• User V/F pattern operationGroup Code Parameter Name Setting Range Initial UnitFunction group 1 F30 [V/F pattern] 2 0 ~ 2 0F31 [User V/F frequency 1] - 0 ~ 400 15.00 Hz~ ~F38 [User V/F voltage 4] - 0 ~ 100 100 %• Select F30 to 2 {User V/F}.• User can adjust the Volt/Frequency ratio according to V/F pattern of specialized motorsand load characteristics.CAUTIONIn case of using a standard induction motor, if this value is set much higher than linear V/Fpattern, it could result in torque shortage or motor overheating due to over-energizing.When User V/F pattern is active, F28 - [Torque Boost in forward direction] and F29 - [TorqueBoost in reverse direction] are deactivated.Voltage100%F38F36F34LinearV/FF32Startfreq.F31 F33 F35 F37 Basefreq.Freq.• Output voltage adjustmentGroup Code Parameter Name Setting Range Initial UnitFunction group 1 F39[Output voltageadjustment]- 40 ~ 110 100 %• This function is used to adjust the output voltage of the inverter. This is useful when youuse a motor that has a rated voltage lower than the input voltage.100%Voltage70%100% setting70% settingBase freq.Freq.7-18