Emotron MSF 2.0 Softstarter
Emotron MSF 2.0 Softstarter Emotron MSF 2.0 Softstarter
Observation Fault indication Cause SolutionThe motor is runningbut an alarm isgiven.The motor jerks etc.The monitor functiondoes not work.F12(Shorted thyristor)F15(Serial communication contactbroken)When starting, motor reachesfull speed but it jerks orvibrates.Starting or stopping time toolong.No alarm or pre-alarmPerhaps a damaged thyristor.Bypass contactor is used butparameter [340] ’Bypass’ is notset to “on”.Serial communication contact broken.If “Torque control” or “Pump control”is selected, it is necessary toinput motor data into the system.When stop command is given, a freewheelstop is made. Initiate a resetand a restart. If alarm F14 appearsimmediately, contact your local MSFsales outlet.If the motor must be started urgently,the softstarter can start the motordirect on-line (DOL). Set the startmethod to DOL in this case (parameter[310]=4).Set parameter [340] Bypass to on.Initiate a reset and try to establishcontact. Check contacts, cables andoption board.Verify- Serial communication unit address[270].- Baudrate [271].- Parity [272].If the fault is not found, run themotor from the control panel ifurgent, see also manual for serialcommunication.Configure nominal motor data inmenus [210]-[215]. Select theproper torque control alternative inmenu [310] (linear or square)according to the load characteristic.Select a correct initial- and endtorque at start in menus [311] and[312]. If ’Bypass’ is selected, checkthat the current transformers arecorrectly connected.Start time too short. Increase start time [315].If voltage control is used as startmethod, the initial voltage at startAdjust initial voltage at start [311].may be too low. Starting voltageincorrectly set.Motor too small in relation to ratedcurrent of softstarter.Motor too large in relation to loadof softstarter.Starting voltage not setcorrectly.Ramp times not set correctly.Motor too large or too small inrelation to load.It is necessary to input nominalmotor data for this function.Incorrect alarm margins or normalload.Use a smaller model of the softstarter.Use larger model of softstarter.Readjust the start ramp.Select the current limit function.Readjust the start and/or stop ramptime.Change to another motor size.Input nominal motor data in menus[210]-[215]. Adjust alarm marginsand normal load in menus [402] -[412]. Use Auto set [411] if needed.If a Bypass contactor is used, checkthat the current transformers arecorrectly connected.Emotron AB 01-4135-01r2 Troubleshooting 103
Observation Fault indication Cause SolutionUnexplainablealarm.The system seemslocked in an alarm.F5, F6, F7, F8, F9, F10 Alarm delay time is too short.F2(Thermal motor protection)F3(Softstarter overheated)PTC input terminal could be open.Motor could still be too warm.If internal motor protection isused, the cooling in the internalmodel may take some time.Ambient temperature to high.Perhaps fan failure.Adjust the response delay times forthe alarms in menus [229], [404],[410], [432], [435] and [438].PTC input terminal should be shortcircuit if not used. Wait until motorPTC gives an OK (not overheated) signal.Wait until the internal cooling isdone. Try to restart after a while.Check that cables from power partare connected in terminals 71 to 74.MSF-017 to MSF-250 should have ajumper between terminals 71 and72. Check also that the fan(s) is (are)rotating.104 Troubleshooting Emotron AB 01-4135-01r2
- Page 55 and 56: 8.4.3 Reset to factory setting [243
- Page 57 and 58: External alarm auto reset [257]This
- Page 59 and 60: With voltage control the output vol
- Page 61 and 62: To optimize the start, use the sett
- Page 63 and 64: Torque boost current limit [316]In
- Page 65: NOTE: For several start/stops it is
- Page 68 and 69: Slow speed controlled by an externa
- Page 70 and 71: JOG commands can be given via analo
- Page 72 and 73: Power Factor Control PFC [341]Durin
- Page 74 and 75: Max power alarm [400]In this menu m
- Page 76: Min power alarm response delay [410
