®PRE-ENGINEEREDVENTILATIONAIR-HANDLERCATALOGForm RZ-C-P REEV A(Version A)

®PRE-ENGINEEREDVENTILATIONAIR-HANDLERCATALOGForm RZ-C-P REEV A(Version A)


BACKGROUNDReznor was founded in 1888 to manufacture the “Reznor”reflector heater, which used a luminous flame gas burner developedby George Reznor. This technological breakthroughwas an immediate success and hastened the expansion of gasheating in residential and <strong>com</strong>mercial applications. Technologicaldevelopment and innovation have been the hallmark ofReznor products through the years. The development of theforced <strong>air</strong> gas unit heater, the modular Thermocore ® heat exchanger,and the high-efficiency, sealed-draft Venturion ® unitheater have kept Reznor products at the forefront of technologicaladvances in <strong>com</strong>mercial and industrial gas heating. Asa result of this pioneering role in the heating, makeup <strong>air</strong>, andventilating equipment field, the products offered today are themost advanced in engineering design to satisfy a wide varietyof applications.FACILITIESReznor heaters were first manufactured and sold in Mercer,Pennsylvania (70 miles north of Pittsburgh) in 1888. Overthe years, the <strong>com</strong>pany has grown and expanded. Today, withsales worldwide, Reznor products are being manufactured infacilities throughout North America and Europe.PRODUCT SCOPEWell-equipped engineering laboratories for both productdevelopment and testing can be found at many of the manufacturingsites. All domestic lab sites are agency approved.Reznor Products include a <strong>com</strong>plete line of heating, makeup<strong>air</strong> and ventilating systems, using gas, oil, hot water/steam, orelectric heat sources. Reznor heater <strong>catalog</strong>s are designed toaid the engineer, architect or contractor in specifying the correctequipment for all standard and special applications. Technicaldata is <strong>pre</strong>sented on unit heaters, duct furnaces, infraredheaters, makeup <strong>air</strong> systems, <strong>pre</strong>-<strong>engineered</strong> custom-designedsystems, energy recovery units, packaged cooling, and evaporativecooling modules. Consult your local Reznor Sales Re<strong>pre</strong>sentativefor further assistance in specifying Reznor Equipmentfor your specific application.SERVICESProduct service requirements are handled through contractorsand/or distributors, with backup from local re<strong>pre</strong>sentativesand factory-based service team. Replacement parts inventoriesfor both warranty and non-warranty requirements are maintainedat service centers throughout the country and at the manufacturingfacilities.For the Reznor Re<strong>pre</strong>sentative in your area call 800-695-1901 or go to our web site www.RezSpec.<strong>com</strong>.®Page 52 Form C-PREEVA


Indirect-FiredPre-Engineered Ventilation Air-HandlersModel SDHIndoor, Separated-CombustionPackaged System®ANSI Z83.8CSA 2.6Model PDHIndoor, Power-VentedPackaged SystemCUSTOMERCQSAGENCYCONVERGENTQUALITY SYSTEMPRODUCTPROCESSSTART-UPWARRANTYModel RDHRooftop, Power-VentedPackaged SystemIMPORTANT: Specifications are subject tochange without notice. This guide is intended toprovide specifications and technical informationonly.This guide is not intended to be an instructionmanual. When installing heating and ventilatingequipment, you must check and conform to alllocal and national building codes. Improperinstallation of heating and ventilating equipmentcould be dangerous. Consult manufacturer'sinstallation manual for instructions and importantwarnings.Table of ContentsModel SDHDescription .............................................. 2-3Technical Data ........................................... 4Dimensions ................................................ 5Model PDHDescription .............................................. 6-7Technical Data ........................................... 8Dimensions ................................................ 9Model RDHDescription .......................................... 10-11Technical Data ......................................... 12Dimensions .............................................. 13Advantages of Reznor PreevA ® ....................................... 14System Configuration ..................................... 15Combustible and Service Clearances ............. 16Operating Heating Limits ................................ 16Factory-Installed Optional ModulesMixing Box ......................................... 17-19Evaporative Cooling Module ............... 20-21Cooling Coil Module ............................ 22-30Pressure Drop Table ................................ 31Blower Charts ..................................... 32-33Blower Curves .............. www.RezSpec.<strong>com</strong>Heating and Heating/Cooling Controls 34-36Remote Console and Thermostats ..... 37-40AccessoriesModels PDH/SDH Accessories................ 41Model RDH Accessories .......................... 42Roof Curb Dimensions ............................. 43High Altitude Capacity Changes ................ 44-45Full Load Amp (FLA) Tables ........................... 45Sample SpecificationModel SDH .............................................. 46Model PDH .............................................. 47Model RDH .............................................. 48Warranty ......................................................... 49Form C- PREEVA Page 1


®Indoor, Separated-CombustionPackaged Heating SystemModel SDHCUSTOMERCQSAGENCYCONVERGENTQUALITY SYSTEMPRODUCTPROCESSSTART-UPWARRANTYCSA 2.6ANSI Z83.8DESCRIPTIONModel SDH is the new separated-<strong>com</strong>bustion addition tothe Reznor ® line of Pre-Engineered Ventilation Air-Handlers(PREEVA ® ). Since the introduction of separated-<strong>com</strong>bustion technology,Reznor products have been the industry standard. Thisnew separated-<strong>com</strong>bustion packaged heater is <strong>engineered</strong> withthat same quality plus many new standard and optional features.Model SDH is available in 11 sizes from 75 MBH to 400MBH. Each size is designed for a minimum of 81% thermalefficiency and is available for use with either natural gas or propane.Model SDH separated-<strong>com</strong>bustion heaters are approvedfor <strong>com</strong>mercial/industrial installations in the United States andCanada by ETL Testing Agency.Standard features include the Reznor TCORE 2® heat exchangerand single burner <strong>com</strong>bustion system, a multi-try direct sparkignition with 100% lockout, <strong>pre</strong>ssure switch to verify venter flow,resiliently isolated venter motor, a high temperature limit control,and a centrifugal belt-driven blower capable of up to 3”w.c. of total static <strong>pre</strong>ssure. Both the forward curved blower andthe blower motor are factory installed on vibration isolationmounts. All published <strong>air</strong>flow data and sound data are supportedby AMCA tested and rated <strong>air</strong>flow performance curves.The energy usage of the system has been designed to meet thecurrent ASHRAE Standard 90.1 (maximum 1.2 bhp per 1000cfm).Operation is controlled through an integrated circuit board.The circuit board monitors heater operation and has LED diagnosticindicator lights to identify abnormalities in heating controlfunctions.Optional features include factory-assembled, modular sections- a draw-through cooling coil cabinet module with eitherchilled water or DX coil and an inlet <strong>air</strong> mixing box modulewith a variety of configurations and damper options. A <strong>com</strong>pleteheating and cooling advanced digital control package isavailable in addition to <strong>com</strong>mon industry standard analog heatingonly and makeup <strong>air</strong> controls. (See the list on the right formany more features to select.)Model SDH separated-<strong>com</strong>bustion units require installationof either a horizontal or vertical vent/<strong>com</strong>bustion <strong>air</strong> kit thatincludes a specially designed concentric adapter box. The uniquebox design allows for only one building penetration for both theflue outlet and <strong>com</strong>bustion <strong>air</strong> inlet.STANDARD FEATURES• Patented* TCORE 2® Combustion System• ETL certification• Minimum 81% thermal efficiency• Proven separated-<strong>com</strong>bustion technology including shipped-separatevent/<strong>com</strong>bustion <strong>air</strong> kit (vertical or horizontal)• Maximum 70°F temperature rise (optional 120°F)• Circuit breaker protected transformer for 24-volt controls• Integrated circuit board with diagnostic indicator lights• Multi-try direct spark ignition with 100% lockout• High temperature limit control• Vibration/noise isolated venter motor, blower(s) and blower motor(spring or rubber isolators)• L50 bearing rating with a life expectancy of 150,000 hours• Reverse <strong>air</strong>flow limit switch• Airflow <strong>pre</strong>ssure switch to verify circulating blower operation onmakeup <strong>air</strong> options• Easily convertible single gas orifice system• Socketed, high quality switching relays to facilitate service• All service and vent connections from a single side• Vent runs up to 45 feet• Through-the-cabinet or through-the-base electrical• Engineered condensate management• Three hinged service doors with heavy duty hardware• Fully gasketed door panel with safety door switch• Pre-coat white gloss finish• 4-point base suspension; or slab or floor mounting• Fork lift openings built into the heavy gauge baseChoose FACTORY-INSTALLED FEATURES• TCORE 2® Titanium Stabilized Heat Exchanger -aluminized steel,409 stainless steel, or 316 stainless steel (stainless steel heat exchangerrequired for 70° - 120°F temperature rise)• Heat Exchanger Extended Warranty - 5-year or 10-year• Natural Gas or Propane• ControlsSpace Temperature Heating only- Analog single or two-stage gas valve with room thermostat control(thermostat is available as a shipped-separate accessory ormay be field-supplied)Space Temperature Heating/Cooling- Digital two-stage heating/three-stage cooling with room <strong>com</strong>mandmodule- Digital electronic modulation heating (25% low fire - natural gas,40% low fire - propane)/ two-stage cooling with room <strong>com</strong>mandmoduleDischarge Temperature Makeup Air (heating only)- Analog 2-stage with 2-stage ductstat or electronic sensor and 2-stage valve; high fire/40% low fire modulating controlPage 2 Form C-PREEVA* U.S. Patent No. 6,889,686


