

Achtung: Um die einwandfreie<br />

Funktion der Überwachungsschaltungen<br />

der Motormodule zu gewährleisten, sollten<br />

nicht mehr als 4 Motormodule an einen<br />

Aktorkreisausgang des Netzmoduls<br />

angeschlossen werden. Eine Parallelschaltung<br />

von Motormodul-Ausgängen auf<br />

einen Motorkreis ist nicht erlaubt.<br />

LED !<br />

Colour: Yellow, function: Fault<br />

LED alight when the module is not<br />

initialised, or the processor is not working.<br />

LED flashes when there is an error. The<br />

flashing rhythm shows the error (see Table<br />

Flashing Code).<br />

Function for MZ2<br />

The module provides the following<br />

functions that are individually configured<br />

using the PC software and controlled by<br />

the MCU module. The errors recognised<br />

by the self test and the test functions are<br />

signalled to the MCU-module via the<br />

LED ! and transmitted to the GM-module.<br />

Self test functions<br />

The module has the following self test<br />

functions:<br />

- Monitoring of the supply voltage<br />

- Validity of the initialisation data<br />

- Status check<br />

- RAM-test at start<br />

- Fault free operating program<br />

Supply of the actuator circuits<br />

The module supplies up to 4 actuator<br />

circuits. The total current consumption of<br />

all circuits supplied must not be more than<br />

16 amps. Of this 3 minutes are permitted<br />

as operation, followed by 7 minutes rest<br />

(ED30).<br />

Each actuator circuit has a maximum 8 A<br />

available. Connection takes place via<br />

terminal block 1.<br />

If actuators are operated using ED100,<br />

e.g. adhesive magnet circuits, the power is<br />

therefore to be limited to 2.4 A per circuit.<br />

Warning: In order to guarantee<br />

perfect function of the monitoring switches<br />

for the motor modules, no more than 4<br />

motor modules should be connected to<br />

the<br />

actuator circuit output of this power<br />

supply unit. Parallel switching of motor<br />

module outputs to one motor circuit is not<br />

permitted.<br />

3<br />

D<br />

GB


4<br />

Funktionen MZ2<br />

Versorgung der MZ2 Module<br />

Das Modul versorgt alle Module der Modulzentrale über den MZ2<br />

Bus Stecker.<br />

Achtung: Module dürfen niemals bei eingeschalteter<br />

Versorgung auf die Hutschiene montiert werden, dies führt zur<br />

Zerstörung des Moduls und der externen Aktorkreis-Überwachungsdioden.<br />

Um die MZ2 Modulversorgung abzuschalten, muss<br />

der Stecker von Klemmblock 4: MZ2-Bus abgezogen werden.<br />

Überwachung der Eingangsspannung<br />

Das Netzmodul überwacht die Eingangsspannung (230 V Netz).<br />

Ein kontinuierlicher Verlust der Eingangsspannung für einen Zeitraum<br />

länger als 15 Sekunden wird als „Power fail“ Meldung an die<br />

MCU weitergeleitet. Diese schaltet dann die gesamte Anlage in<br />

den Notbetriebmodus. Kürzere Unterbrechungen der Netzversorgung<br />

werden ohne Meldung überbrückt. Nach 30 Sekunden Netzausfall<br />

erlischt die grüne LED und das Netzmodul schaltet in den<br />

Notbetriebmodus. Die grüne LED blinkt dann alle 2 Sekunden kurz<br />

auf und die eigene Stromaufnahme des Netzmoduls sinkt auf<br />

4,3 mA. Liegt länger als 8 Sekunden Eingangsspannung an, wird<br />

der Notbetrieb des Netzteils und der Anlage automatisch beendet.<br />

Überwachung der Ausgangsspannungen<br />

