2012 Edition <strong>Red</strong>book<br />
6" MIN.<br />
10" MAX.<br />
H = HEIGHT BEYOND<br />
REACH OF SERVICE<br />
LADDER<br />
H<br />
21'-0"<br />
MAX. HEIGHT OF LADDER<br />
ACCESSIBLE SERVICE<br />
SERVICE MAST<br />
SPLIT BOLT CONNECTOR, CONNECT<br />
LEAD OF GUY WIRE TO #14 LASHING<br />
WIRE<br />
GUY WIRE<br />
#14 SOLID COPPER WIRE<br />
FOR LASHING SERVICE CABLE<br />
TO GUY WIRE<br />
1/2" EYEBOLT<br />
SERVICE ENTRANCE CABLE<br />
4" MAX.<br />
SERVICE CABLE TAPED<br />
@ END W/ SELF-SEALING<br />
MATERIAL PER NEC<br />
PARALLEL NEUTRAL<br />
CONNECTOR<br />
GUY GRIP FOR<br />
GUY WIRE<br />
CONNECT GUY WIRE & #14<br />
LASHING TO NEUTRAL WIRE,<br />
EXTEND NEUTRAL FOR SERVICE<br />
CONNECTION<br />
H + 2' LIPA CONNECTION<br />
DROP SWING SERVICE FOR<br />
INACCESSIBLE SERVICE ENTRANCE ATTACHMENT<br />
AUTOMATIC DEAD END<br />
BAIL<br />
WORK BY<br />
WORK BY<br />
CONTRACTOR LIPA<br />
120' SPAN MAX.<br />
1/0-3/C AL (TYPICAL)<br />
3'-2" SAG AT 120' AT 90 F<br />
APPROVAL BY LIPA REQUIRED<br />
PRIOR TO INSTALLATION<br />
D6<br />
POOL<br />
22'-6"<br />
TO POLE<br />
SERVICE CONNECTORS<br />
TO POLE<br />
NOTE: ONLY TO BE USED WHERE<br />
NORMAL ACCESSIBLE SERVICE<br />
CONNECTION IS IMPOSSIBLE