ChooseFACTORY-INSTALLEDFEATURES (cont’d)• Controls (cont’d)Discharge Temperature Heating/Cooling Makeup Air- Digital two-stage heating/three-stage cooling with room <strong>com</strong>mand module- Digital electronic modulation heating (25% low fire - natural gas, 40% low fire - propane)/ twostagecooling with room <strong>com</strong>mand module• Supply Voltage - 115/1; 208/1; 230/1; 208/3; 230/3; 460/3; 575/3• UV Germicidal Lamps - Ultraviolet Emitter for neutralization of VOCs and <strong>air</strong>borne micro-organismsfor improved IAQ - not filtration. (Requires Cooling Coil Cabinet Option AU. Separate 115/1or 208/1 or 230/1 wiring/breaker and a separate disconnect must be provided.)• Inlet Air Filters - 1” or 2” disposable or permanent; 1”, 2”, or 4” pleated disposable; arranged invertical flat bank for ease of service• Cabinet Configuration and Construction- Left or right side controls- No insulation; single or double wall with standard (R value 3.8) or high-density (R value 4.4)insulation- Blower cabinet screen- Inlet duct connection flange- Discharge duct flange or louvers (horizontal or horizontal and vertical)• Mixing Box Module- five inlet configuration <strong>com</strong>binations including top, bottom, and rear- manual, motorized 2 or 3 position, or motorized modulating return <strong>air</strong> or outside <strong>air</strong> and return <strong>air</strong>dampers- direct-coupled 24VAC damper actuators- damper control selections such as 0-135 ohms resistance potentiometer, building <strong>pre</strong>ssure, or 0-10 v control• Blower Motor (1/4 to 5 HP) - see <strong>pre</strong>ssure drops and blower charts- open dripproof, TEFC, <strong>pre</strong>mium efficiency, or 2-speed open dripproof- adjustable sheave and belt- motor contactor; IEC motor starter; or factory-installed variable frequency drive• Cooling Coil Module- DX coil (single, dual or 1/3-2/3 circuit; galvanized or stainless casing; copper or aluminum fins(coated or uncoated))- chilled water coil (3-45 tons; 1/4, 1/2, 3/4, or full circuiting; galvanized or stainless casing; copperor aluminum fins (coated or uncoated))• Evaporative Cooling Module- white <strong>pre</strong>-painted or 300 series stainless steel cabinet- 300 series stainless steel reservoir- recirculating pump or AquaSaver microprocessor-based, timed water distribution system- 6” or 12” Glacier-Cor ® or optional Glas-dek ® UL 900 Class II non<strong>com</strong>bustible media- 1” or 2” aluminum <strong>pre</strong>-filter- freeze protection kit (factory-installed)- automatic fill and drain kit (field-installed)- water hammer arrestor (field installed)• Unit mounted, lockable, non-fused service on/off switch• Convenience Outlet• Firestat• Discharge Temperature Low Limit• Over/Under Voltage or Phase Loss Protection• High Ambient Limit (burner cutoff)• Gas Pressure Switches (high, low, or both)ChooseFIELD-INSTALLEDOPTIONALACCESSORIES• Variable Frequency Drive (factory-installed is also available)• Downturn Nozzles (25-65° or 50-90°) with directional louvers• Thermostats to match analog controls• Gas Pressure Regulator• Smoke Detector (in ductwork)• Remote Control Console and Unit Monitoring• Main Unit Disconnect SwitchForm C- PREEVA Page 3


Model SDH TECHNICAL DATAModel SDH Size 75 100 125 150 175 200 225 250 300 350 400ACabinet Size A B C DEInput Heating Capacity* Btuh 75,000 100,000 125,000 150,000 175,000 200,000 225,000 250,000 300,000 350,000 400,000kw/h 22.0 29.3 36.6 43.9 51.2 58.6 65.9 73.2 87.8 102.5 117.1Output Heating Capacity Btuh 60,750 81,000 101,250 121,500 141,750 162,000 182,250 202,500 243,000 283,500 324,000(81% Thermal Efficiency) kw/h 17.8 23.7 29.6 35.6 41.5 47.4 53.4 59.3 71.2 83.0 94.9Control Amps (24 volt)1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0Full Load Amps (115 volt, lessmotor)1.2 1.2 1.2 0.9 0.9 1.7 1.7 1.7 3.0 3.0 3.0Blower Sizeinches 10x10 10x10 (2) 9x7 (2) 9x7 12x12 12x12 12x12 (2)12x7 (2)12x7 (2)12x12 (2)12x12Minimum TemperatureRiseAir Volume at MinimumTemperature Rise°F 40 40 40 40 40 40 40 40 40 40 40cfm 1406 1875 2344 2813 3281 3750 4219 4688 5625 6563 7500m3/min 40 53 66 80 93 106 119 133 159 186 212Maximum TemperatureRise°F 100 100 100 100 100 100 100 100 100 100 100Air Volume at Maximum cfm 563 750 938 1125 1313 1500 1688 1875 2250 2625 3000Temperature Rise m 3 /min 16 21 27 32 37 42 48 53 64 74 85VentConnectionDiameter inches 4 4 4 5 5 5 5 6 6 6 6CombustionDiameter inchesAir Connection4 4 4 5 6 6 6 6 6 6 6Maximum Vent Length fe et 25 35 30 30 30 40 40 45 45 45 45meters 7.62 10.67 9.14 9.14 9.14 12.19 12.19 13.72 13.72 13.72 13.72GasNatural inches 1/2 1/2 1/2 1/2 1/2 1/2 3/4 3/4 3/4 3/4 3/4Connection Propane inches 1/2 1/2 1/2 1/2 1/2 1/2 3/4 3/4 3/4 3/4 3/4Ship Weight (basic unit lbs 421 433 545 553 645 659 659 863 877 1008 1019only; add module wts) kg 191 196 247 251 293 299 299 391 398 457 462Net Weight (basic unit lbs 323 331 413 421 478 492 492 615 629 721 732only; add module wts) kg 146 150 187 191 217 223 223 279 285 327 332Filter (Qty) and Size (Factoryinstalledfilters are optional.)(2) 16x25 (2) 16x25 (2) 20x25 (2) 20x25(2) 16x16 (2) 16x16 (2) 16x16 (3) 16x16(2) 16x20 (2) 16x20 (2) 16x20 (3) 16x20(3) 16x16(3) 16x20(1) 16x16 (1) 16x16(2) 20x20 (2) 20x20(3) 16x20 (3) 16x20* Reznor PreevA Model SDH is specially certified for high altitude derate of 2.3% per 1,000 feet (300 M) of elevation [up to maximum of 9,000feet (2,750 M) - U.S.; 4,500 feet (1,375 M) - Canada]. See high altitude capacity tables for <strong>com</strong>plete details.Corner Weights***Size W X Y Z75100125150175200225250300350400lbs.lbs.lbs.lbs.lbs.lbs.lbs.lbs.lbs.lbs.lbs.7070929280808012412415815863638787747474110110155155929611311715616316318018719820298102121125168175175201208210217(kg.)(kg.)(kg.)(kg.)(kg.)(kg.)(kg.)(kg.)(kg.)(kg.)(kg.)(32)(32)(42)(42)(36)(36)(36)(56)(56)(72)(72)(29)(29)(39)(39)(34)(34)(34)(50)(50)(70)(70)(42)(44)(51)(53)(71)(74)(74)(82)(85)(90)(92)(44)(46)(55)(57)(76)(79)(79)(91)(94)(95)(98)*** Corner weights are for base unit and includestandard controls only. Weights donot include motor, double wall construction,or any optional accessories such ascooling coil cabinet, or mixing box.See dimension drawing on next page forlocation of corner.Page 4 Form C-PREEVA