Das Modul überwacht die Spannungsversorgung der Aktorenkreise.<br />

Erkannte Fehler werden als Blinkfolge über die gelbe<br />

Störungs-LED signalisiert (siehe auch Abschnitt Blinkcodes).<br />

Akkuladung<br />

Wird das Netzmodul mit Akkumulatoren betrieben, werden die<br />

angeschlossenen Akkus automatisch geladen. Falls die Option<br />

“temperaturgeführte Ladung” aktiviert ist (PC Konfiguration),<br />

hängen Ladestrom und Spannung von der Temperatur ab. Hierzu<br />

muss der Temperaturfühler angeschlossen sein. Der Temperaturfühler<br />

wird auf Funktion überwacht. Wird dabei ein Fehler festgestellt,<br />

schaltet das Netzmodul auf nicht temperaturgeführte<br />

Ladung um. Der Fehler wird über die gelbe Störungs-LED<br />

signalisiert (siehe auch Abschnitt Blinkcodes).<br />

Überwachung des Akkus<br />

In regelmäßigen Abständen wird die Kapazität der Akkus geprüft.<br />

Hierzu wird die Akkuladung kurzzeitig unterbrochen und der Akku<br />

belastet.<br />

Eine unterbrechungsfreie Versorgung der Anlage ist selbstverständlich<br />

gewährleistet. Festgestellte Fehler werden über die<br />

gelbe Störungs-LED signalisiert (siehe auch Abschnitt Blinkcodes).<br />

Akku Tiefentladeschutz<br />

Befindet sich das Netzmodul im Notbetriebmodus und die<br />

Akkuspannung liegt länger als 2 Minuten kontinuierlich unter<br />

19,5 V, dann wird die Anlage und das Netzteil abgeschaltet.<br />

Achtung: Die Anlage wird erst wieder eingeschaltet, wenn<br />

wieder Netzspannung anliegt oder wenn die Akkuspannung über<br />

24 V liegt.<br />

Hat die Anlage wegen des Tiefentladeschutzes abgeschaltet, dann<br />

liegt die Abschaltschwelle bei 23 V statt bei 19,5 V. Die Abschaltschwelle<br />

wird automatisch wieder auf 19,5 V gesetzt, wenn die<br />

Netzversorgung länger als 5 Minuten kontinuierlich anliegt.<br />

Sicherungsüberwachung<br />

Das Modul überwacht die Sicherungen auf Unterbrechung. Ist an<br />

einem Aktorkreis keine Last angeschlossen, so ist die zugehörige<br />

Sicherung zu entfernen, sonst wird ein Sicherungsfehler angezeigt.<br />

Festgestellte Fehler werden über die gelbe Störungs-LED<br />

signalisiert (siehe auch Abschnitt Blinkcodes).<br />

Übertemperaturschutz<br />

Tritt während des Betriebes eine unzulässig hohe Temperatur im<br />

Netzmodul auf, so schaltet das Netzmodul in den Notbetrieb (zum<br />

Notbetrieb siehe auch Überwachung der Eingangsspannung).<br />

Die Anlage wird dann über die angeschlossenen Akkus weiter<br />

Functions for MZ2<br />

Supply of the MZ2 modules<br />

The module supplies all modules of the module centre via the MZ2<br />

bus plug.<br />

Warning: Modules must never be fitted on the top hat rail<br />

when the supply is switched on; this will lead to damage to the<br />

module and the external actuator circuit monitoring diodes. To<br />

switch the MZ2 module supply off the plug must be removed from<br />

the terminal block 4 MZ2-bus.<br />

Monitoring the input voltage<br />

The power supply unit monitors the input voltage (230 V mains<br />

supply). Continuous loss of the input voltage for a period of longer<br />

than 15 seconds is passed onto the MCU as a "Power fail"<br />

message. This then switches the whole system into emergency<br />

operation mode. Shorter interruptions to the power supply are<br />

bridged without a message. After 30 seconds power failure the<br />

