• Operating command via FX, RX terminal 2Group Code Parameter Name Setting Range Initial UnitDrive group drv [Drive mode] 2 0 ~ 4 1I/O groupI17[Multi-function inputterminal P1 define]0 0 ~ 27 0I18[Multi-function inputterminal P2 define]1 0 ~ 27 1• Set the drv to 2.• Set I17 and I18 to 0 and 1 to use P1 and P2 as FX and RX terminals.• FX: Operating command setting. Motor runs in forward direction when RX terminal (P2) isOFF.• RX: Direction of motor rotation select. Motor runs in reverse direction when RX terminal(P2) is ON.Freq.FXRX• Operating command via RS485 communicationGroup Code Parameter Name Setting Range Initial UnitDrive group drv [Drive mode] 3 0 ~ 4 1I/O groupI59[Communication protocolselect]- 0 ~ 1 0I60 [Inverter number] - 1 ~ 250 1I61 [Baud rate] - 0 ~ 4 3• Set the drv to 3.• Set I59, I60 and I61correctly.• Inverter operation is performed via RS485 communication.• Refer to Chapter. 13, RS485 communication.7-9