P1P7P8CMFX : I17 = 0N.O. : I23 = 18N.C. : I24 = 19FrequencyP4(A contact)P5(B contact)Runcommand10.6 Inverter OverloadGroup Code Parameter Set Range Initial Unit[Multi-function output terminalI/O I546 12select]0 ~ 19groupI55 [Multi-function relay select] 617 Inverter overload prevention function is activated when the current above inverter rated currentflows. Multi-function output terminal (MO) or Multi-function relay (3ABC) is used as the alarm signaloutput during inverter overload trip.10.7 Speed command lossGroup Code Parameter Set Range Initial UnitI/OgroupI16I62I63I54[Select criteria for analog speedcommand loss][Drive mode select at loss ofspeed command][Wait time after loss of speedcommand][Multi-function output terminalselect]I55 [Multi-function relay select] 110 0 ~ 2 0- 0 ~ 2 0- 0.1 ~ 120 1.0 sec0 ~ 1911 1217• Select the Drive mode when frequency reference set via Analog (V1, I) input terminal orcommunication option is lost. I16: This is to set the criteria for analog input signal loss.I16[Criteria for analoginput signal loss]012Disabled (Does not check the analog inputsignal loss)When half the value set in I2, I7, I12 isenteredWhen less than the value set in I 2, I 7, I 12is entered10-6