green LED goes out and the power supply unit switches into<br />

emergency operation mode. The green LED then flashes briefly<br />

every 2 seconds and the own power consumption of the power<br />

module drops to 4.3 mA. If input voltage is fed for longer than 8<br />

seconds, emergency operation of the power pack and the system<br />

finishes automatically.<br />

Monitoring of the output voltage<br />

The module monitors the supply voltage of the actuator circuits.<br />

Errors recognised are shown as a flashing sequence via the yellow<br />

fault LED (see also the section on Flashing Codes).<br />

Battery charging<br />

If the power pack is operated using storage batteries, the storage<br />

batteries connected are charged automatically. Should the<br />

temperature guided charging option be activated (PC<br />

configuration) the charging current and voltage depend on the<br />

temperature. The temperature probe must be connected for this.<br />

The temperature probe function is monitored. If an error is<br />

discovered the power pack does not switch to temperature guided<br />

charging. Errors are signalled as a flashing sequence via the yellow<br />

fault LED (see also the section on Flashing Codes).<br />

Battery monitoring<br />

The battery capacity is checked at regular intervals. To do this, the<br />

battery charging is interrupted briefly and the battery charged. It<br />

goes without saying that supply of the system free of interruption is<br />

guaranteed. Errors discovered are shown via the yellow fault LED<br />

(see also the section on Flashing Codes).<br />

Battery over discharge protection<br />

If the power supply unit is in emergency mode and the battery<br />

voltage is continuously less than 19.5 V for longer than 2 minutes,<br />

then the system and power pack are switched off.<br />

Warning: The system is only switched on again when supply<br />

voltage is available again, or when the battery voltage is above<br />

24 V.<br />

If the system has switched off due to the over discharge protection,<br />

then the switch off threshold is 23 V instead of 19.5 V. The switch<br />

off threshold is set automatically to 19.5 V again, when the power<br />

supply is available for longer than 5 minutes.<br />

Fuse monitoring<br />

The module monitors the fuses for interruption. If no load is<br />

connected to an actuator circuit, remove the respective fuse;<br />

otherwise a fuse error is displayed. Errors discovered are signalled<br />

via the yellow fault LED (see also the section on Flashing Codes) .<br />

Excess temperature protection<br />

If an unacceptably high temperature occurs in the power supply<br />

unit during operation, then the power supply unit switches into<br />

emergency operation (for emergency operation see also<br />

Monitoring of the input voltage). The system then continues to be


Funktionen für die MZ2 Functions for MZ2<br />

versorgt. Hat sich das Netzteil abgekühlt, wechselt es automatisch<br />

wieder in den Normalbetrieb.<br />

Betrieb ohne Akkus<br />

Aktorkreise mit Lastabschaltungen<br />

Bauartbedingt können Schaltnetzteile auch kurzzeitig nur den<br />

angegebenen Strom liefern. Das Netzmodul begrenzt den Strom<br />

auf 16 A. Bei Motorkreisen mit Lastabschaltung kann dies dazu<br />

führen, dass die Lastabschaltungen nicht abschalten. Der<br />

erforderliche Abschaltstrom liegt dann über dem maximalen Ausgangsstrom<br />

