LIPA<br />
METERED<br />
SERVICE<br />
THE FOLLOWING 2 ONE-LINE SCHEMATICS OUTLINE THE CONNECTIONS<br />
LIPA WILL ALLOW FOR THE INTERCONNECTION OF OPTIONAL STANDBY<br />
SYSTEM EQUIPMENT. THE INTENT OF THE INTERCONNECTION<br />
SCHEMES IS TO PREVENT BOTH BACKFEED INTO THE LIPA<br />
ELECTRIC DISTRIBUTION SYSTEM, AND UNINTENTIONAL PARALLEL<br />
OPERATION WITH AN ENERGIZED LIPA SYSTEM. IMPROPER<br />
PARALLEL OPERATION CAN RESULT IN SERIOUS DAMAGE TO THE<br />
GENERATOR, THE LIPA DISTRIBUTION SYSTEM, OR BOTH, AND BE<br />
A SAFETY HAZARD TO PERSONNEL.<br />
MAIN<br />
DISCONNECT<br />
NOTE: CUSTOMER'S METERING<br />
EQUIPMENT MUST BE<br />
PLACARDED THAT A GENERATOR IS PRESENT<br />
LIPA<br />
METERED<br />
SERVICE<br />
TO ENTIRE<br />
LOAD<br />
GENERATOR<br />
PROTECTIVE<br />
CIRCUIT BREAKER<br />
DOUBLE THROW SWITCH<br />
FIG. 1: STANDBY GENERATOR FOR ENTIRE LOAD.<br />
MAIN<br />
DISCONNECT<br />
NOTE: CUSTOMER'S METERING<br />
EQUIPMENT MUST BE<br />
LOADS NOT<br />
BACKED UP<br />
BY GENERATOR<br />
PLACARDED THAT A GENERATOR IS PRESENT<br />
STANDBY LOAD<br />
GENERATOR<br />
PROTECTIVE<br />
CIRCUIT BREAKER<br />
DOUBLE THROW SWITCH<br />
FIG. 2: STANDBY GENERATOR FOR PARTIAL LOADS<br />
OPTIONAL STANDBY SYSTEMS<br />
D35<br />
Section 11 - Drawings<br />
G<br />
GENERATOR<br />
G<br />
GENERATOR