• Power On Start selectGroup Code Parameter Name Setting Range Initial UnitDrive group drv [Drive mode] 1, 2 0 ~ 4 1Function group 2 H20 [Power On Start select] 1 0 ~ 1 0• Set H20 to 1.• When AC input power is applied to the inverter with drv set to 1 or 2 {Run via controlterminal} ON, motor starts acceleration.• This parameter is inactive when drv is set to 0 {Run via keypad} or 3 {RS485communication}.CAUTIONParticular attention must be directed to this function due to potential hazard as motor starts torun suddenly upon applying AC input power.Input voltageFrequencyRuncommandWhen H20 is 0 When H20 is 1• Restart after fault resetGroup Code Parameter Name Setting Range Initial UnitDrive group drv [Drive mode] 1, 2 0 ~ 4 1Function group 2H21[Restart after fault resetselection]1 0 ~ 1 0• Set H21 to 1.• Motor starts acceleration if drv is set to 1 or 2 and the selected terminal is ON when a faultis cleared.• This parameter is inactive when drv is set to 0 {Run via keypad} or 3 {RS485communication}.CAUTIONParticular attention must be directed to this function due to potential hazard as motor starts torun suddenly after the fault is cleared.7-11