Table III<br />

Motor Starting Limitations<br />

Three-Phase Equipment With<br />

Motors Rated In Horsepower<br />

Minimum Demand Motor Size Maximum Starting<br />

Required – KW<br />

(HP)<br />

Current Amp.<br />

No Minimum Demand<br />

Required<br />

2 or less 50<br />

10 3 64<br />

10 5 92<br />

10 7 127<br />

20 10 162<br />

20 15 232<br />

30 20 300<br />

Table IV<br />

Three-Phase Air Conditioning<br />

Minimum Demand<br />

Or Heat Pump Equipment<br />

Capacity<br />

Required – KW BTU/Hr.<br />

No minimum demand<br />

required<br />

20,000 or less 50<br />

38<br />

Section 9 – Motors and Controllers<br />

Maximum Starting<br />

Current Amp.<br />

10 30,000 75<br />

10 40,000 100<br />

10 50,000 125<br />

10 60,000 135<br />

10 75,000 150<br />

20 100,000 175<br />

20 150,000 225<br />

30 200,000 275<br />

30 225,000 300