- Page 79 and 80: Undervoltage level [437]This menu i
- Page 81 and 82: Relay outputsPTC inputPTCCurrent tr
- Page 83 and 84: Analogue start/stop off-value [503]
- Page 85 and 86: Digital input 3 function [512]In th
- Page 87 and 88: Scaling analogue output, max [523]T
- Page 89 and 90: K1 contact function [533]In this me
- Page 91 and 92: !CAUTION: Very high currents can ar
- Page 93 and 94: For applications which use the reve
- Page 95 and 96: It is possible to use just one digi
- Page 97 and 98: Line main voltage L1-L38.10.2 Statu
- Page 99 and 100: 8.11 Alarm listThe alarm list is ge
- Page 101 and 102: whether they need a Reset signal (m
- Page 103 and 104: 100 Protection and alarm Emotron AB
- Page 105: Observation Fault indication Cause
- Page 109 and 110: 106 Maintenance Emotron AB 014135-0
- Page 111 and 112: 12.3.1 Cable kit for external curre
- Page 113 and 114: 110 Options Emotron AB 01-4135-01r2
- Page 115 and 116: Table 19Typical motor power at main
- Page 117 and 118: Table 21Typical motor power at main
- Page 119 and 120: 13.2 General electrical specificati
- Page 121 and 122: Table 25Power lossesModelPower loss
- Page 123 and 124: 13.5 Derating at highertemperatureB
- Page 125 and 126: 13.9 Semi-conductor fusesAlways use
- Page 127 and 128: Table 27Parameter listMenuno.Functi
- Page 129 and 130: Table 27Parameter listMenuno.Functi
- Page 131 and 132: Table 27Parameter listMenuno.Functi
- Page 133 and 134: Table 27Parameter listMenuno.Functi
- Page 135: Operation R .......................
- Page 138: Emotron AB, Mörsaregatan 12, SE-25
Observation Fault indication Cause SolutionThe motor is runningbut an alarm isgiven.The motor jerks etc.The monitor functiondoes not work.F12(Shorted thyristor)F15(Serial communication contactbroken)When starting, motor reachesfull speed but it jerks orvibrates.Starting or stopping time toolong.No alarm or pre-alarmPerhaps a damaged thyristor.Bypass contactor is used butparameter [340] ’Bypass’ is notset to “on”.Serial communication contact broken.If “Torque control” or “Pump control”is selected, it is necessary toinput motor data into the system.When stop command is given, a freewheelstop is made. Initiate a resetand a restart. If alarm F14 appearsimmediately, contact your local <strong>MSF</strong>sales outlet.If the motor must be started urgently,the softstarter can start the motordirect on-line (DOL). Set the startmethod to DOL in this case (parameter[310]=4).Set parameter [340] Bypass to on.Initiate a reset and try to establishcontact. Check contacts, cables andoption board.Verify- Serial communication unit address[270].- Baudrate [271].- Parity [272].If the fault is not found, run themotor from the control panel ifurgent, see also manual for serialcommunication.Configure nominal motor data inmenus [210]-[215]. Select theproper torque control alternative inmenu [310] (linear or square)according to the load characteristic.Select a correct initial- and endtorque at start in menus [311] and[312]. If ’Bypass’ is selected, checkthat the current transformers arecorrectly connected.Start time too short. Increase start time [315].If voltage control is used as startmethod, the initial voltage at startAdjust initial voltage at start [311].may be too low. Starting voltageincorrectly set.Motor too small in relation to ratedcurrent of softstarter.Motor too large in relation to loadof softstarter.Starting voltage not setcorrectly.Ramp times not set correctly.Motor too large or too small inrelation to load.It is necessary to input nominalmotor data for this function.Incorrect alarm margins or normalload.Use a smaller model of the softstarter.Use larger model of softstarter.Readjust the start ramp.Select the current limit function.Readjust the start and/or stop ramptime.Change to another motor size.Input nominal motor data in menus[210]-[215]. Adjust alarm marginsand normal load in menus [402] -[412]. Use Auto set [411] if needed.If a Bypass contactor is used, checkthat the current transformers arecorrectly connected.<strong>Emotron</strong> AB 01-4135-01r2 Troubleshooting 103