• Overload tripGroup Code Parameter Set Range Initial UnitFunctiongroup 1F56 [Overload trip select] 1 0 ~ 1 1F57 [Overload trip level] - 30 ~ 200 180 %F58 [Overload trip time] - 0 ~ 60 60 sec• Set F56 to 1.• Inverter output is turned off when motor is overloaded.• Inverter output is turned off when excessive current flows to the motor for F58 – [Overloadtrip time].10.3 Stall preventionGroup Code Parameter Set Range Initial UnitFunctiongroup 1I/OgroupF59 [Stall prevention select] - 0 ~ 7 0F60 [Stall prevention level] - 30 ~ 200 150 %I54[Multi-function output terminalselect]I55 [Multi-function relay select] 70 ~197 12• During acceleration: Motor starts deceleration when current exceeding the value set inF60 flows.• During constant run: Motor decelerates when current exceeding the value set in F60flows.• During deceleration: Motor deceleration is stopped when inverter DC link voltage risesabove a certain voltage level.• F60: The value is set as the percent of motor rated current (H33).• I54, I55: Inverter outputs signals through multi-function output terminal (MO) or relayoutput (3ABC) or external sequence when stall prevention function is activated. Motor stallstatus still can be monitored in these codes though F59 is not selected (000). F59: Stall prevention can be set as the table below.F59 Stall preventionDuringSetting DecelerationDuringconstantspeed17DuringAccelerationBit 2 Bit 1 Bit 00 - - -1 - - 2 - -3 - 4 - -5 - 6 -7 10-3

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!