11.07.2015 Views

iG5A, product manual - H2flow

iG5A, product manual - H2flow

iG5A, product manual - H2flow

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Ex 1) The inverter determines the freq reference is lost when DRV- Frq is set to 3 (AnalogV1 input), I 16 to 1 and analog input signal is less than half the value set in I 7.Ex 2) The inverter determines the freq reference is lost when DRV- Frq is set to 6 (V1+I), I16 to 2 and V1 input signal is either below the value set in I 7 or I input value is less thanthe I 12 value. I62: When no frequency command is given for the time set in I63, set the drive mode as thetable below.I62[Drive mode selectafter loss offrequency command]Continuous operation with the frequency0before command loss occurs1 Free run stop (output cut off)2 Decel to stop I54, I55: Multi-function output terminal (MO) or Multi-function relay output (3ABC) is used tooutput information on loss of frequency command to external sequence.Ex) when I16 is set to 2, I62 to 2, I63 to 5.0 sec and I54 to 11, respectively,Setfreq5 secFreqMORuncommand10.8 DB Resistor Enable Duty settingGroup Code Parameter Set Range Initial UnitFunction H75 [Enable duty limit] 1 0 ~ 1 1group 2 H76 [Enable duty] - 0 ~ 30 10 %• Set H75 to 1.• Set %ED (Enable Duty) in H76.10-7

Hooray! Your file is uploaded and ready to be published.

Saved successfully!