26.11.2012 Views

FIRE DETECTION - Urmet

FIRE DETECTION - Urmet

FIRE DETECTION - Urmet

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Photo-optical smoke detector<br />

FDO500 cod. SD4800121<br />

Low profile photo-optical smoke detector, complete with self-learning circuit<br />

and short-circuit isolator.<br />

•<br />

•<br />

•<br />

•<br />

•<br />

•<br />

•<br />

•<br />

•<br />

•<br />

Smoke detectors work according to the light scattering principle caused by<br />

smoke particles present in the air. The smoke detector has the automatic gain<br />

control function; a microcontroller calculates reading compensation to keep<br />

constant sensitivity and corrects any level increase due to dust depositing<br />

into the analysis cell. Smoke detectors shall be installed in places protected<br />

against draughts which may divert the flow of combustion particles and in<br />

places where the common activities performed do not cause gas material<br />

fires.<br />

Power supply: 20Vdc (modulated voltage between -15% and + 10%)<br />

Average absorption at rest: 250 mA@20Vdc<br />

Absorption at alarm: 2mA@20Vdc<br />

Two-colour led: red alarm - green regular operation<br />

Relative humidity max: 93%<br />

Working temperature: 0 ÷ 50°C<br />

Weight: 70 g<br />

Dimensions: ø 90 x 31 (H) mm<br />

Certificato EN54 parte 7, certification number: 1293-CPD-0082<br />

RIVELATORI CONVENZIONALI<br />

Heat detector<br />

FAP500 DIGITAL SYSTEM<br />

FAP500 SYSTEM: DETECTORS<br />

FDT500 cod. SD5700121<br />

Low profile heat detector, complete with self-learning circuit and short-circuit<br />

isolator.<br />

• Heat detectors monitor the temperature values in the area where they are<br />

installed.<br />

• A microcontroller analyses and compares the signal received from a NTC<br />

type temperature detector and activates the alarm if the read temperature<br />

exceeds 58°C.<br />

• Power supply: 20Vdc (modulated voltage between -15% and + 10%)<br />

• Average absorption at rest: 250 mA@20Vdc<br />

• Absorption at alarm: 2mA@20Vdc<br />

• Static alarm threshold: 58°<br />

• Two-colour led: red alarm - green regular operation<br />

• Relative humidity max: 93%<br />

• Working temperature: 0 ÷ 50°C<br />

• Weight: 70 g<br />

• Dimensions: ø 90 x 40 (H) mm<br />

• Compliant with EN54 Standards, part 5 class A1S, certification number:<br />

1293-CPD-0084.<br />

44<br />

FDO500<br />

FDT500