des Netzmoduls. Der Abschaltstrom wird hauptsächlich<br />

durch den Innenwiderstand des Motors bestimmt und<br />

kann erheblich über dem Nennstrom liegen. Es ist also dafür zu<br />

sorgen, dass der Abschaltstrom aller gleichzeitig abschaltenden<br />

Kreise, auch kurzzeitig, nicht über 16 A liegt. Das gleiche gilt für<br />

den Anlaufstrom. Wenn mehrere kleinere Antriebe über mehrere<br />

Motormodule zu einem Kreis zusammengeschaltet werden, kann<br />

durch eine mit Hilfe der Konfigurationssoftware einstellbare<br />

Verzögerung das Problem entschärft werden.<br />

Betrieb mit Akkus<br />

Akkutypen<br />

Der Betrieb mit Akkumulatoren wird in der PC Software eingestellt.<br />

Als Akkus dürfen nur Bleigel Akkus: 24 V; 1,2 bis 18 Ah eingesetzt<br />

werden. Bei Akkubetrieb liefert das Netzteil kurzzeitig einen<br />

höheren Strom > 16 A. Die Akkus sind regelmäßig zu warten. Als<br />

Temperaturfühler darf nur der MZ2-Temperaturfühler angeschlossen<br />

werden.<br />

Blinkcodes der NM16A<br />

The system then continues to be supplied via the batteries<br />

connected. When the power pack has cooled down it automatically<br />

changes into normal operation.<br />

Operation without battery<br />

Actuator circuits with load switch off<br />

Switching power packs can only supply the power given for a short<br />

period of time due to the design. The power supply unit limits the<br />

power to 16 A. In the case of motor circuits with load switch off this<br />

can lead to the load switch offs not switching off. The switch off<br />

power required then lies above the maximum output power for the<br />

power supply unit. The switch off power is mainly determined by<br />

the motor internal resistance and can be considerably above the<br />

rated current. It must therefore be ensured that the switch off power<br />

for all circuits that switch off at the same time is not more than 16<br />

A. The same applies for starting current. If several smaller drives<br />

are switched to one circuit via several motor modules, the problem<br />

can be diffused with the aid of a delay set using the configuration<br />

software.<br />

Operation with batteries<br />

Battery types<br />

Operation using batteries is set in the PC Software.<br />

Only lead gel batteries: 24 V; 1.2 to 18 Ah may be used.<br />

The batteries are to be serviced regularly. Only the MZ2temperature<br />

probe may be connected as a temperature probe.<br />

Erkannte Fehler werden als Blinkfolge über die gelben Störungs-LED ausgegeben. Die Blinkfolgen haben folgende Bedeutung:<br />

Blinkfolge Fehler Auslöser<br />

DAUER Initdaten Initialisierungsdaten fehlen oder Prozessor läuft nicht<br />

1 Netzfehler Fehler im 230 V Netz<br />

2 Batteriefehler Akkuspannung nicht innerhalb erlaubter Grenzen<br />

6 Busfehler Kommunikation mit der CPU gestört<br />

8 Selbsttest Programmüberwachung<br />

9 Init Initialisierungsdaten fehlen oder fehlerhaft<br />

10 Akkutemperatursensor Temperatursensor fehlerhaft<br />

11 Sicherung Sicherung fehlerhaft<br />

12 Versorgung 5 V int. Versorungsspannung +5 V fehlerhaft<br />

13 Akkucharge Akku Ladestrom nicht innerhalb der erlaubten Grenzen<br />

14 SupplyUB Interner Netzfehler<br />

Aus Kein Fehler -<br />

Flashing codes NM16A<br />

Errors recognised are emitted as a flashing sequence via the yellow fault LED. The flashing sequences have the following meaning:<br />

