Emotron MSF 2.0 Softstarter
Emotron MSF 2.0 Softstarter Emotron MSF 2.0 Softstarter
Table 27Parameter listMenuno.Function / ParameterRange /SettingsFactorysettingCustomer setting / Parameter set 1-41 2 3 4Page436Undervoltage alarm (Alarmcode F10)oFF. Disabled1. Warning2. Coast3. Stop4. Alarm brakeoFF 75437 Undervoltage level 75 - 100 % of U n 85 76438Response delay undervoltagealarm1 - 90 s 1 76439 Phase sequence L123, L321, L--- Read-out 76440I/O SETTINGSInput signalsPhase reversal alarm (Alarmcode F16)500 Analogue / digital inputoFF. Disabled1. Warning2. CoastoFF. Disabled1. Digital, Rotation sensor2. Digital, Slow speed3. Digital, Jog forward4. Digital, Jog reverse5. Digital, Auto set6. Analogue start/stop, 010 V / 0 20 mA7. Analogue start/stop, 210 V / 4 20 mAoFF 76oFF 77501 Digital input pulses 1 - 100 1 78502 Analogue start-stop on-value 0 - 100 % 25 79503 Analogue start-stop off-value 0 - 100 % 75 80504Analogue start-stop delaytime510 Digital input 1 function1 - 999 s 1 s 80oFF. Disabled1. Start signal2. Stop signal3. Parameter set input 14. Parameter set input 25. External alarm signal6. Start R signal7. Start L signal1 81511 Digital input 2 function Same as menu 510 2 81512 Digital input 3 function Same as menu 510 3 82513 Digital input 4 function Same as menu 510 4 82Output signals520 Analogue output521 Analogue output functionoFF. Disabled1. 0 – 10 V / 0 – 20 mA,2. 2 – 10 V / 4 – 20 mA,3. 10 – 0 V / 20 – 0 mA,4. 10 – 2 V / 20 – 4 mA1 = RMS current2 = Line voltage3 = Shaft power4 = TorqueoFF 821 83522 Scaling analogue output, min 0 - 500 % 0 83Emotron AB 01-4135-01r2 Set-up menu list 127
Table 27Parameter listMenuno.Function / ParameterRange /SettingsFactorysettingCustomer setting / Parameter set 1-41 2 3 4Page523 Scaling analogue output, max 0 - 500 % 100 84530 Relay K1oFF. Relay inactive1. Operation2. Full voltage3. Power pre-alarms4. Reverse current brake5. Run6. Run R7. Run L8. Operation R9. Operation L10. Power alarms11. Max power alarm12. Max power pre-alarm13. Min power alarm14. Min power pre-alarm15. All alarms (except powerpre-alarms)16. All alarms (except poweralarm and pre-alarms)17. External alarm signal18. Auto reset expired19. All alarms which needmanual reset1 85531 Relay K2 Same as menu 530 2 85532 Relay K3 Same as menu 530 15 85533 K1 contact function1. Normally open (N.O.)2. Normally closed (N.C.)1 86534 K2 contact function Same as menu 533 1 86VIEW OPERATIONOperation700 Current 0.0 - 9999 A Read-out 92701 Line main voltage 0 - 720 V Read-out 92702 Power factor 0.00 - 1.00 Read-out 92703 Output shaft power -999 - 9999 kW Read-out 92704Output shaft power in percentageunits0 - 200 % of P n Read-out 93705 Shaft torque -999 - 9999 Nm Read-out 93706Shaft torque in percentageunits0 - 250 % of T n Read-out 93707 Softstarter temperaturelow, 30 - 96 ˚C resp low, 85 -Read-out204 ˚F93708 Current phase L1 0.0 - 9999 A Read-out 93709 Current phase L2 0.0 - 9999 A Read-out 93710 Current phase L3 0.0 - 9999 A Read-out 93711 Line main voltage L1-L2 0 - 720 V Read-out 93712 Line main voltage L1-L3 0 - 720 V Read-out 94713 Line main voltage L2-L3 0 - 720 V Read-out 94714 Phase sequence L123, L321, L--- Read-out 94128 Set-up menu list Emotron AB 01-4135-01r2
