9.4 Analog OutputGroup Display Parameter Name Setting Range Default UnitI/O group I50 [Analog output item select] - 0 ~ 3 0[Analog output levelI51- 10 ~ 200 100 %adjustment]• Output item and the level from the AM terminal are selectable and adjustable. I50: The selected item will be output to Analog output terminal (AM).I50Analog outputitem selectItem corresponding to 10V200V 400V0 Output frequency. Max Frequency (F21)1 Output current150% of Inverter ratedcurrent2 Output voltage 282Vac 564Vac3Inverter DC linkvoltage400Vdc 800Vdc I51: If you want to use Analog output value as a gauge input, the value can be adjustableaccording to various gauge specifications.AM0 ~ 10VdcCM9-6