NOTES: 1. ALL ITEMS SHOWN SHALL BE FURNISHED AND INSTALLED BY THE CUSTOMER UNLESS OTHERWISE STATED. 2. ALL METER PAN ASSEMBLIES SHALL BE AS APPROVED BY LIPA. METER SOCKETS SHALL BE EQUIPPED WITH A FIFTH JAW LOCATED IN THE NINE O' CLOCK POSITION. 3. GAS PIPES SHALL NOT BE USED AS A GROUNDING ELECTRODE. 4. GROUNDING SHALL BE IN ACCORDANCE WITH THE APPLICABLE SECTIONS OF ARTICAL 250 OF THE NATIONAL ELECTRICAL CODE. WALL 6. SERVICE ENTRANCE TYPE "SE" CABLE SHALL BE AS APPROVED BY LIPA AND CAN BE USED WITHOUT BEING ENCASED IN IN CONDUIT ON THE LINE SIDE OF THE METER ENCLOSURE, PROVIDING IT WILL NOT COME IN CONTACT WITH ANY AWNINGS, SHUTTERS, SIGNS, OR ANY OTHER OBJECTS THAT CAN CAUSE MECHANICAL INJURY TO THE CABLE. WHEN INSTALLED ON THE SIDE OF A BUILDING ADJACENT TO A DRIVEWAY THE CABLE SHALL BE ENCASED IN CONDUIT. PROTECTIVE SLEEVING ON TYPE "SE" CABLE IS REQUIRED TO A HEIGHT OF EIGHT FEET ABOVE FINISHED GRADE. THE SLEEVE SHALL BE SPACED APPROXIMATELY ONE INCH FROM THE TOP OF THE METER PAN. WEATHER TIGHT TYPE "SE" CONNECTORS SHALL BE USED FOR CONNECTION TO THE METER ENCLOSURE. 7. A FOUR FOOT CLEARANCE FROM FLOOR TO CEILING SHALL BE MAINTAINED IN FRONT OF THE METER INSTALLATION FOR SAFE ACCESS. 12" MIN FINISHED FLOOR OR GRADE UNIT IDENTIFICATION SEE NOTE 9 INTERNAL BUSING OVERHEAD ENTRANCE (SEE NOTES 5 & 6) �� �� �� �� GROUND CONDUCTOR TO NEUTRAL OF CUSTOMERS MAIN DISCONNECT PANEL ALTERNATE UNDERGROUND CONDUIT ENTRANCE (SEE NOTE 11) 1/2" x 8' CU WELD OR 5/8" X 8' CU PLATED GROUND ROD 8. IN ADDITION TO LIPA REQUIREMENTS, INSTALLATIONS, MAY BE SUBJECT TO THE APPROVAL OF THE LOCAL ELECTRICAL INSPECTION AGENCY AS WELL AS LOCAL MUNICIPALITIES HAVING JURISDICTION. 9. ALL METER PANS AND SERVICE DISCONNECT SWITCHES SHALL BE PERMANENTLY STENCILED INTERNALLY AND EXTERNALLY WITH THE BUILDING AND/OR SUITE NUMBER TO IDENTIFY THE PORTION OF THE PREMISES BEING SERVED. 10. ONLY FACTORY PREFABRICATED KNOCKOUTS ON METER ENCLOSURES SHALL BE USED. UNDERGROUND AND OVERHEAD SERVICE SINGLE PHASE SELF CONTAINED METERS OUTDOOR MULTI-METER SOCKET ENCLOSURE 12" MIN TOP OF METER GLASS 6'-0" MAX. 3'-0" MIN. 5. OVERHEAD SERVICE CONDUITS AND PROTECTIVE SLEEVES SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE(NEC). 11. RIGID METALLIC CONDUIT (RMC) AND RIGID NON-METALLIC CONDUIT (RNC) (SCHD. 40 OR 80 RESPECTIVELY, AS REQUIRED), ARE APPROVED FOR BELOW GRADE USE. ELECTRIC METALLIC TUBING (EMT) AND INTERMEDIATE METALLIC CONDUIT (IMC) ARE NOT APPROVED FOR BELOW GRADE INSTALLATION. D21 Section 11 - Drawings 12. LINE AND LOAD CONDUCTORS SHALL NOT CROSS WITHIN THE METER ENCLOSURE. RIGHT SIDE OF METER ENCLOSURE SHALL NOT BE USED AS A RACEWAY EXCEPT FOR ROUTING NEUTRAL CABLE AS SHOWN. NEUTRAL CABLE SHALL BE NEATLY TRAINED SO AS TO PERMIT PROPER OPERATION OF THE LEVER, AND SHALL BE COVERED WIRE. WALL DWG. BASED ON LIPA CS 8009
