11.07.2015 Views

iG5A, product manual - H2flow

iG5A, product manual - H2flow

iG5A, product manual - H2flow

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

CHAPTER 10 -PROTECTIVE FUNCTIONS10.1 Electronic ThermalGroup Code Parameter Set Range Initial UnitFunctiongroup 1F50F51F52[ETH (Electronic thermal)select][Electronic thermal level for 1minute][Electronic thermal level forcontinuous]1 0 ~ 1 0- 50 ~ 200 150 %- 50 ~ 150 100 %F53 [Motor type] - 0 ~ 1 0• Select F50 – [Electronic thermal select] to 1.• It activates when the motor is overheated (time-inverse). If current greater than set in F51flows, inverter output is turned off for the preset time in F51- [Electronic thermal level for 1minute]. F51: Enter the value of max current that is capable of flowing to the motor continuously for oneminute. It is set in percent of motor rated current. The value cannot be set lower than F52. F52: Enter the amount of current for continuous operation. Normally motor rated current isused. It cannot be set greater than F51. F53: For an inductance motor, cooling effects decrease when a motor is running at low speed.A special motor is a motor that uses a separately powered cooling fan maximize cooling effecteven in low speed.F53[Motor type]01Standard motors having a cooling fan directlyconnected to the shaftSpecial motor that uses a separately poweredcooling fan.Current forcontinuous [%]100F53 = 195F53 = 265Freq [Hz]20 6010-1