Select 1 and 2 for F70The center value of analogue input (selected by the set value of I6~I15) asstandard, if the input is big it gets (+), if small (-) and gets reflected in theoutput frequency as the ratio set in F71. Select 3 for F70OV as standard, if analog input voltage is big, it gets (+), if small (-) and getsreflected in the output frequency as the ratio set in F71. DRAW operation exampleIf draw operation is set to 30Hz, F70=3(V1: -10V ~10V), F71=10.0% selected,(I3~I15 = plant shipment) Frequency that gets changed by DRAW operation is27Hz(V1=-10V) ~33Hz(V1=10V)CautionWhen operating DRAW, set command frequency to FRQ/FRQ2 and set therest of it from F70(DRAW mode select). For example, if FRQ=2(V1) andF70=1(V1), it does not operate.8-27