2012 Edition Redbook 15'-0"MIN LEAVE 3'-0" OF CONDUCTOR FOR CONNECTION. FINAL CONNECTION BY LIPA. CONDUCTORS TO BE IDENTIFIED WITH COLORED TAPE SERVICE DROP CABLE OVERHEAD SERVICE CONDUIT (SEE NOTES 5 & 6) 3'-0"MIN 6'-0"MAX NOTES: CONDUIT STRAPS ADEQUATELY SECURED TOP OF METER GLASS 4' CLEARANCE FLOOR TO CEILING "LB" CONDULET GROUND CONDUCTOR FINISHED GRADE 1/2" x 8' CU WELD OR 5/8" X 8' CU PLATED GROUND ROD THE NATIONAL ELECTRIC CODE. INSIDE WALL MOUNT PLUMB & LEVEL TO CUSTOMER'S 1. ALL ITEMS SHOWN SHALL BE FURNISHED AND INSTALLED BY THE CUSTOMER UNLESS OTHERWISE STATED. 2. ALL METER PAN ASSEMBLIES SHALL BE AS APPROVED BY LIPA. METER SOCKET ASSEMBLY SHALL BE EQUIPPED WITH A LEVER OPERATED, JAW RELEASE BYPASS MECHANISM. 4. GROUNDING SHALL BE IN ACCORDANCE WITH THE APPLICABLE SECTIONS OF ARTICLE 250 OF 6. SERVICE ENTRANCE TYPE "SE" CABLE SHALL BE AS APPROVED BY LIPA AND CAN BE USED WITHOUT BEING ENCASED IN CONDUIT ON THE LINE SIDE OF THE METER ENCLOSURE, PROVIDING IT WILL NOT COME IN CONTACT WITH ANY AWNINGS, SHUTTERS, SIGNS, OR ANY OTHER OBJECTS THAT CAN CAUSE MECHANICAL INJURY TO THE CABLE. WHEN INSTALLED ON THE SIDE OF A BUILDING ADJACENT TO A DRIVEWAY THE CABLE SHALL BE ENCASED IN CONDUIT. PROTECTIVE SLEEVING ON TYPE "SE" CABLE IS REQUIRED TO A HEIGHT OF EIGHT FEET ABOVE FINISHED GRADE. THE SLEEVE SHALL BE SPACED A MINIMUM OF ONE INCH FROM THE TOP OF THE METER PAN. WEATHERTIGHT TYPE "SE" CONNECTORS SHALL BE USED FOR CONNECTION TO THE METER ENCLOSURE. 6"MIN SERVICE ENTRANCE WEATHER HEAD 10"MAX POINT OF ATTACHMENT OUTDOOR POLYPHASE METER SOCKET CONDUIT MAIN DISCONNECT TO NEUTRAL OF CUSTOMER'S MAIN DISTRIBUTION PANEL NEUTRAL LUG ALTERNATE POSITION OF LOAD CONDUIT HUB BONDING BUSHING & LOCKNUT 3. GAS SERVICE PIPES SHALL NOT BE USED AS A GROUNDING ELECTRODE OVERHEAD SERVICE POLY-PHASE SELF CONTAINED METERS 200 AMPERE SOCKET METER INSTALLATION N A A LINE SIDE B C B C LOAD SIDE METER SOCKET PHASE CONDUCTOR IDENTIFICATION MIN. 2" COLORED TAPE DELTA WYE 240/120 208Y/120 PHASE A BLUE BLUE PHASE B BLACK BLACK PHASE C ORANGE RED NEUTRAL WHITE OR GRAY 5. OVERHEAD SERVICE CONDUITS AND PROTECTIVE SLEEVES SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE.(NEC) 7. A FOUR FOOT CLEARANCE FROM FLOOR TO CEILING SHALL BE MAINTAINED IN FRONT OF THE METER INSTALLATION FOR SAFE ACCESS. 