NOTES:<br />
1. * DENOTES ITEMS PERFORMED BY CONTRACTOR / CUSTOMER.<br />
2. UTILITY CONNECTS CONDUIT TO SPLICE BOX AND MAKES SERVICE CONNECTIONS IN SPLICE BOX.<br />
3. 200 AMP SERVICES SHALL BE RUN IN ONE 2" CONDUIT MIN. 320 AMP SERVICES SHALL BE RUN IN A 3 1/2"<br />
CONDUITS MIN. . 400 AMP SERVICES SHALL BE RUN IN A SINGLE 4" CONDUIT. ALL SERVICES SHALL BE RUN FROM THE<br />
METER PAN TO A SPLICE BOX AT THE PROPERTY LINE.<br />
4. 600 AND 800 AMP SERVICES SHALL BE RUN IN TWO PARALLEL 4" CONDUITS FROM THE TRANS S CABINET TO A<br />
SPLICE BOX AT THE PROPERTY LINE. 600 AND 800 AMP SERVICES ARE INSTALLED, OWNED AND MAINTAINED BY THE CUSTOMER.<br />
5. UNDER NO CIRCUMSTANCES SHALL A CUSTOMER / CONTRACTOR ENTER A LIPA SPLICE BOX.<br />
12" MIN. 24"<br />
GAS SERVICE<br />
ELECTRIC SERVICE<br />
CABLE IN CONDUIT<br />
COMMUNICATIONS<br />
FACILITIES<br />
SERVICE TRENCH<br />
SERVICE CONDUIT SYSTEM *<br />
(MIN. SCHD 40)<br />
* TERMINATE CONDUIT<br />
24" AWAY FROM SPLICE<br />
BOX ON CENTERLINE.<br />
* SEAL CABLE ENDS<br />
24" MIN.<br />
PLYWOOD *<br />
SCHD. 40 CONDUIT *<br />
24"<br />
PLAN VIEW<br />
ANGLE OF APPROACH TO SPLICE BOX<br />
TO BE DETERMINED BY LOCAL FIELD<br />
CONDITIONS AND APPROVAL BY UTILITY.<br />
TEMPORARY 48" x 48" x 1/2"<br />
UTILITY CABLE<br />
IN CONDUIT<br />
SPLICE BOX<br />
10 FOOT MINIMUM CABLE *<br />
COILED & COVERED<br />
WITH 4'x4'x1/2" PLYWOOD<br />
SEAL CABLE *<br />
ENDS<br />
DUCTSEAL CONDUIT *<br />
(TEMPORARY)<br />
ELEVATION VIEW<br />
SPLICE BOX<br />
CUSTOMER / CONTRACTOR INSTALLED<br />
SINGLE PHASE RESIDENTIAL RUD SERVICE<br />
D17<br />
Section 11 - Drawings<br />
CURB<br />
COMMON TRENCH<br />
CURB<br />
ROAD<br />
UTILITY CABLE<br />
IN CONDUIT<br />
ROAD<br />
DWG. BASED ON<br />
LIPA CS 6491