- Page 79 and 80: Undervoltage level [437]This menu i
- Page 81 and 82: Relay outputsPTC inputPTCCurrent tr
- Page 83 and 84: Analogue start/stop off-value [503]
- Page 85 and 86: Digital input 3 function [512]In th
- Page 87 and 88: Scaling analogue output, max [523]T
- Page 89 and 90: K1 contact function [533]In this me
- Page 91 and 92: !CAUTION: Very high currents can ar
- Page 93 and 94: For applications which use the reve
- Page 95 and 96: It is possible to use just one digi
- Page 97 and 98: Line main voltage L1-L38.10.2 Statu
- Page 99 and 100: 8.11 Alarm listThe alarm list is ge
- Page 101 and 102: whether they need a Reset signal (m
- Page 103 and 104: 100 Protection and alarm Emotron AB
- Page 105 and 106: Observation Fault indication Cause
- Page 107 and 108: Observation Fault indication Cause
- Page 109 and 110: 106 Maintenance Emotron AB 014135-0
- Page 111 and 112: 12.3.1 Cable kit for external curre
- Page 113 and 114: 110 Options Emotron AB 01-4135-01r2
- Page 115 and 116: Table 19Typical motor power at main
- Page 117 and 118: Table 21Typical motor power at main
- Page 119 and 120: 13.2 General electrical specificati
- Page 121 and 122: Table 25Power lossesModelPower loss
- Page 123 and 124: 13.5 Derating at highertemperatureB
- Page 125 and 126: 13.9 Semi-conductor fusesAlways use
- Page 127 and 128: Table 27Parameter listMenuno.Functi
- Page 129: Table 27Parameter listMenuno.Functi
- Page 133 and 134: Table 27Parameter listMenuno.Functi
- Page 135: Operation R .......................
- Page 138: Emotron AB, Mörsaregatan 12, SE-25
Table 27Parameter listMenuno.Function / ParameterRange /SettingsFactorysettingCustomer setting / Parameter set 1-41 2 3 4Page436Undervoltage alarm (Alarmcode F10)oFF. Disabled1. Warning2. Coast3. Stop4. Alarm brakeoFF 75437 Undervoltage level 75 - 100 % of U n 85 76438Response delay undervoltagealarm1 - 90 s 1 76439 Phase sequence L123, L321, L--- Read-out 76440I/O SETTINGSInput signalsPhase reversal alarm (Alarmcode F16)500 Analogue / digital inputoFF. Disabled1. Warning2. CoastoFF. Disabled1. Digital, Rotation sensor2. Digital, Slow speed3. Digital, Jog forward4. Digital, Jog reverse5. Digital, Auto set6. Analogue start/stop, 010 V / 0 20 mA7. Analogue start/stop, 210 V / 4 20 mAoFF 76oFF 77501 Digital input pulses 1 - 100 1 78502 Analogue start-stop on-value 0 - 100 % 25 79503 Analogue start-stop off-value 0 - 100 % 75 80504Analogue start-stop delaytime510 Digital input 1 function1 - 999 s 1 s 80oFF. Disabled1. Start signal2. Stop signal3. Parameter set input 14. Parameter set input 25. External alarm signal6. Start R signal7. Start L signal1 81511 Digital input 2 function Same as menu 510 2 81512 Digital input 3 function Same as menu 510 3 82513 Digital input 4 function Same as menu 510 4 82Output signals520 Analogue output521 Analogue output functionoFF. Disabled1. 0 – 10 V / 0 – 20 mA,2. 2 – 10 V / 4 – 20 mA,3. 10 – 0 V / 20 – 0 mA,4. 10 – 2 V / 20 – 4 mA1 = RMS current2 = Line voltage3 = Shaft power4 = TorqueoFF 821 83522 Scaling analogue output, min 0 - 500 % 0 83<strong>Emotron</strong> AB 01-4135-01r2 Set-up menu list 127