8.4 Parameter set handlingThe use of different parameter sets can be helpful whenusing one softstarter to start different motors or when workingunder various load conditions. There are four parametersets available in <strong>MSF</strong> <strong>2.0</strong>. Parameter set handling is controlledby the following parameters:[240] Select parameter set[241] Actual parameter set[242] Copy parameter set[243] Reset to factory setting8.4.1 Select parameter set [240]Parameter Set 1Parameter Set 2Parameter Set 3200, 210, 211, 212, 213,214, 220, 221, 222, 224,225, 226, 228, 229, 230,231, 250, 251, 252, 253,254, 255, 256, 257, 258,259, 260, 261, 262, 263,310, 311, 312, 313, 314,315, 316, 317, 320, 321,322, 324, 325, 326, 327,330, 331, 332, 333, 334,335, 340, 341, 342, 400,401, 402, 403, 404, 405,406, 407, 408, 409, 410,412, 420, 430, 431, 432,433, 434, 435, 436, 437,438, 500, 501, 502, 503,504, 520, 521, 522, 523,000Parameter Set 4Common for all parameter sets2 4 0Select parameter setDefault: 1Range: 0, 1, 2, 3, 40 External control of parameter sets.1, 2, 3, 4 Selection of parameter sets 1-4.Actual parameter set [241]This menu is available when external control of parametersets is chosen in menu [240]. This menu shows whichparameter set is actually selected via the digital inputs.2 4 111Range: 1, 2, 3, 4Actual parameter setSettingRead-out8.4.2 Copy parameter set [242]This function will simplify configuration of different parametersets. It is possible to copy an already configured parameterset into another set as follows:• Select a copy alternative in this menu, for example P1-2.Press “ENTER”. “CoPY” is displayed for 2 seconds toindicate successful copy process. After that, “no” is displayed.• Go to menu [240] and select parameter set 2.• Make the required new settings in corresponding menusfor parameter set 2.101, 201, 202, 215, 240, 242, 243, 270,271, 272, 273, 300, 323, 411, 440, 510,511, 512, 513, 530, 531, 532, 533, 534,7322 4 2noCopy parameter setMulti SettingFig. 35 Parameter overviewSelect parameter set [240]In this menu one of the parameter sets 1-4 can be selecteddirectly or external control of parameter sets via digitalinputs can be chosen. If external control of parameter sets ischosen, the digital inputs have to be configured properly (seedescription of menus [510] to [513]). By default digitalinputs 3 and 4 (terminals 16 and 17) are configured forexternal control of parameter sets.Default:Range:noP1-2 etc.nono, P1-2, P1-3, P1-4, P2-1, P2-3, P2-4,P3-1, P3-2, P3-4, P4-1, P4-2, P4-3No actionCopy parameter set 1 to parameter set 2etc.NOTE: Copying parameter sets is only allowed when thesoftstarter is not running.<strong>Emotron</strong> AB 01-4135-01r2 Functional description 51

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!