2012 Edition <strong>Red</strong>book<br />
NOTES:<br />
1. * INDICATES ITEMS PROVIDED BY CONTRACTOR.<br />
2. 300 AMP AND LARGER SERVICES MAY REQUIRE TWO CONDUITS INTO METER PAN.<br />
3. 2" MECHANICAL COUPLING SHALL BE EITHER ANACO P/N HUSKY SD-4006 OR<br />
FERNCO P/N 1056-22/SR-11.<br />
6" TO 12"<br />
*CUT CONDUIT @ 45<br />
METER PAN *<br />
(TO LIPA SPEC)<br />
3" WATERTIGHT ADAPTOR *<br />
(CONDUIT TO METER)<br />
3" SCHEDULE 80 PVC *<br />
OR RIGID GALVANIZED<br />
FINAL GRADE<br />
DUCT SEAL<br />
CONDUIT END<br />
24" MIN.<br />
36" MAX.<br />
CABLE-IN-CONDUIT<br />
45 SWEEP*<br />
AIM IN DIRECTION<br />
OF SPLICE BOX<br />
METER PAN *<br />
(TO LIPA SPEC)<br />
2" WATERTIGHT ADAPTOR *<br />
(CONDUIT TO METER)<br />
2" SCHEDULE 80 PVC *<br />
OR RIGID GALV. STEEL<br />
FINAL GRADE<br />
CABLE-IN-CONDUIT<br />
LIPA INSTALLED SINGLE PHASE RESIDENTIAL RUD SERVICE<br />
6"<br />
2" PVC OR RGS COUPLING*<br />
2" MECHANICAL<br />
COUPLING *<br />
3 INCH SERVICE RISER 2 INCH SERVICE RISER<br />
D16<br />
24" MIN.<br />
36" MAX.<br />
DWG. BASED ON<br />
LIPA CS 6491