Model SDH DIMENSIONSOptional EvaporativeCooling Module(always first)OptionalMixingBoxOptionalCoolingCoilCabinetTop ViewBSuspensionPointsA5A3 or A4A1 or A2A - Suspension PointsC5C3 or C4C1 or C2COptional EvaporativeCooling Module(always first)OptionalMixingBoxOptionalCoolingCoilCabinetAirflow*CombustionAir Inlet*FlueOutlet*GasConnectionDHJ10-1/2(267)E5E3 or E4E1 or E2Side ViewEGFTo downloaddimensional drawingsby size go towww.RezSpec.<strong>com</strong>,click on the tab thatsays, “Support.” Thenclick on “DimensionDrawings.”RearView1-1/16 (27)Size E1 E2 E3 E4 E5 F G H J K M N P Q R S T75, 100 2303 2220 3009 3092 3798 528 454 92 427 857 627 876 695 450 128 351 72125, 150 2303 2220 3009 3092 3798 528 454 92 427 1111 881 876 695 704 128 351 72175, 200, 225 2702 2619 3408 3491 4197 814 629 102 437 857 627 1111 928 531 51 584 74250, 300 2702 2619 3408 3491 4197 814 629 102 437 1270 1040 1111 928 732 262 584 74350, 400A 2702 2619 3408 3491 4197 814 629 102 437 1473 1243 1111 928 977 219 584 74Form C- PREEVA Page 5N P4-17/32(115)NOTE: Dimensions A, C, and E change with selection of factory-installed modules.Configuration A, C, E A1, C1, E1 A2, C2, E2 A3, C3, E3 A4, C4, E4 A5, C5, E5Evaporative Cooling Module X X X XMixing Box X X X XCooling Coil Module X X X XBasic Unit X X X X X X X XInlet AirOpening(M x P)For dimensions ofoptional inletduct flange,see AccessoriesSection.MKQDischarge Air Opening(Q x S)shown withoptional louversFront ViewFor dimensions of optional dischargeduct flange, see Accessories Section.Dimensions - inches (±1/8)Size A A1 A2 A3 A4 A5 B C C1 C2 C3 C4 C5 D E75, 100 56-5/8 87-11/16 84-7/16 115-15/32 118-3/4 146-1/2 32-5/8 54-3/4 85-13/16 82-9/16 113-5/8 116-7/8 144-11/16 4 59-5/8125, 150 56-5/8 87-11/16 84-7/16 115-15/32 118-3/4 146-1/2 42-5/8 54-3/4 85-13/16 82-9/16 113-5/8 116-7/8 144-11/16 4 59-5/8175, 200, 225 72-5/16 103-3/8 100-1/8 131-3/16 134-7/16 162-1/4 32-5/8 70-7/16 101-1/2 98-7/32 129-19/64 132-9/16 160-11/32 5 75-5/16250, 300 72-5/16 103-3/8 100-1/8 131-3/16 134-7/16 162-1/4 48-7/8 70-7/16 101-1/2 98-7/32 129-19/64 132-9/16 160-11/32 5 75-5/16350, 400A 72-5/16 103-3/8 100-1/8 131-3/16 134-7/16 162-1/4 56-7/8 70-7/16 101-1/2 98-7/32 129-19/64 132-9/16 160-11/32 5 75-5/16Size E1 E2 E3 E4 E5 F G H J K M N P Q R S T75, 100 90-21/32 87-13/32 118-15/32 121-23/32 149-17/32 20-25/32 17-7/8 3-5/8 16-51/64 33-3/4 24-11/16 34-15/32 27-11/32 17-23/32 5-3/64 13-13/16 2-27/32125, 150 90-21/32 87-13/32 118-15/32 121-23/32 149-17/32 20-25/32 17-7/8 3-5/8 16-51/64 43-3/4 34-11/16 34-15/32 27-11/32 27-23/32 5-3/64 13-13/16 2-27/32175, 200, 225 106-3/8 103-7/64 134-11/64 137-7/16 165-1/4 32-1/32 24-3/4 4 17-7/32 33-3/4 24-11/16 43-23/32 36-9/16 20-29/32 2 23 2-59/64250, 300 106-3/8 103-7/64 134-11/64 137-7/16 165-1/4 32-1/32 24-3/4 4 17-7/32 50 40-15/16 43-23/32 36-9/16 28-13/16 10-5/16 23 2-59/64350, 400A 106-3/8 103-7/64 134-11/64 137-7/16 165-1/4 32-1/32 24-3/4 4 17-7/32 58 48-15/16 43-23/32 36-9/16 38-15/32 8-41/64 23 2-59/64Dimensions - mm (±3)Size A A1 A2 A3 A4 A5 B C C1 C2 C3 C4 C5 D E75, 100 1438 2227 2144 2933 3016 3722 829 1391 2180 2097 2886 2969 3675 102 1514125, 150 1438 2227 2144 2933 3016 3722 1083 1391 2180 2097 2886 2969 3675 102 1514175, 200, 225 1837 2626 2543 3332 3415 4121 829 1789 2578 2495 3284 3367 4073 127 1913250, 300 1837 2626 2543 3332 3415 4121 1241 1789 2578 2495 3284 3367 4073 127 1913350, 400A 1837 2626 2543 3332 3415 4121 1445 1789 2578 2495 3284 3367 4073 127 1913RTS


