• Rotating direction select via –10 ~ +10[V] input of V1 terminalGroup Code Parameter Name Setting Range Initial UnitDrive group frq [Frequency setting] 2 0 ~ 9 0drv [Drive mode] - 0 ~ 3 1• Set frq to 2.• Inverter is operating as the table below regardless of Drive mode setting.FWD RUN CommandREV RUN Command0 ~ +10 [V] FWD RUN REV RUN-10 ~ 0 [V] REV RUN FWD RUN Motor runs in Forward direction when input voltage to V1-CM is 0~10[V] and FWD RUNcommand is active. When input voltage polarity is reversed to –10~0[V] during FWD RUN, motordecelerates to stop and runs in reverse direction. When input voltage to V1-CM is 0~10[V] and REV RUN command is active, motor runs inReverse direction and if -10~0[V] is input, motor rotating direction is reverse.• FX/RX Run DisableGroup Code Parameter Name Setting Range Initial UnitDrive groupdrCFunction group 1 F 1[Direction of motorrotation select][Forward/Reverse rundisable]- F, r F- 0 ~ 2 0• Select the direction of motor rotation.• 0: Forward and Reverse run enable• 1: Forward run disable• 2: Reverse run disable7-10