8. IN ADDITION TO LIPA's REQUIREMENTS, INSTALLATIONS MAY BE SUBJECT TO THE APPROVAL OF THE LOCAL ELECTRICAL INSPECTION AGENCY AS WELL AS LOCAL MUNICIPALITIES. 9. ONLY FACTORY PREFABRICATED KNOCKOUTS ON METER ENCLOSURES SHALL BE USED. 10. LINE AND LOAD CONDUCTORS SHALL NOT CROSS WITHIN THE METER ENCLOSURE. RIGHT SIDE OF METER ENCLOSURE SHALL NOT BE USED AS A RACEWAY EXCEPT FOR ROUTING NEUTRAL CABLE AS SHOWN. NEUTRAL CABLE SHALL BE NEATLY TRAINED SO AS TO PERMIT PROPER OPERATION OF THE LEVER, AND SHALL BE COVERED WIRED. 11. CONDUIT SHALL BE RIGID METAL OR SCHEDULE 80 PVC. D22 DWG. BASED ON LIPA CS 8207
- Page 21 and 22: 2012 Edition Redbook 4.0 SERVICE CO
- Page 23 and 24: 2012 Edition Redbook G) Where it is
- Page 25 and 26: 2012 Edition Redbook 4.3.9 For open
- Page 27 and 28: 2012 Edition Redbook 4.7.6 For dire
- Page 29 and 30: 2012 Edition Redbook 4.11.2 When th
- Page 31 and 32: 2012 Edition Redbook and its compon
- Page 33 and 34: 2012 Edition Redbook 5.0 SERVICE EQ
- Page 35 and 36: 2012 Edition Redbook 6.0 SERVICE AT
- Page 37 and 38: 2012 Edition Redbook 7.0 GROUNDING
- Page 39 and 40: 2012 Edition Redbook 8.0 REVENUE ME
- Page 41 and 42: 2012 Edition Redbook • insulating
- Page 43 and 44: 2012 Edition Redbook the neutral bu
- Page 45 and 46: 2012 Edition Redbook 9.0 MOTORS AND
- Page 47 and 48: 2012 Edition Redbook Operating Volt
- Page 49 and 50: 2012 Edition Redbook 10.0 SPECIAL P
- Page 51 and 52: 2012 Edition Redbook 11.0 GENERAL D
- Page 53 and 54: 2012 Edition Redbook V A A: CLEARAN
- Page 55 and 56: 2012 Edition Redbook ROOFING ROOF M
- Page 57 and 58: 2012 Edition Redbook 6" MIN. 10" MA
- Page 59 and 60: 2012 Edition Redbook NOTE: SERVICE
- Page 61 and 62: 2012Edition Redbook 6" MIN. 10" MAX
- Page 63 and 64: 2012 Edition Redbook NOTES: 1. CONT
- Page 65 and 66: 2012 Edition Redbook GRADE 4" SECON
- Page 67 and 68: 2012 Edition Redbook NOTES: 1. * IN
- Page 69 and 70: 2012 Edition Redbook 3'-0" MIN / 6'
- Page 71: 2012 Edition Redbook TOP OF METER G
- Page 75 and 76: 2012 Edition Redbook GAS METER LEFT
- Page 77 and 78: 2012 Edition Redbook METAL CAP OR A
- Page 79 and 80: 2012Edition Redbook 5" NEUTRAL BUS
- Page 81 and 82: 2012 Edition Redbook LIPA APPROVED
- Page 83 and 84: 2012 Edition Redbook METAL ENCL. SI
- Page 85 and 86: 2012 Edition Redbook WIRE SIZED IN
- Page 87 and 88: 2012 Edition Redbook 12.0 SECONDARY
- Page 89 and 90: 2012 Edition Redbook SUNRISE HWY. B
- Page 91 and 92: 2012 Edition Redbook ARRANDALE AVE.