®Indoor, Power-VentedPackaged Heating SystemModel PDHCUSTOMERCQSAGENCYCONVERGENTQUALITY SYSTEMPRODUCTPROCESSSTART-UPWARRANTYCSA 2.6ANSI Z83.8DESCRIPTIONModel PDH is the new indoor, indirect-fired, power-ventedaddition to the Reznor ® line of Pre-Engineered Ventilation Air-Handlers (PREEVA ® ).Model PDH is available in 11 sizes from 75 MBH to 400MBH. Each size is designed for a minimum 81% thermal efficiencyand is available for use with either natural gas or propane.Model PDH indoor, power-vented heaters are approvedfor <strong>com</strong>mercial/industrial installations in the United States andCanada by the ETL Testing Agency.Standard features include the Reznor TCORE 2® heat exchangerand single burner <strong>com</strong>bustion system, a multi-try direct sparkignition with 100% lockout, <strong>pre</strong>ssure switch to verify venter flow,resiliently isolated venter motor, a high temperature limit control,and a centrifugal belt-driven blower capable of up to 3”w.c. of total static <strong>pre</strong>ssure. Both the forward curved blower andthe blower motor are factory installed on vibration isolationmounts. All published <strong>air</strong>flow data and sound data are supportedby AMCA tested and rated <strong>air</strong>flow performance curves.The energy usage of the system has been designed to meet thecurrent ASHRAE Standard 90.1 (maximum 1.2 bhp per 1000cfm).Operation is controlled through an integrated circuit board.The circuit board monitors heater operation and has LED diagnosticindicator lights to identify abnormalities in heating controlfunctions.Optional features include factory-assembled, modular sections— a draw-through cooling coil cabinet module with eitherchilled water or DX coil and an inlet <strong>air</strong> mixing box modulewith a variety of configurations and damper options. A <strong>com</strong>pleteheating and cooling advanced digital control package isavailable in addition to <strong>com</strong>mon industry standard analog heatingonly and makeup <strong>air</strong> controls. (See the list on the right formany more features to select.)Model PDH indoor, power-vented units require installationof an optional vent cap (or field-supplied equivalent).Page 6 Form C-PREEVA* U.S. Patent No. 6,889,686STANDARD FEATURES• Patented* TCORE 2® Combustion System• ETL certification• Minimum 81% thermal efficiency• Maximum 70°F temperature rise (optional 120°F)• Circuit breaker protected transformer for 24-volt controls• Integrated circuit board with diagnostic indicator lights• Multi-try direct ignition with 100% lockout• High temperature limit control• Vibration/noise isolated venter motor, blower(s) and blower motor(spring or rubber isolators)• L50 bearing rating with a life expectancy of 150,000 hours• Reverse <strong>air</strong>flow limit switch• Airflow <strong>pre</strong>ssure switch to verify circulating blower operation onmakeup <strong>air</strong> options• Easily convertible single gas orifice system• Socketed, high quality switching relays to facilitate service• All service and vent connections from a single side• Vent runs up to 50 feet• Through-the-cabinet or through-the-base electrical• Engineered condensate management• Three hinged service doors with heavy duty hardware• Pre-coat white gloss finish• 4-point base suspension; or slab or floor mounting• Fork lift openings built into the heavy gauge baseChoose FACTORY-INSTALLED FEATURES• TCORE 2® Titanium Stabilized Heat Exchanger -aluminized steel,409 stainless steel, or 316 stainless steel (stainless steel heat exchangerrequired for 70° - 120°F temperature rise)• Heat Exchanger Extended Warranty - 5-year or 10-year• Natural Gas or Propane• ControlsSpace Temperature Heating only- Analog single or two-stage gas valve with room thermostat control(thermostat is available as a shipped-separate accessory ormay be field-supplied)Space Temperature Heating/Cooling- Digital two-stage heating/three-stage cooling with room <strong>com</strong>mandmodule- Digital electronic modulation heating (25% low fire - natural gas,40% low fire - propane)/ two-stage cooling with room <strong>com</strong>mandmoduleDischarge Temperature Makeup Air (heating only)- Analog 2-stage with 2-stage ductstat or electronic sensor and 2-stage valve; high fire/40% low fire modulating controlDischarge Temperature Heating/Cooling Makeup Air- Digital two-stage heating/three-stage cooling with room <strong>com</strong>mandmodule- Digital electronic modulation heating (25% low fire - natural gas,40% low fire - propane)/ two-stage cooling with room <strong>com</strong>mandmodule


ChooseFACTORY-INSTALLEDFEATURES (cont’d)• Supply Voltage - 115/1; 208/1; 230/1; 208/3; 230/3; 460/3; 575/3• UV Germicidal Lamps - Ultraviolet Emitter for neutralization of VOCs and <strong>air</strong>borne microorganismsfor improved IAQ - not filtration. (Requires Cooling Coil Cabinet Option AU. Separate115/1 or 208/1 or 230/1 wiring/breaker and a separate disconnect must be provided.)• Inlet Air Filters - 1” or 2” disposable or permanent; 1”, 2”, or 4” pleated disposable; arranged invertical flat bank for ease of service• Cabinet Configuration and Construction- Left or right side controls- No insulation; single or double wall with standard or high R-value insulation- Blower cabinet screen- Inlet duct connection flange- Discharge duct flange or louvers (horizontal or horizontal and vertical)• Mixing Box Module- five inlet configuration <strong>com</strong>binations including top, bottom, and rear- manual, motorized 2 or 3 position, or motorized modulating return <strong>air</strong> or outside <strong>air</strong> and return<strong>air</strong> dampers- direct-coupled 24VAC damper actuators- damper control selections such as 0-135 ohms resistance potentiometer, building <strong>pre</strong>ssure, or 0-10 v control• Blower Motor (1/4 to 5 HP) - see <strong>pre</strong>ssure drops and blower charts- open dripproof, TEFC, <strong>pre</strong>mium efficiency, or 2-speed open dripproof- adjustable sheave and belt- motor contactor; IEC motor starter; or factory-installed variable frequency drive• Cooling Coil Module- DX coil (single, dual or 1/3-2/3 circuit; galvanized or stainless casing; copper or aluminum fins(coated or uncoated))- chilled water coil (3-45 tons; 1/4, 1/2, 3/4, or full circuiting; galvanized or stainless casing;copper or aluminum fins (coated or uncoated))• Evaporative Cooling Module- white <strong>pre</strong>-painted or 300 series stainless steel cabinet- 300 series stainless steel reservoir- recirculating pump or AquaSaver microprocessor-based, timed water distribution system- 6” or 12” Glacier-Cor ® or optional Glas-dek ® UL 900 Class II non<strong>com</strong>bustible media- 1” or 2” aluminum <strong>pre</strong>-filter- freeze protection kit (factory-installed)- automatic fill and drain kit (field-installed)- water hammer arrestor (field installed)• Unit mounted, lockable, non-fused service on/off switch• Convenience Outlet• Firestat• Discharge Temperature Low Limit• Over/Under Voltage or Phase Loss Protection• High Ambient Limit (burner cutoff)• Gas Pressure Switches (high, low, or both)ChooseFIELD-INSTALLEDOPTIONALACCESSORIES• Variable Frequency Drive (factory-installed is also available)• Downturn Nozzles (25-65° or 50-90°) with directional louvers• Thermostats to match analog controls• Gas Pressure Regulator• Smoke Detector (in ductwork)• Remote Control Console and Unit Monitoring• Main Unit Disconnect Switch• Vent CapForm C- PREEVA Page 7


