11.07.2015 Views

Krohne Mass Flow Meter Tech Sheet - Don Johns

Krohne Mass Flow Meter Tech Sheet - Don Johns

Krohne Mass Flow Meter Tech Sheet - Don Johns

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

3 INSTALLATIONOPTIMASS 1000Mounting positions1 The meter can be mounted at an angle but it is recommended that the flow is uphill.2 Avoid mounting the meter with the flow running downhill because it can cause siphoning. If the meter has to be mountedwith the flow running downhill, install an orifice plate or control valve downstream of the meter to maintain backpressure.3 Horizontal mounting with flow running left to right.4 Avoid mounting meter with long vertical runs after the meter as it can cause cavitation. Where the installation includesa vertical run after the meter, install an orifice plate or control valve downstream to maintain backpressure.5 The meter can be mounted vertically but it is recommended that the flow is uphill.6 Avoid mounting the meter vertically with the flow running downhill. This can cause siphoning. If the meter has to beinstalled this way, install an orifice plate or control valve downstream to maintain backpressure.28www.krohne.com03/2009 - 4000040302 - TD OPTIMASS 1000 R03 en

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!