2012 Edition <strong>Red</strong>book<br />
LIPA APPROVED<br />
CT/TRANS CABINET<br />
LIPA APPROVED<br />
400-1200 C.T CABINET<br />
MOUNTED TO WALL<br />
NOTES:<br />
NEUTRAL BUS<br />
OR APPROVED STRUCTURE.(Note4)<br />
LOAD (LINE)<br />
SIDE<br />
CT<br />
TRANSFORMER RATED<br />
METER SOCKET<br />
AND TEST SWITCH<br />
ENCLOSURE<br />
CURRENT<br />
COPPER BUS<br />
WALL<br />
THE BOND WIRE SHALL BE GREEN OR MARKED AS SUCH AND SHALL BE BONDED TO THE<br />
METER SOCKET ENCLOSURE AND TO THE CT. CABINET.<br />
1-1/4" CONDUIT MIN.<br />
WITH CONTROL CABLE<br />
(SEE NOTE #6 AND #7)<br />
1. LIPA APPROVED CURRENT TRANSFORMER CABINET AND METER SOCKET SHALL NOT BE LOCATED IN ANY<br />
AREA CLASSIFIED AS A HALLWAY, CONFINED SPACE, OR WHERE A LADDER ACCESS IS REQUIRED. (Ref Sect-8.2.3)<br />
2. PITS AND VAULTS BELOW GRADE ARE NOT ACCEPTABLE AS METER ROOMS. METER<br />
ENCLOSURES OR CURRENT TRANSFORMER CABINETS SHALL NOT BE LOCATED IN THESE<br />
TYPES OF AREAS.<br />
3. REFER TO NEC ARTICLE 250 FOR GROUNDING AND BONDING REQUIREMENT.<br />
4. CENTERLINE OF C.T CABINET SHALL BE A MAXIMUM OF 5'-0" OR A MINIMUM OF 3'-6"<br />
FROM FINISHED FLOOR.<br />
CT<br />
LINE (LOAD)<br />
SIDE<br />
LIPA APPROVED<br />
5. CONTROL CABLE SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR, SEE SECT. 8.9. FINAL<br />
TERMINATION IN THE METER AND TRANSFORMER CABINET SHALL BE DONE BY LIPA<br />
6. MAXIMUM DISTANCE OF METER SOCKET FROM C.T CABINET SHALL BE DETERMINED BY LIPA<br />
7. WHEN PVC CONDUIT IS USED A # 8 AWG 600 VOLT FACTORY INSULATED COPPER BOND<br />
WIRE SHALL BE INSTALLED BETWEEN THE METER SOCKET ENCLOSURE AND THE C.T CABINET<br />
CT<br />
TRANSFORMER RATED METER SOCKET<br />
AND<br />
TRANSFORMER (TYP)<br />
8. REFER TO DRAWINGS D26, D27, D28, AND D29 FOR OTHER REQUIREMENTS.<br />
9. LINE AND LOAD SIDES OF THE COMPARTMENT SHALL BE CLEARLY AND PERMANENTLY<br />
MARKED.<br />
CURRENT TRANSFORMER CABINET INSTALLATION<br />
D30<br />
EXIT THROUGH MFG.<br />
KNOCKOUT ONLY<br />
6'-0" MAXIMUM<br />
4'-0" MINIMUM<br />
FINISHED GRADE<br />
DWG. BASED ON<br />
LIPA CS 8606