Model PDH TECHNICAL DATAModel PDH Size 75 100 125 150 175 200 225 250 300 350 400ACabinet Size A B C DEInput Heating Btuh 75,000 100,000 125,000 150,000 175,000 200,000 225,000 250,000 300,000 350,000 400,000Capacity*kw/h 22.0 29.3 36.6 43.9 51.2 58.6 65.9 73.2 87.8 102.5 117.1Output Heating Btuh 60,750 81,000 101,250 121,500 141,750 162,000 182,250 202,500 243,000 283,500 324,000Capacity (81% Thermal kw/h 17.8 23.7 29.6 35.6 41.5 47.4 53.4 59.3 71.2 83.0 94.9Control Amps (24 volt)1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0Full Load Amps (115 volt, lessmotor)1.2 1.2 1.2 0.9 0.9 1.7 1.7 1.7 3.0 3.0 3.0Blower Sizeinches 10x10 10x10 (2) 9x7 (2) 9x7 12x12 12x12 12x12 (2)12x7 (2)12x7 (2)12x12 (2)12x12Minimum Temperature°FRise40 40 40 40 40 40 40 40 40 40 40Air Volume at Min. cfm 1406 1875 2344 2813 3281 3750 4219 4688 5625 6563 7500Temperature Rise m 3 /min. 40 53 66 80 93 106 119 133 159 186 212Maximum TemperatureRiseAir Volume at Max.°F 100 100 100 100 100 100 100 100 100 100 100cfm 563 750 938 1125 1313 1500 1688 1875 2250 2625 3000m 3 /min. 16 21 27 32 37 42 48 53 64 74 85Temperature RiseVe ntConnectionDiameter inches 4 4 4 5 5 5 5 6 6 6 6Maximum Vent Length feet 30 40 35 35 35 50 50 50 50 50 50meters 9.14 12.19 10.67 10.67 10.67 15.24 15.24 15.24 15.24 15.24 15.24Gas Natural inches 1/2 1/2 1/2 1/2 1/2 1/2 3/4 3/4 3/4 3/4 3/4Connection Propane inches 1/2 1/2 1/2 1/2 1/2 1/2 3/4 3/4 3/4 3/4 3/4Ship Weight (basic unitonly; add module wts)Net Weight (basic unitonly; add module wts)Filter (Qty) and Size (Factoryinstalledfilters are optional.)lbs 421 433 545 553 645 659 659 863 877 1008 1019kg (191) (196) (247) (251) (293) (299) (299) (391) (398) (457) (462)lbs 323 331 413 421 478 492 492 615 629 721 732kg (146) (150) (187) (191) (217) (223) (223) (279) (285) (327) (332)(1) 16x16 (1) 16x16(2) 16x16 (2) 16x16 (2) 16x16 (3) 16x16 (3) 16x16(2) 16x25 (2) 16x25 (2) 20x25 (2) 20x25(2) 20x20 (2) 20x20(2) 16x20 (2) 16x20 (2) 16x20 (3) 16x20 (3) 16x20(3) 16x20 (3) 16x20* Reznor PreevA Model PDH is specially certified for high altitude derate of 2.3% per 1,000 feet (300 M) of elevation [up to maximum of 9,000feet (2,750 M) - U.S.; 4,500 feet (1,375 M) - Canada]. See high altitude capacity tables for <strong>com</strong>plete details.Corner Weights***Size W X Y Z75100125150175200225250300350400lbs.lbs.lbs.lbs.lbs.lbs.lbs.lbs.lbs.lbs.lbs.7070929280808012412415815863638787747474110110155155929611311715616316318018719820298102121125168175175201208210217(kg.)(kg.)(kg.)(kg.)(kg.)(kg.)(kg.)(kg.)(kg.)(kg.)(kg.)(32)(32)(42)(42)(36)(36)(36)(56)(56)(72)(72)(29)(29)(39)(39)(34)(34)(34)(50)(50)(70)(70)(42)(44)(51)(53)(71)(74)(74)(82)(85)(90)(92)(44)(46)(55)(57)(76)(79)(79)(91)(94)(95)(98)*** Corner weights are for base unit and includestandard controls only. Weights donot include motor, double wall construction,or any optional accessories such ascooling coil cabinet, or mixing box.See dimension drawing on next page forlocation of corner.Page 8 Form C-PREEVA


Model PDH DIMENSIONSOptional EvaporativeCooling Module(always first)OptionalMixingBoxOptionalCoolingCoilCabinetTop ViewBSuspensionPointsA5A3 or A4A1 or A2A - Suspension PointsC5 C3 or C4 C1 or C2CTo downloaddimensional drawingsby size go towww.RezSpec.<strong>com</strong>,click on the tab thatsays, “Support.” Thenclick on “DimensionDrawings.”E5Optional EvaporativeCooling Module(always first)OptionalMixingBoxE3 or E4RearViewN POptionalCoolingCoilCabinetE1 or E21-1/16 (27)AirflowInlet AirOpening(M x P)For dimensions ofoptional inletduct flange,see AccessoriesSection.Side View*FlueOutlet*GasConnectionECombustionAir InletGFQDischarge Air Opening(Q x S)shown withoptional louversJ10-1/2(267)RTSFront ViewFor dimensions of optional dischargeduct flange, see Accessories Section.Size E2 E3 E4 E5 F G J K M N P Q R S T75, 100 2220 3009 3092 3798 528 454 427 857 627 876 695 450 128 351 72125, 150 2220 3009 3092 3798 528 454 427 1111 881 876 695 704 128 351 72175, 200, 225 2619 3408 3491 4197 814 629 437 857 627 1111 928 531 51 584 74250, 300 2619 3408 3491 4197 814 629 437 1270 1040 1111 928 732 262 584 74350, 400A 2619 3408 3491 4197 814 629 437 1473 1243 1111 928 977 219 584 74Form C- PREEVA Page 94-17/32(115)NOTE: Dimensions A, C, and E change with selection of factory-installed modules.Configuration A, C, E A1, C1, E1 A2, C2, E2 A3, C3, E3 A4, C4, E4 A5, C5, E5Evaporative Cooling Module X X X XMixing Box X X X XCooling Coil Module X X X XBasic Unit X X X X X X X XDimensions - inches (±1/8)Size A A1 A2 A3 A4 A5 B C C1 C2 C3 C4 C5 E E175, 100 56-5/8 87-11/16 84-7/16 115-15/32 118-3/4 146-1/2 32-5/8 54-3/4 85-13/16 82-9/16 113-5/8 116-7/8 144-11/16 59-5/8 90-21/32125, 150 56-5/8 87-11/16 84-7/16 115-15/32 118-3/4 146-1/2 42-5/8 54-3/4 85-13/16 82-9/16 113-5/8 116-7/8 144-11/16 59-5/8 90-21/32175, 200, 225 72-5/16 103-3/8 100-1/8 131-3/16 134-7/16 162-1/4 32-5/8 70-7/16 101-1/2 98-7/32 129-19/64 132-9/16 160-11/32 75-5/16 106-3/8250, 300 72-5/16 103-3/8 100-1/8 131-3/16 134-7/16 162-1/4 48-7/8 70-7/16 101-1/2 98-7/32 129-19/64 132-9/16 160-11/32 75-5/16 106-3/8350, 400A 72-5/16 103-3/8 100-1/8 131-3/16 134-7/16 162-1/4 56-7/8 70-7/16 101-1/2 98-7/32 129-19/64 132-9/16 160-11/32 75-5/16 106-3/8Size E2 E3 E4 E5 F G J K M N P Q R S T75, 100 87-13/32 118-15/32 121-23/32 149-17/32 20-25/32 17-7/8 16-51/64 33-3/4 24-11/16 34-15/32 27-11/32 17-23/32 5-3/64 13-13/16 2-27/32125, 150 87-13/32 118-15/32 121-23/32 149-17/32 20-25/32 17-7/8 16-51/64 43-3/4 34-11/16 34-15/32 27-11/32 27-23/32 5-3/64 13-13/16 2-27/32175, 200, 225 103-7/64 134-11/64 137-7/16 165-1/4 32-1/32 24-3/4 17-7/32 33-3/4 24-11/16 43-23/32 36-9/16 20-29/32 2 23 2-59/64250, 300 103-7/64 134-11/64 137-7/16 165-1/4 32-1/32 24-3/4 17-7/32 50 40-15/16 43-23/32 36-9/16 28-13/16 10-5/16 23 2-59/64350, 400A 103-7/64 134-11/64 137-7/16 165-1/4 32-1/32 24-3/4 17-7/32 58 48-15/16 43-23/32 36-9/16 38-15/32 8-41/64 23 2-59/64Dimensions - mm (±3)Size A A1 A2 A3 A4 A5 B C C1 C2 C3 C4 C5 E E175, 100 1438 2227 2144 2933 3016 3722 829 1391 2180 2097 2886 2969 3675 1514 2303125, 150 1438 2227 2144 2933 3016 3722 1083 1391 2180 2097 2886 2969 3675 1514 2303175, 200, 225 1837 2626 2543 3332 3415 4121 829 1789 2578 2495 3284 3367 4073 1913 2702250, 300 1837 2626 2543 3332 3415 4121 1241 1789 2578 2495 3284 3367 4073 1913 2702350, 400A 1837 2626 2543 3332 3415 4121 1445 1789 2578 2495 3284 3367 4073 1913 2702MK