Flash Code Error Cause of Error<br />

DURATION Initdata Initialisation data missing or processor not running<br />

1 Mains error Error in 230 V mains supply<br />

2 Battery error Battery voltage not within permitted boundaries<br />

6 Bus error Communication with the CPU disrupted<br />

8 Self test Program monitoring<br />

9 Init Initialisation data missing or incorrect<br />

10 Battery temperature sensor Temperature sensor faulty<br />

11 Fuse Fuse faulty<br />

12 Supply 5V int. supply voltage +5 V faulty<br />

13 Battery charge Battery charging current not within the permitted boundaries<br />

14 SupplyUB Internal supply fault<br />

Off No error -<br />

5<br />

D<br />

GB


6<br />

Dauerleuchten<br />

Continuous lamps<br />

1 mal blinken<br />

1 times flash<br />

2 mal blinken<br />

2 times flash<br />

Fehlercodes<br />

Die Fehler im einzelnen<br />

Diese Liste beinhaltet einige typische<br />

Fehler und beschreibt das geeignete<br />

Vorgehen zu deren Behebung. Nicht alle<br />

möglichen Fehler können automatisch<br />

erfasst werden, daher ist eine regelmäßige<br />

Prüfung und Wartung der Anlage unumgänglich.<br />

Die Fehler werden an die RWA-Bedienstellen<br />

weitergeleitet. Dort werden sie als<br />

Blinkcode ‚1' (230 V Netzfehler) oder<br />

Blinkcode ‚2' (Netzteilfehler) signalisiert<br />

(siehe Modulbeschreibungen MCU und<br />

MM).<br />

Dauerleuchten<br />

Dieser Fehler kann zwei Ursachen haben,<br />

entweder fehlen die Initialisierungsdaten<br />

oder der Prozessor läuft nicht.<br />

Abhilfe:<br />

- Nachsehen, ob der Adresswahlschalter<br />

auf der richtigen Adresse steht.<br />

- Nachsehen, ob das MCU Modul für die<br />

eingestellte Adresse Daten hat, das<br />

Modul muss im PC Programm eingetragen<br />

und konfiguriert worden sein.<br />

- Ca. 2 Minuten abwarten, bis die MCU<br />

einem Modul die aktuellen Initialisierungsdaten<br />

übermittelt hat.<br />

- Auf dem MCU-Modul ein Anlagenreset<br />

auslösen.<br />

- Falls nichts hilft, Modul austauschen.<br />

Netzfehler<br />

Der mitlaufende Selbsttest hat eine fehlerhafte<br />

230 V Netzversorgung festgestellt.<br />

Der Fehler wird erst 15 Sekunden nach<br />

Netzausfall signalisiert und ist nur für ca.<br />

15 Sekunden sichtbar, danach schaltet<br />

das Modul in den Notbetriebmodus.<br />

Abhilfe:<br />

- Prüfen, ob die Verdrahtung zum Netz in<br />

Ordnung ist, insbesondere Klemmen:<br />

13, 14 und 15.<br />

- Prüfen, ob das Netz eingeschaltet ist und<br />

ausreichend Spannung und Strom liefert.<br />

- Falls nichts hilft, Modul austauschen<br />

Batteriefehler<br />

Der mitlaufende Selbsttest hat eine fehlerhafte<br />

Akkuspannung festgestellt.<br />

Abhilfe:<br />

- Prüfen, ob die Akkusicherung in Ordnung<br />

ist.<br />

- Prüfen, ob die Verdrahtung zum Akku in<br />

Ordnung ist, insbesondere Klemmen:<br />

1 und 5.<br />

- Prüfen, ob der Akku in Ordnung ist, ggf.<br />

austauschen.<br />

- Falls der Akku entladen wurde, einige<br />

Zeit abwarten, bis der Akku wieder<br />

geladen wurde<br />

- Falls nichts hilft, Modul austauschen.<br />

Error detecting codes<br />

Errors in detail<br />

This list contains some typical errors and<br />

describes a suitable procedure for<br />

rectification. Not all possible faults can be<br />

collated automatically, regular inspection<br />

and maintenance of the system is<br />

therefore absolutely necessary.<br />

The faults are passed onto the SHE<br />

Control Centres. These are shown there as<br />

flashing code "1" (230 V supply fault) or<br />

flashing code "2" (power pack fault (see:<br />

Module descriptions MCU and MM).<br />

Continuous lights<br />

This error can have two causes; either<br />

initialisation data or the processor is not<br />

running.<br />

Remedial Measure:<br />

- Check if the address selector switch is<br />

on the correct address.<br />

- Check if the MCU module has data for<br />

the address set, the module must be<br />

entered in the PC program and have<br />

been configured.<br />

- Wait for approx. 2 minutes until the MCU<br />

has transferred the current initialisation<br />

data to a module.<br />

- Trigger system reset on the MCU-module.<br />

- If nothing helps replace the module.<br />

Mains error<br />

The continuous self test has discovered a<br />

fault 230 V mains supply. The error is<br />

signalled only after 15 seconds of power<br />

failure and is only visible for approx. 15<br />

seconds, after that the module switches<br />

into emergency operation.<br />

Remedial Measure:<br />

- Check if the wiring to the mains supply is<br />

in order, in particular terminals:<br />

13, 14 and 15.<br />

- Check that the mains supply is switched<br />

on and is supplying adequate voltage<br />

and power.<br />

- If nothing helps replace the module.<br />

Battery error<br />

The continuous self test has discovered<br />

faulty battery voltage.<br />

Remedial Measure:<br />

- Check that the battery fuse is ok.<br />

- Check if the wiring to the battery is in<br />

order, in particular terminals: 1 and 5.<br />

- Check if the battery is ok, replace if<br />

necessary.<br />

- If the battery has been discharged, wait<br />

for some time until the battery has been<br />

charged again.<br />

-<br />

If nothing helps replace the module.


