5.3 Motor dataSet the data, according to the motor type plate, to obtainoptimal settings for start, stop and motor protection.NOTE! The default settings are for a standard 4-polemotor according to the nominal power of the softstarter.The softstarter will run even if no specific motor data isselected, but the performance will not be optimal.2 1 040 0Nominal motor voltageDefault: 400 VRange: 200-700 V200-700 Nominal motor voltage.Setting2 1 4Nominal power factorDefault: 0.86Range: 0.50-1.000.50-1.00 Nominal motor power factor.2 1 50. 8650Nominal frequencyDefault: 50 HzRange: 50 Hz, 60 Hz50, 60 Nominal frequency.SettingSetting2 1 1Setting5.4 Start and stop1 7Nominal motor currentDefault: I nsoft in ARange: 25-200% of I nsoft in A25-200 Nominal motor current.3 1 510Default: 10 sRange: 1-60 s1-60 Start time.Start timeSetting2 1 2Setting7. 5Nominal motor powerDefault: P nsoft in kWRange: 25-400% of P nsoft in kW or HP.25-400 Nominal motor power.2 1 31 4 50Default: N nsoft in rpmRange: 500-3600 rpm500-3600 Nominal motor speed.SettingNominal motor speed3 2 04Stop methodDefault: 4 (Coast)Range: 1, 2, 3, 4, 51 Linear torque control2 Square torque control3 Voltage control4 Coast5 BrakeDefault “Stop method” is Coast (freewheeling).Setting28 How to get started <strong>Emotron</strong> AB 01-4135-01r2