CUSTOMERCQSAGENCYCONVERGENTQUALITY SYSTEMPRODUCTPROCESSSTART-UPWARRANTYModel RDHDESCRIPTIONModel RDH is the new rooftop, indirect-fired, power-ventedaddition to the Reznor ® line of Pre-Engineered Ventilation Air-Handlers (PREEVA ® ).Model RDH is available in 11 sizes from 75 MBH to 400MBH. Each size is designed for a minimum 81% thermal efficiencyand is available for use with either natural gas or propane.Model RDH rooftop, power-vented heaters are approvedfor <strong>com</strong>mercial/industrial installations in the United States andCanada by the ETL Testing Agency.Standard features include the Reznor TCORE 2® heat exchangerand single burner <strong>com</strong>bustion system, a multi-try direct sparkignition with 100% lockout, <strong>pre</strong>ssure switch to verify venter flow,resiliently isolated venter motor, a high temperature limit control,and a centrifugal belt-driven blower capable of up to 3”w.c. of total static <strong>pre</strong>ssure. Both the forward curved blower andthe blower motor are factory installed on vibration isolationmounts. All published <strong>air</strong>flow data and sound data are supportedby AMCA tested and rated <strong>air</strong>flow performance curves.The energy usage of the system has been designed to meet thecurrent ASHRAE Standard 90.1 (maximum 1.2 bhp per 1000cfm).Operation is controlled through an integrated circuit board.The circuit board monitors heater operation and has LED diagnosticindicator lights to identify abnormalities in heating controlfunctions.Optional features include factory-assembled, modular sections— a draw-through cooling coil cabinet module with eitherchilled water or DX coil; an inlet <strong>air</strong> mixing box modulewith a variety of configurations and damper options; and anevaporative cooling module. A <strong>com</strong>plete heating and coolingadvanced digital control package is available in addition to <strong>com</strong>monindustry standard analog heating only and makeup <strong>air</strong> controls.(See the list on the right for many more features to select.)Page 10 Form C-PREEVA®CSA 2.6ANSI Z83.8Rooftop, Power-VentedPackaged Heating SystemSTANDARD FEATURES• ETL certification• Minimum 81% thermal efficiency• Maximum 100°F temperature rise (optional 120°F)• Double wall cabinet with insulation• Pre-coat white gloss finish, 60 gloss minimum and RAL 9001, meetsASTM B117 specification for salt spray for 1,000 hours• Circuit breaker protected transformer for 24-volt controls• Integrated circuit board with diagnostic indicator lights• Multi-try direct ignition with 100% lockout• High temperature limit control• Vibration/noise isolated venter motor, blower(s) and blower motor(spring or rubber isolators)• L50 bearing rating with a life expectancy of 150,000 hours• Reverse <strong>air</strong>flow limit switch• Airflow <strong>pre</strong>ssure switch to verify circulating blower operation onmakeup <strong>air</strong> options• Easily convertible single gas orifice system• Socketed, high quality switching relays to facilitate service• All service connections from a single side• Through-the-cabinet or through-the-base electrical• Engineered condensate management• Three hinged service doors with heavy duty hardware• 4-point lift eyes on base of unit• Slab or roof mounting• Heavy gauge baseChoose FACTORY-INSTALLED FEATURES• TCORE 2® Titanium Stabilized Heat Exchanger -aluminized steel,409 stainless steel, or 316 stainless steel (stainless steel heat exchangerrequired for 70° - 120°F temperature rise)• Heat Exchanger Extended Warranty - 5-year or 10-year• Natural Gas or Propane• ControlsSpace Temperature Heating only- Analog single or two-stage gas valve with room thermostat control(thermostat is available as a shipped-separate accessory ormay be field-supplied)Space Temperature Heating/Cooling- Digital two-stage heating/three-stage cooling with room <strong>com</strong>mandmodule- Digital electronic modulation heating (25% low fire - natural gas,40% low fire - propane)/ two-stage cooling with room <strong>com</strong>mandmoduleDischarge Temperature Makeup Air (heating only)- Analog 2-stage with 2-stage ductstat or electronicsensor and 2-stage valve; high fire/40% low firemodulating controlDischarge Temperature Heating/Cooling Makeup Air- Digital two-stage heating/three-stage cooling with room <strong>com</strong>mandmodule- Digital electronic modulation heating (25% low fire - natural gas,40% low fire - propane)/ two-stage cooling with room <strong>com</strong>mandmodule- Building management system ready package• Supply Voltage - 115/1; 208/1; 230/1; 208/3; 230/3; 460/3; 575/3• Unit mounted, lockable, non-fused service on/off switch


ChooseFACTORY-INSTALLEDFEATURES(cont’d)• UV Germicidal Lamps - Ultraviolet Emitter for neutralization of VOCs and <strong>air</strong>borne micro-organismsfor improved IAQ - not filtration. (Requires Cooling Coil Cabinet Option AU. Separate 115/1 or 208/1or 230/1 wiring/breaker and a separate disconnect must be provided.)• Inlet Air Filters - 1” or 2” disposable or permanent; 1”, 2”, or 4” pleated disposable; arranged invertical flat bank for ease of service• Cabinet Configuration and Construction (Double Wall)- Left or right side controls- High R-value insulation- Inlet duct connection flange- Discharge duct flange• Mixing Box Module (Double Wall)- three inlet configuration <strong>com</strong>binations with 100% bottom return <strong>air</strong> opening and/or 100% outside <strong>air</strong>rear opening- inlet <strong>air</strong> configuration with 30% outside <strong>air</strong> opening and 100% return <strong>air</strong> opening- manual, motorized 2 or 3 position, or motorized modulating return <strong>air</strong> or outside <strong>air</strong> and return <strong>air</strong>dampers- direct-coupled 24VAC damper actuators- damper control selections such as 0-135 ohms resistance potentiometer, building <strong>pre</strong>ssure, or 0-10 vcontrol- Bottom return <strong>air</strong> screen• Downturn Plenum Cabinet (Double Wall)- shutoff dampers• Blower Motor (1/4 to 5 HP) - see <strong>pre</strong>ssure drops and blower charts- open dripproof, TEFC, <strong>pre</strong>mium efficiency, or 2-speed open dripproof- adjustable sheave and belt- motor contactor; IEC motor starter; or factory-installed variable frequency drive• Cooling Coil Module (Double Wall)- DX coil (single, dual or 1/3-2/3 circuit; galvanized or stainless casing; copper or aluminum fins(coated or uncoated))- chilled water coil (3-45 tons; 1/4, 1/2, 3/4, or full circuiting; galvanized or stainless casing; copper oraluminum fins (coated or uncoated))- stainless steel removable drain pan• Evaporative Cooling Module- white <strong>pre</strong>-painted or 300 series stainless steel cabinet- 300 series stainless steel reservoir- recirculating pump or AquaSaver microprocessor-based, timed water distribution system- 6” or 12” Glacier-Cor ® or optional Glas-dek ® UL 900 Class II non<strong>com</strong>bustible media- 1” or 2” aluminum <strong>pre</strong>-filter- freeze protection kit (factory-installed)- automatic fill and drain kit (field-installed)- water hammer arrestor (field installed)• Convenience Outlet• Firestat• Discharge Temperature Low Limit• Over/Under Voltage or Phase Loss Protection• High Ambient Limit (burner cutoff)• Gas Pressure Switches (high, low, or both)ChooseFIELD-INSTALLEDOPTIONALACCESSORIES• Variable Frequency Drive (factory-installed is also available)• Thermostats to match analog controls• Gas Pressure Regulator• Smoke Detector (in ductwork)• Remote Control Console and Unit Monitoring• Fusible and Non-Fused Disconnect Switch (NEMA 3R)• Vent Vertical Extension Kit• 16” Insulated Roof Curb• Intake Air Hood with Rain Baffles• Perimeter roof curb transitions to (C)RGB/RPB roof curbs (for Model RDH replacement of Models(C)RGB/RPB)Form C- PREEVA Page 11


