LIPA<br />

METERED<br />

SERVICE<br />

THE FOLLOWING 2 ONE-LINE SCHEMATICS OUTLINE THE CONNECTIONS<br />

LIPA WILL ALLOW FOR THE INTERCONNECTION OF OPTIONAL STANDBY<br />

SYSTEM EQUIPMENT. THE INTENT OF THE INTERCONNECTION<br />

SCHEMES IS TO PREVENT BOTH BACKFEED INTO THE LIPA<br />

ELECTRIC DISTRIBUTION SYSTEM, AND UNINTENTIONAL PARALLEL<br />

OPERATION WITH AN ENERGIZED LIPA SYSTEM. IMPROPER<br />

PARALLEL OPERATION CAN RESULT IN SERIOUS DAMAGE TO THE<br />

GENERATOR, THE LIPA DISTRIBUTION SYSTEM, OR BOTH, AND BE<br />

A SAFETY HAZARD TO PERSONNEL.<br />

MAIN<br />

DISCONNECT<br />

NOTE: CUSTOMER'S METERING<br />

EQUIPMENT MUST BE<br />

PLACARDED THAT A GENERATOR IS PRESENT<br />

LIPA<br />

METERED<br />

SERVICE<br />

TO ENTIRE<br />

LOAD<br />

GENERATOR<br />

PROTECTIVE<br />

CIRCUIT BREAKER<br />

DOUBLE THROW SWITCH<br />

FIG. 1: STANDBY GENERATOR FOR ENTIRE LOAD.<br />

MAIN<br />

DISCONNECT<br />

NOTE: CUSTOMER'S METERING<br />

EQUIPMENT MUST BE<br />

LOADS NOT<br />

BACKED UP<br />

BY GENERATOR<br />

PLACARDED THAT A GENERATOR IS PRESENT<br />

STANDBY LOAD<br />

GENERATOR<br />

PROTECTIVE<br />

CIRCUIT BREAKER<br />

DOUBLE THROW SWITCH<br />

FIG. 2: STANDBY GENERATOR FOR PARTIAL LOADS<br />

OPTIONAL STANDBY SYSTEMS<br />

D35<br />

Section 11 - Drawings<br />

G<br />

GENERATOR<br />

G<br />

GENERATOR