6 mal blinken<br />

6 times flash<br />

8 mal blinken<br />

8 times flash<br />

9 mal blinken<br />

9 times flash<br />

10 mal blinken<br />

10 times flash<br />

11 mal blinken<br />

11 times flash<br />

Fehlercodes<br />

Busfehler<br />

Die Kommunikation mit dem MCU Modul<br />

ist gestört.<br />

Abhilfe:<br />

- Nachsehen, ob der Adresswahlschalter<br />

auf der richtigen Adresse steht.<br />

- Prüfen, ob das Modul richtig auf der<br />

Schiene eingeschnappt ist.<br />

- Prüfen, ob die Busverbinder auf der<br />

Hutschiene in Ordnung sind.<br />

- Ca. 5 Minuten abwarten, ob die MCU die<br />

Kommunikation neu initialisiert.<br />

- Falls der Fehler länger als 5 Minuten<br />

anhält, auf dem MCU-Modul ein Anlagenreset<br />

auslösen.<br />

- Falls nichts hilft, Modul austauschen.<br />

Selbsttest<br />

Der mitlaufende Selbsttest hat einen<br />

Fehler im Programm festgestellt.<br />

Abhilfe:<br />

- Das Modul zum Service einschicken.<br />

Achtung: Ein sicherer Weiterbetrieb<br />

ist nicht gewährleistet!<br />

Initdaten Fehler<br />

Der mitlaufende Selbsttest hat einen<br />

internen Fehler festgestellt.<br />

Abhilfe:<br />

- Ca. 2 Minuten abwarten, bis die MCU<br />

einem neuen Modul die aktuellen<br />

Initialisierungsdaten übermittelt hat.<br />

- Auf dem MCU-Modul ein Anlagenreset<br />

auslösen.<br />

- Falls nichts hilft, Modul austauschen.<br />

Achtung: Ein sicherer Weiterbetrieb<br />

ist nicht gewährleistet!<br />

Akkutemperatursensor<br />

Der mitlaufende Selbsttest hat einen<br />

fehlerhaften Temperatursensor oder<br />

Temperaturwert festgestellt.<br />

Abhilfe:<br />

- Prüfen, ob der Temperatursensor richtig<br />

aufgesteckt ist.<br />

- Prüfen, ob die Akkutemperatur tatsächlich<br />

außerhalb der Spezifikation liegt.<br />

- Umgebung ändern, falls Umgebungstemperatur<br />

in Ordnung ist, Akku<br />

erneuern.<br />

- Temperatursensor austauschen.<br />

- Falls kein Temperatursensor angeschlossen<br />

ist, Option: „temperaturgeführte<br />

Ladung“ mit Hilfe des PC<br />

Konfigurationsprogramms abschalten.<br />

- Falls nichts hilft, Modul austauschen.<br />

Sicherung<br />

Der mitlaufende Selbsttest hat eine<br />

fehlerhafte Sicherung festgestellt.<br />

Abhilfe:<br />

- Prüfen, welche Sicherung defekt ist,<br />

Stromkreis auf Schluss prüfen.<br />

- Schluss beheben, Sicherung erneuern.<br />

- Falls nichts hilft, Modul austauschen.<br />

Error detecting codes<br />

Bus error<br />

Communication with the MCM module is<br />

disrupted.<br />

Remedial Measure:<br />

- Check if the address selector switch is<br />

on the correct address.<br />

- Check that the module is snapped onto<br />

the correct rail.<br />

- Check that the bus connector on the top<br />

hat rail is ok.<br />

- Wait for approx. 5 minutes, in case the<br />

MCU initialises the communication<br />

again.<br />

- If the error lasts for longer than 5<br />

minutes, trigger a system reset on the<br />

MCU-module.<br />

- If nothing helps replace the module.<br />

Self test<br />

The continuous self test has discovered an<br />

error in the program.<br />

Remedial Measure:<br />

- Send the module into the service<br />

department.<br />

Warning: Further safe operation can<br />

no longer be guaranteed.<br />

Init data error<br />

The continuous self test has discovered an<br />

internal error.<br />