Model RDH TECHNICAL DATAModel RDH Size 75 100 125 150 175 200 225 250 300 350 400ACabinet Size ABC D EInput Heating Btuh 75,000 100,000 125,000 150,000 175,000 200,000 225,000 250,000 300,000 350,000 400,000Capacity**kw/h 22.0 29.3 36.6 43.9 51.2 58.6 65.9 73.2 87.8 102.5 117.1Output Heating Btuh 60,750 81,000 101,250 121,500 141,750 162,000 182,250 202,500 243,000 283,500 324,000Capacity (81% kw/h 17.8 23.7 29.6 35.6 41.5 47.4 53.4 59.3 71.2 83.0 94.9Control Amps (24 volt) 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0Full Load Amps (115 volt,less motor)1.2 1.2 1.2 0.9 0.9 1.7 1.7 1.7 3.0 3.0 3.0Blower Sizeinches 10x10 10x10 (2) 9x7 (2) 9x7 12x12 12x12 12x12 (2)12x7 (2)12x7 (2)12x12 (2)12x12MinimumTemperature Rise°F 40 40 40 40 40 40 40 40 40 40 40Air Volume at Min. cfm 1406 1875 2344 2813 3281 3750 4219 4688 5625 6563 7500Temperature Rise m 3 /min. 40 53 66 80 93 106 119 133 159 186 212MaximumTemperature Rise°F 70 - 120 70 - 120 70 - 120 70 - 120 70 - 120 70 - 120 70 - 120 70 - 120 70 - 120 70 - 120 70 - 120Air Volume at 100°F cfm 563 750 938 1125 1313 1500 1688 1875 2250 2625 3000Temperature Rise m 3 /min. 16 21 27 32 37 42 48 53 64 74 85Gas Natural inches 1/2 1/2 1/2 1/2 1/2 1/2 3/4 3/4 3/4 3/4 3/4Connection Propane inches 1/2 1/2 1/2 1/2 1/2 1/2 3/4 3/4 3/4 3/4 3/4Ship Weight (basic unit lbs 453 466 586 595 693 719 719 925 940 1,080 1,092only; add module wts) kg (205) (211) (266) (270) (314) (326) (326) (420) (426) (490) (495)Net Weight (basic unit lbs 355 364 454 463 526 552 552 677 692 793 805only; add module wts)* kg (161) (165) (206) (210) (239) (250) (250) (307) (314) (360) (365)Filter (Qty) and Size (Factoryinstalledfilters are optional.)(1) 16x16 (1) 16x16(2) 16x16 (2) 16x16 (2) 16x16 (3) 16x16 (3) 16x16(2) 16x25 (2) 16x25 (2) 20x25 (2) 20x25(2) 20x20 (2) 20x20(2) 16x20 (2) 16x20 (2) 16x20 (3) 16x20 (3) 16x20(3) 16x20 (3) 16x20* Does not include motor weight** Reznor PreevA Model RDH is specially certified for high altitude derate of 2.3% per 1,000 feet (300 M) of elevation [up to maximum of 9,000feet (2,750 M) - U.S.; 4,500 feet (1,375 M) - Canada]. See high altitude capacity tables for <strong>com</strong>plete details.Downturn Plenum Weight• Add weight below to unit weight in Technical Data Table. DownturnPlenum Option AQ5 or AQ8 available on Model RDH Only.DownturnPlenum OnlyNet WeightModel RDH Size 75-100 125-225 250-300 350-400AOption AQ5 lbs 140 158 190 206Bottom Opening kg 63 72 86 93Option AQ8 lbs 156 176 211 229Bottom Opening & 2Position DamperCorner Weights***kg 71 80 96 104Lbs.(kg.)Size W X Y Z W X Y Z75 77 69 101 108 (35) (31) (46) (49)100 79 71 104 110 (36) (32) (47) (50)125 98 89 129 138 (44) (40) (59) (63)150 100 90 132 140 (45) (41) (60) (64)175 114 103 150 160 (52) (47) (68) (73)200 117 106 154 164 (53) (48) (70) (74)225 120 108 157 167 (54) (49) (71) (76)250 147 132 193 205 (67) (60) (88) (93)300 150 135 197 210 (68) (61) (89) (95)350 172 155 226 241 (78) (70) (103) (109)400A 174 157 229 244 (79) (71) (104) (111)*** Corner weights are for base unit and includestandard controls only. Weights donot include motor, double wall construction,or any optional accessories such ascooling coil cabinet, or mixing box.See dimension drawing on next page forlocation of corner.Page 12 Form C-PREEVA


Model RDH DIMENSIONSDimesnions A, C, and R are for base unit with nofactory-installed modules. Additions of the followingmodules affect the dimensions.- Mixing Box (MXB Option)- Cooling Coil Cabinet (AU Option)- Downturn Plenum (AQ Option)- Evaporative Cooling Module (ECC Option).• A 1is the dimension for base with any 1 module.• A 2is the dimension for base with any 2 modules.• A 3is the dimension for base with any 3 modules.• A 4is the dimension for base with 4 modules.Dimensions C, K, and R change with selection ofthree of the optional factory-installed modules:- Mixing Box (MXB Option)- Cooling Coil Cabinet (AU Option)- Downturn Plenum (AQ Option)(selection of Evaporative Cooling Module has no affecton these dimensions).• C 1is the dimension for base with 1 module.• C 2is the dimension for base with 2 modules.• C 3is the dimension for base with 3 modules.• K 2is the dimension for base unit with:- Mixing Box (MXB Option) AND- Downturn Plenum (AQ Option) only.• K 3is the dimension for base unit with- Mixing Box (MXB Option) AND- Cooling Coil Cabinet (AU Option) AND- Downturn Plenum (AQ Option).• R 1dimension is for base unit WITH Downturn Plenum(AQ Option). Additions of other modules donot affect R 1.• U dimension applies only when Mixing Box (MXBOption) is selected.J9-1/16”230mmEMountedHeight6-1/4”159mmInlet Air Flangewith OptionalMixing Box,w/o Evap. Clg.CabinetHInletAirOpeningRear View ofBasic Cabinet(no optional modules)Optional OptionalEvap.Clg. Mixing BoxA4(InsideCurb)OptionalCoolingBasic (BlowerCabinet & Heat Section)Side ViewBottom ViewC (Inside Curb)Front Viewwith OptionalDownturn PlenumOptionalDownturnSize H J K 2 K 3 L M N P R R 1 S T U75, 100 (686) (610) (2,073) (2,778) (344) (351) (659) (725) (483) (1,187) (446) (554) (348)125, 150 (940) (610) (2,073) (2,778) (344) (478) (659) (725) (483) (1,187) (700) (554) (348)175, 200, 225 (686) (845) (2,473) (3,178) (579) (313) (776) (960) (679) (1,384) (527) (671) (348)250, 300 (1,099) (845) (2,473) (3,178) (579) (621) (776) (960) (679) (1,384) (727) (671) (348)350, 400A (1,302) (845) (2,473) (3,178) (579) (706) (776) (960) (679) (1,384) (973) (671) (348)Form C- PREEVA Page 13A33/4”(19 mm)Duct Flange3/4”(19 mm)Duct FlangeFor more detailed unit dimension drawings and data, please see theProduct Submittal pages for model RDH on the Reznor web site.For detail dimensions of individual modules see sections coveringthose modules later in this <strong>catalog</strong>.For roof curb dimensions, see page 43.For detailed dimensional drawingsgo www.RezSpec.<strong>com</strong>, click onthe tab that says, “Support.” Thenclick on “Dimension Drawings.”GC3FUcLReturnAir withOptionalMixingBoxGFInlet AirOpeningA1Rear Viewwith OptionalMixing Box(no Evap. Clg.)C1XWT3-1/16”77 mmK2 or K3AD(Inside Curb)BCombustionAirVentcLGas ConnctionYZ3-1/16”77 mmR or R1C2 or C3cLSypplyAir withOptionalDownturnGA2 or A3CLCLcL17-15/16”455mm PcL9-1/4”235mm13-11/16”348mmF3/4”(19 mm)Duct FlangeMSFront Viewwithout DownturnPlenumD(Inside Curb)BDimension (±1/8 inches)Size A A 1 A 2 A 3 A 4 B C C 1 C 2 C 3 D E F G75, 100 60 13/16 88 9/16 116 5/16 144 1/16 171 13/16 33 3/4 53 9/16 81 5/16 109 1/16 136 13/16 31 9/16 30 7/16 22 7/8 18 3/8125, 150 60 13/16 88 9/16 116 5/16 144 1/16 171 13/16 43 3/4 53 9/16 81 5/16 109 1/16 136 13/16 41 9/16 30 7/16 26 1/2 18 3/8175, 200, 225 76 1/2 104 1/4 132 159 3/4 187 1/2 33 3/4 69 1/4 97 124 3/4 152 1/2 31 9/16 39 11/16 22 7/8 18 3/8250, 300 76 1/2 104 1/4 132 159 3/4 187 1/2 50 69 1/4 97 124 3/4 152 1/2 47 13/16 39 11/16 34 3/4 18 3/8350, 400A 76 1/2 104 1/4 132 159 3/4 187 1/2 58 69 1/4 97 124 3/4 152 1/2 55 13/16 39 11/16 45 13/16 18 3/8Size H J K 2 K 3 L M N P R R 1 S T U75, 100 27 24 81 5/8 109 3/8 13 9/16 13 13/16 25 15/16 28 9/16 19 46 3/4 17 9/16 21 13/16 13 11/16125, 150 37 24 81 5/8 109 3/8 13 9/16 18 13/16 25 15/16 28 9/16 19 46 3/4 27 9/16 21 13/16 13 11/16175, 200, 225 27 33 1/4 97 3/8 125 1/8 22 13/16 12 5/16 30 9/16 37 13/16 26 3/4 54 1/2 20 3/4 26 7/16 13 11/16250, 300 43 1/4 33 1/4 97 3/8 125 1/8 22 13/16 24 7/16 30 9/16 37 13/16 26 3/4 54 1/2 28 5/8 26 7/16 13 11/16350, 400A 51 1/4 33 1/4 97 3/8 125 1/8 22 13/16 27 13/16 30 9/16 37 13/16 26 3/4 54 1/2 38 5/16 26 7/16 13 11/16Dimensions (±3mm)Size A A 1 A 2 A 3 A 4 B C C 1 C 2 C 3 D E F G75, 100 (1,545) (2,249) (2,954) (3,659) (4,364) (857) (1,360) (2,065) (2,770) (3,475) (802) (773) (581) (467)125, 150 (1,545) (2,249) (2,954) (3,659) (4,364) (1,111) (1,360) (2,065) (2,770) (3,475) (1,056) (773) (673) (467)175, 200, 225 (1,943) (2,648) (3,353) (4,058) (4,763) (857) (1,759) (2,464) (3,169) (3,874) (802) (1,008) (581) (467)250, 300 (1,943) (2,648) (3,353) (4,058) (4,763) (1,270) (1,759) (2,464) (3,169) (3,874) (1,214) (1,008) (883) (467)350, 400A (1,943) (2,648) (3,353) (4,058) (4,763) (1,473) (1,759) (2,464) (3,169) (3,874) (1,418) (1,008) (1,164) (467)LN


