• Function group 2LEDdisplayAddressforcommunicationParameternameH27 A31B [Auto Restarttime]H30 A31E [Motor typeselect]H31 A31F [Number ofmotor poles]Min/MaxrangeDescription0~60 [sec] This parameter sets the timebetween restart tries.0.2~ 22.00.2 0.2kW~ ~22.0 22.0kW2 ~ 12 This setting is displayed via rPMin drive group.FactorydefaultsAdj.during runPage1.0 O 8-207.5 1) X4 X8-16H32 A320 [Rated slipfrequency]0 ~ 10[Hz]fs=fr⎛ rpm×P ⎞− ⎜ ⎟⎝ 120 ⎠2.33 2) XWhere,f s = Rated slip frequencyf r = Rated frequencyrpm = Motor nameplateRPMpolesP = Number of MotorH33 A321 [Motor ratedcurrent]H34 A322 [No LoadMotor Current]H36 A324 [Motorefficiency]H37 A325 [Load inertiarate]0.5~150[A]Enter motor rated current on thenameplate.0.1~ 50 [A] Enter the current value detectedwhen the motor is rotating in ratedrpm after the load connected tothe motor shaft is removed.Enter the 50% of the rated currentvalue when it is difficult tomeasure H34 – [No Load MotorCurrent].50~100[%]0 ~ 2Enter the motor efficiency (seemotor nameplate).Select one of the followingaccording to motor inertia.26.3 X11 X87 X0 X 8-11) : H30 is preset based on inverter rating.0 Less than 10 times1 About 10 times2 More than 10 times2) : H32 ~ H36 factory default values are set based on OTIS-LG motor.5-12