• Up-down mode selectGroup Display Parameter Name Setting Range Default UnitDrivegroupI/OgroupFrq [Frequency setting method] 8 0~8 0I17[Multi-function inputterminal P1 define]0 0I23[Multi-function input0 ~ 2715terminal P7define]6I24[Multi-function inputterminal P8define]167F65 [Up-down mode select] - 0~2 0Functiongroup 1 F66 [Up-down step frequency] - 0~400 0.00 Hz• Select 8 in Frq code of drive group• Select the terminal which uses as a up-down drive among multi-function input (P1~P8)• Operates in selected mode as a step frequency set in F66. The up-down mode is Select as followsF65 Up/down select 01The reference frequency is increased according to base ofMax./Min. frequency.(Initial value)Increased as many as step frequency (F66) according toedge input2 Combination of 0 and 1F66 Step frequency Frequency increased according to edge input When F65 is 0: If you press UP, it is increased up to Max. frequency as a speed set in theabove. (If frequency limit exist, speed is increased up to upper limit.) If press DOWN, It isdecreased as a speed set in the above regardless of stop method. (If frequency limit exist,speed is decreased up to lower limit.)P1 I17 = 0P6P7P8CMI22 = 25I23 = 15I24 = 16FrequencyP7 (UP)P8 (DOWN)Runcommand(FX)SavedFrequencyOutputFrequencyP6(CLEAR)P7 (UP)Drivecommend (FX)8-5