• 4: FDT-5 Activated as B contact contrast to FDT-4.Active condition:Accel time: Run Frequency >= FDT LevelDecel time: Run Frequency > (FDT Level – FDT Bandwidth/2)Group Display Parameter Name Setting Range Default Unit[Detected FrequencyHzI/O group I52- 30.00level]0 ~ 400[Detected FrequencyI53-10.00Bandwidth]• Cannot be set above Max frequency (F21).When setting I52 and I53 to 30.0Hz and 10.0 Hz, respectively30Hz25HzFreq.MORuncommand• 5: Overload (OLt) Refer to page 10-2.• 6: Inverter Overload (IOLt) Refer to page 10-6.• 7: Motor stall (STALL) Refer to page 10-3.• 8: Over voltage trip (Ovt) Activated when over voltage trip occurs due to DC link voltage exceeded 400Vdc for200V class and 820Vdc for 400V class.• 9: Low voltage trip (Lvt) Activated when low voltage trip occurs due to DC link voltage under 180Vdc for 200Vclass and 360Vdc for 400V class.• 10: Inverter heatsink overheat (OHt) Activated when the heatsink is overheated.• 11: Command loss Activated when Analog (V1,I) and RS485 communication commands are lost.9-10