26.11.2012 Views

FIRE DETECTION - Urmet

FIRE DETECTION - Urmet

FIRE DETECTION - Urmet

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Modules<br />

ADDRESSED <strong>FIRE</strong> <strong>DETECTION</strong> SYSTEMS<br />

ACCESSORIES FOR ADDRESSED SYSTEMS<br />

MCR/DIN-2000 cod. SC9110121<br />

Analogue addressed module with collective addressing. The module allows to<br />

manage a secondary line, made up of conventional detectors. Max number<br />

of elements is 10.<br />

• The interface has 4 O.C. repetitions and 4 relays for failure, alarm 1, alarm<br />

2 reset status.<br />

• Supply voltage: 20÷30Vdc<br />

• Working voltage: 18Vdc modulated<br />

• Rest absorption: 1 mA<br />

• Alarm absorption: 20 mA per alarmed relay<br />

• Repetition outputs (O.C.): 100 mA max<br />

• Relay output: 1A @ 24Vdc<br />

• Operation temperature: -10÷50°C<br />

• Dimensions (HxLxD): 112 x 168 x 50 mm.<br />

ISO/BP cod. SC6H00121<br />

Short-circuit analyser module for lines for analogue detections; the module<br />

is designed to ensure the operation of the detectors and/or pushbuttons<br />

that are connected to the same line, in case a short-circuit occurs.<br />

• The module is contained in smoke detector cap.<br />

• On the two sides of the cap there are yellow leds having the task of signalling<br />

the section where the short-circuit is being detected.<br />

• For detection line connection, ZB/200 base is used.<br />

• The module needs no additional power supply.<br />

• Working voltage: 18 Vdc modulated<br />

• Average absorption: 250 µA<br />

• Operation temperature: -20°C to + 50°C<br />

• Protection degree: IP 43<br />

• Dimensions: Ø 100 mm H.45 mm<br />

ISO/BASE cod. SC4H00121<br />

Short-circuit analyser module for lines for analogue detections; the module<br />

is designed to ensure the operation of the detectors and/or pushbuttons<br />

that are connected to the same line, in case a short-circuit occurs.<br />

• Yellow leds having the task of signalling the section where the short-circuit is<br />

being detected.<br />

• The module is contained in ZB/215 connector block.<br />

• The module needs no additional power supply.<br />

• Working voltage: 18 Vdc modulated<br />

• Average absorption: 250 µA<br />

• Operation temperature: -20°C to + 50°C<br />

• Relative humidity: 95 % Max RH non condensing<br />

• Dimensions: Ø 100 mm H.45 mm<br />

MCR/DIN-2000<br />

ISO/BP<br />

ISO/BASE<br />

29