Remedial Measure:<br />

- Wait for approx. 2 minutes until the MCU<br />

has transferred the current initialisation<br />

data to a new module.<br />

- Trigger system reset on the MCU-module.<br />

- If nothing helps replace the module.<br />

Warning: Further safe operation can<br />

no longer be guaranteed!<br />

Battery temperature sensor<br />

The continuous self test has discovered a<br />

faulty temperature sensor or temperature<br />

value.<br />

Remedial Measure:<br />

- Check that the temperature sensor is<br />

inserted correctly.<br />

- Check that the battery temperature is<br />

actually outside of the specification.<br />

- Change the environment, if the ambient<br />

temperature is ok, renew the battery.<br />

- Replace temperature sensor.<br />

- Should no temperature sensor be<br />

connected, option: Switch off<br />

"temperature guided charge" with the aid<br />

of the PC configuration program.<br />

- If nothing helps replace the module.<br />

Fuse<br />

The continuous self test has discovered a<br />

faulty fuse.<br />

Remedial Measure:<br />

- Check which fuse is faulty, check electric<br />

circuit for short.<br />

- Rectify short, replace fuse.<br />

- If nothing helps replace the module.<br />

7<br />

D<br />

GB


12 mal blinken<br />

12 times flash<br />

13 mal blinken<br />

13 times flash<br />

14 mal blinken<br />

14 times flash<br />

Fehlercodes<br />

Versorgung +5 V<br />

Der mitlaufende Selbsttest hat einen<br />

internen Fehler festgestellt.<br />

Abhilfe:<br />

- Das Modul zum Service einschicken.<br />

Achtung: Ein sicherer Weiterbetrieb<br />

ist nicht gewährleistet!<br />

Akkucharge<br />

Der mitlaufende Selbsttest hat eine fehlerhafte<br />

Verbindung zum Akku festgestellt.<br />

Abhilfe:<br />

- Prüfen, ob die Akkusicherung in<br />

Ordnung ist.<br />

- Prüfen, ob die Verdrahtung zum Akku in<br />

Ordnung ist, insbesondere Klemmen:<br />

1 und 5.<br />

- Prüfen, ob der Akku in Ordnung ist, ggf.<br />

austauschen.<br />

- Falls nichts hilft, Modul austauschen.<br />

SupplyUB<br />

Der mitlaufende Selbsttest hat einen<br />

internen Fehler festgestellt.<br />

Abhilfe:<br />

- Modul austauschen.<br />

Dauerleuchten grüne LED: Kein Fehler<br />

Technische Daten<br />

Error detecting codes<br />

Supply +5 V<br />

The continuous self test has discovered an<br />

internal error.<br />

Remedial Measure:<br />

- Send the module into the service<br />

department.<br />

Warning: Further safe operation can<br />

no longer be guaranteed.<br />

Battery charge<br />

The continuous self test has discovered a<br />

faulty battery connection.<br />

Remedial Measure:<br />

- Check that the battery fuse is ok.<br />

- Check that the wiring to the battery is in<br />

order, in particular terminals: 1 and 6.<br />

- Check if the battery is ok, replace if<br />

necessary.<br />

- If nothing helps replace the module.<br />

SupplyUB<br />

The continuous self test has discovered an<br />

internal error.<br />

Remedial Measure:<br />

- Replace module.<br />

Green LED continous lamp: No error<br />

Betriebsspannung des Moduls 230 V AC, 50 Hz (+/-15%)<br />

Ausgangsspannung 27 V DC (+/-15%)<br />

Max. Ausgangsstrom 16 A (ED 30: 3 Minuten EIN, 7 Minuten AUS)<br />

Max. Strom pro Aktorkreis (als Motorkreis/Linearantrieb ED 30) 8 A (ED 30: 3 Minuten EIN, 7 Minuten AUS)<br />

