Table III<br />
Motor Starting Limitations<br />
Three-Phase Equipment With<br />
Motors Rated In Horsepower<br />
Minimum Demand Motor Size Maximum Starting<br />
Required – KW<br />
(HP)<br />
Current Amp.<br />
No Minimum Demand<br />
Required<br />
2 or less 50<br />
10 3 64<br />
10 5 92<br />
10 7 127<br />
20 10 162<br />
20 15 232<br />
30 20 300<br />
Table IV<br />
Three-Phase Air Conditioning<br />
Minimum Demand<br />
Or Heat Pump Equipment<br />
Capacity<br />
Required – KW BTU/Hr.<br />
No minimum demand<br />
required<br />
20,000 or less 50<br />
38<br />
Section 9 – Motors and Controllers<br />
Maximum Starting<br />
Current Amp.<br />
10 30,000 75<br />
10 40,000 100<br />
10 50,000 125<br />
10 60,000 135<br />
10 75,000 150<br />
20 100,000 175<br />
20 150,000 225<br />
30 200,000 275<br />
30 225,000 300