- Page 93 and 94: 2012 Edition Redbook CLINTON RD. GA
- Page 95 and 96: 2012 Edition Redbook HEMPSTEAD (SHE
- Page 97 and 98: 2012 Edition Redbook HEMPSTEAD (SHE
- Page 99 and 100: 2012 Edition Redbook HUNTINGTON VIL
- Page 101 and 102: 2012 Edition Redbook ROCKAWAY PENIN
- Page 103 and 104: 2012 Edition Redbook MIDDLE COUNTRY
- Page 105 and 106: 2012 Edition Redbook VALLEY STREAM
- Page 108 and 109: Notice This book is updated on a re
- Page 110: www.lipower.org
NOTES:<br />
1. ALL ITEMS SHOWN SHALL BE FURNISHED AND INSTALLED BY THE CUSTOMER UNLESS OTHERWISE STATED.<br />
2. ALL METER PAN ASSEMBLIES SHALL BE AS APPROVED BY LIPA. METER SOCKETS SHALL BE EQUIPPED WITH A FIFTH JAW<br />
LOCATED IN THE NINE O' CLOCK POSITION.<br />
3. GAS PIPES SHALL NOT BE USED AS A GROUNDING ELECTRODE.<br />
4. GROUNDING SHALL BE IN ACCORDANCE WITH THE APPLICABLE SECTIONS OF ARTICAL 250 OF THE NATIONAL ELECTRICAL<br />
CODE.<br />
WALL<br />
6. SERVICE ENTRANCE TYPE "SE" CABLE SHALL BE AS APPROVED BY LIPA AND CAN BE USED WITHOUT BEING ENCASED IN<br />
IN CONDUIT ON THE LINE SIDE OF THE METER ENCLOSURE, PROVIDING IT WILL NOT COME IN CONTACT WITH ANY AWNINGS,<br />
SHUTTERS, SIGNS, OR ANY OTHER OBJECTS THAT CAN CAUSE MECHANICAL INJURY TO THE CABLE. WHEN INSTALLED ON THE<br />
SIDE OF A BUILDING ADJACENT TO A DRIVEWAY THE CABLE SHALL BE ENCASED IN CONDUIT. PROTECTIVE SLEEVING ON<br />
TYPE "SE" CABLE IS REQUIRED TO A HEIGHT OF EIGHT FEET ABOVE FINISHED GRADE. THE SLEEVE SHALL BE SPACED<br />
APPROXIMATELY ONE INCH FROM THE TOP OF THE METER PAN. WEATHER TIGHT TYPE "SE" CONNECTORS SHALL BE USED<br />
FOR CONNECTION TO THE METER ENCLOSURE.<br />
7. A FOUR FOOT CLEARANCE FROM FLOOR TO CEILING SHALL BE MAINTAINED IN FRONT OF THE METER INSTALLATION FOR<br />
SAFE ACCESS.<br />
12" MIN<br />
FINISHED FLOOR OR GRADE<br />
UNIT IDENTIFICATION<br />
SEE NOTE 9<br />
INTERNAL BUSING<br />
OVERHEAD ENTRANCE<br />
(SEE NOTES 5 & 6)<br />
�� ��<br />
�� ��<br />
GROUND CONDUCTOR TO<br />
NEUTRAL OF CUSTOMERS<br />
MAIN DISCONNECT PANEL<br />
ALTERNATE UNDERGROUND<br />
CONDUIT ENTRANCE<br />
(SEE NOTE 11)<br />
1/2" x 8' CU WELD OR<br />
5/8" X 8' CU PLATED GROUND ROD<br />
8. IN ADDITION TO LIPA REQUIREMENTS, INSTALLATIONS, MAY BE SUBJECT TO THE APPROVAL OF THE LOCAL ELECTRICAL<br />
INSPECTION AGENCY AS WELL AS LOCAL MUNICIPALITIES HAVING JURISDICTION.<br />
9. ALL METER PANS AND SERVICE DISCONNECT SWITCHES SHALL BE PERMANENTLY STENCILED INTERNALLY AND EXTERNALLY<br />
WITH THE BUILDING AND/OR SUITE NUMBER TO IDENTIFY THE PORTION OF THE PREMISES BEING SERVED.<br />
10. ONLY FACTORY PREFABRICATED KNOCKOUTS ON METER ENCLOSURES SHALL BE USED.<br />
UNDERGROUND AND OVERHEAD SERVICE<br />
SINGLE PHASE SELF CONTAINED METERS<br />
OUTDOOR MULTI-METER SOCKET ENCLOSURE<br />
12" MIN<br />
TOP<br />
OF METER GLASS<br />
6'-0" MAX.<br />
3'-0" MIN.<br />
5. OVERHEAD SERVICE CONDUITS AND PROTECTIVE SLEEVES SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE(NEC).<br />
11. RIGID METALLIC CONDUIT (RMC) AND RIGID NON-METALLIC CONDUIT (RNC) (SCHD. 40 OR 80 RESPECTIVELY,<br />
AS REQUIRED), ARE APPROVED FOR BELOW GRADE USE. ELECTRIC METALLIC TUBING (EMT) AND INTERMEDIATE<br />
METALLIC CONDUIT (IMC) ARE NOT APPROVED FOR BELOW GRADE INSTALLATION.<br />
D21<br />
Section 11 - Drawings<br />
12. LINE AND LOAD CONDUCTORS SHALL NOT CROSS WITHIN THE METER ENCLOSURE. RIGHT SIDE OF METER ENCLOSURE<br />
SHALL NOT BE USED AS A RACEWAY EXCEPT FOR ROUTING NEUTRAL CABLE AS SHOWN. NEUTRAL CABLE SHALL<br />
BE NEATLY TRAINED SO AS TO PERMIT PROPER OPERATION OF THE LEVER, AND SHALL BE COVERED WIRE.<br />
WALL<br />
DWG. BASED ON<br />
LIPA CS 8009