Aktorenkreise 4<br />

Max. Strom pro Aktorkreis (Haftmagnetkreis ED 100) 2,4 A (ED 100: ständig EIN)<br />

Max. Strom Modulversorgungungskreis 3 A<br />

Max. Akku Ladestrom 1,5 A<br />

Stromaufnahme (Nennstrom)<br />

2,5 A<br />

Stromaufnahme im Notbetrieb 4,3 mA (bei 27,5 V Betriebsspannung)<br />

Leistungsaufnahme im Notbetrieb 0,18 VA (bei 27,5 V Betriebsspannung)<br />

Akkukapazitäten 24 V; 1,2 - 18 Ah<br />

Akkutyp Bleigel, VdS geprüft<br />

Temperaturbereich 0° - 50 °C<br />

Feuchtigkeitsbereich 10 - 75 % rel. Feuchte, Betauung nicht zulässig<br />

Schutzklasse (Bestimmt durch MZ2 Aufbau)<br />

TÜV-Nr. 2175/05<br />

Technical dates<br />

Module operating voltage 230 V AC, 50 Hz (+/- 15%)<br />

Output voltage 27 V DC (+/- 15%)<br />

Max. output current 16 A (ED 30: 3 Minutes ON, 7 Minutes OFF)<br />

Max. power per actuator circuit (as motor circuit / linear drive ED 30) 8 A (ED 30: 3 Minutes ON, 7 Minutes OFF)<br />

Actuator circuits 4<br />

Max. Power per actuator circuit (adhesive magnet circuit ED 100) 2.4 A (ED 100: constant ON)<br />

Max. Power module supply circuit 3 A<br />

Max. Battery charging current 1.5 A<br />

Power consumption (rated current) 2.5 A<br />

Power consumption in emergency operation 4.3 mA (at 27.5 V operating voltage)<br />

Power consumption in emergency operation 0.118 W (at 27.5 V operating voltage)<br />

Battery capacities 24 V; 1.2 - 18 Ah<br />

Battery type Lead gel, VdS tested<br />

Temperature range 0° - 50°C<br />

Humidity range 10 - 75% re. humidity moisture not permitted<br />

Protection class (determined by MZ2 set up)<br />

TÜV No. 2175/05<br />

8


-X1<br />

PE<br />

Anschlussbeispiel<br />

PE Anschluss Gehäuse<br />

PE connection housing<br />

-X1<br />

L N PE<br />

PE Anschluss Montageplatte<br />

PE connection mounting plate<br />

230V/50Hz<br />

Connection diagram<br />

PE<br />

N<br />

L<br />

Bus / A<br />

Bus / B<br />

Bus / C<br />

Bus / D<br />

Bus / E<br />

A<br />

B<br />

C<br />

D<br />

E<br />

MZ2 BUS<br />

+ Batterie<br />

- Batterie<br />

Temp. Sensor<br />

+<br />

-<br />

+<br />

-<br />

-G1<br />

F 1 2 3 4 5 6<br />

+24 V Gruppe 1<br />

-24 V Group 1<br />

+24VGruppe 2<br />

-24 V Group 2<br />

+24 V Gruppe 3<br />

-24 V Group 3<br />

+24 V Gruppe 4<br />

-24 V Group 4<br />

Ausgang Aktorkreise<br />

Output actuator circuits<br />

Temp. Sensor<br />

9<br />

D<br />

GB