8.11 Speed searchGroup Display Parameter Name Setting Range Default UnitFunctiongroup 2H22 [Speed search select] - 0 ~ 15 0H23 [Current level] - 80 ~ 200 100 %I/O groupH24 [Speed search P gain] -0 ~ 9999100H25 [Speed search I gain] -200[Multi-function outputI5415 12terminal select]0 ~ 18I55 [Multi-function relay select] 1517• This is used to prevent possible fault from occurring if the inverter outputs the voltageduring operation after the load is removed.• The inverter estimates the motor rpm based on output current. Therefore, detecting exactspeed is difficult.The following table shows 4 types of Speed search selection.H22 Speed searchduring H20 –[Power ON start]Speed searchduring InstantPower FailurerestartSpeed searchduring H21-[Restart afterfault reset]Speed searchduringAccelerationBit 3 Bit 2 Bit 1 Bit 00 - - - -1 - - - 2 - - -3 - - 4 - - -5 - - 6 - -7 - 8 - - -9 - - 10 - -11 - 12 - -13 - 14 -15 H23: Limits current during Speed search. Set as the percent of H33. H24, H25: Speed search is activated via PI control. Adjust P gain and I gain corresponding tothe load characteristics. I54, I55: Signal of active Speed search is given to external sequence via Multi-function outputterminal (MO) and Multi-function relay output (3ABC).8-16