DesignLoadAverage Monthly TemperatureEnergySavingsEnergySavingsAPR MAY JUN JUL AUG SEP OCTPREEVA ® is More Efficient Year RoundThe PREEVA Series more accurately matches the load, savesenergy, and provides consistent space <strong>com</strong>fort levels.FullThermal Efficiencies with Gas Input TurndownOperationPREEVA ® @2/3 OperationPREEVA ® @1/3 OperationCooling Advantages:Knowing that 95% of the time units run at off-design conditions,why settle for units that don’t have the ability to providemultiple cooling stages?The red curve in the graph (above left) reflects the averagemonthly temperatures which correlate with the building loadrequirements. With conventional systems of this type, you typicallyrun at full load over the cooling demand, which is re<strong>pre</strong>sentedby the blue Design Load line at the top of the graph.When the PREEVA Series is matched with an “M” SeriesCondensing Unit, you have up to three stages (33%, 67% and100%) to provide the ability to efficiently match the buildingcooling needs. By providing this multiple stage capability, youprovide more accurate space temperatures and save energy, asreflected by the shaded blue area in the graph.There is another advantage to the multiple stage capacityof the PREEVA Series. There is less on/off <strong>com</strong><strong>pre</strong>ssor cycling,which can lengthen equipment life.Thermal Efficiency80%PREEVA ® EfficiencyPREEVA ®EfficiencyConventional Heater Efficiency25% 40% 55% 70% 85% 100%Percentage of Full Gas Input RateHeating Advantages:The PREEVA Series is also superior to conventional heatingequipment.The red line in the graph (above right) shows the PREEVASeries heating efficiencies through a series of firing rates. Highefficiency (81%) is provided when the unit is at full rate. Thanksto some innovative advancements by the Reznor EngineeringTeam, the efficiencies remain high even when less than full rateis required.By operating at various firing rates, the right amount ofheating can be applied, matching the need, saving energy andproviding more even space temperatures for consistent <strong>com</strong>fortlevels.The blue line shows the heating efficiencies for a conventionalheating system if it could operate at a range of firingrates. The shaded area in between re<strong>pre</strong>sents the improved efficienciesrealized with the PREEVA Series. Improved efficienciesare reflected in lower operating costs.PREEVA Heating Advantage:Comparison of Possible Fuel (Natural Gas) Savings for Selected CitiesVersus Conventional Heating SystemsPage 14 Form C-PREEVAOperated 24 hours - 7 days per WeekDischarge AirTemperature Rise toMaintain 75°F DischargeTemperatureTotal Annual Hours of GasInput Turndown RatesPercent of Annual GasInput Turndown RatesPercentage of Annual FuelSavings versusConventional HeaterAnnual Dollars Saved for aPDH 300 based on NaturalGas Cost of $1.25 /ThermOperated 6 AM to 5 PM - 7 Days per WeekDischarge AirTemperature Rise toMaintain 75°F DischargeTemperatureTotal Annual Hours of GasInput Turndown RatesPercent of Annual GasInput Turndown RatesPercentage of Annual FuelSavings versusConventional HeaterAnnual Dollars Saved for aPDH 300 based on NaturalGas Cost of $1.25 /ThermCityCityBoston 70°F 4,315 52% 12% $1,338 Boston 60°F 2,093 54% 10% $580Fargo 105°F 3,801 47% 11% $1,113 Fargo 105°F 1,938 46% 11% $572Memphis 60°F 2,971 44% 11% $890 Memphis 60°F 1,316 46% 12% $413Minneapolis 100°F 3,661 45% 11% $1,087 Minneapolis 95°F 1,706 47% 11% $534Pittsburgh 80°F 3,818 45% 11% $769 Pittsburgh 75°F 1,999 54% 12% $560San Diego 40°F 3,462 41% 10% $944 San Diego 35°F 1,962 45% 11% $533


SYSTEM CONFIGURATIONSMXB1 Mixing Boxwith or withoutDamper(s)AUxx CoilCabinet withDX or ChilledWater CoilModel SDHor PDHAirflow - - - ->BlowerMXB AU BASICBasicCooling Coil BasicMixing Box BasicMixing Box Cooling Coil BasicHeatSectionOptionalDischargeAccessories(Factory orFieldInstalled)• Design the system to your specifications• Available in six configurations• Optional Main Filter Rack is in Base Cabinetor Cooling Coil Module• Coil Cabinets and/or Mixing Boxes are FactoryInstalled on the Unit and Shipped asOne AssemblyECCxEvaporativeCooling ModuleorASxx 100%Outside Air Hoodor 30% Air Hoodwith Option GD6MXB1 MixingBox with orwithoutDamper(s)AUxx CoilCabinet withDX or ChilledWater CoilModel RDHAirflow - - - ->BlowerHeatSectionOptionalDownturnPlenumECCx or ASxx MXB1 AU BASIC AQBasicCooling Coil BasicMixing Box BasicEvap. Cooler BasicMixing Box Cooling Coil BasicEvap. Cooler Cooling Coil BasicEvap. Cooler Mixing Box BasicEvap. Cooler Mixing Box Cooling Coil BasicBasic DownturnCooling Coil Basic DownturnMixing Box Basic DownturnEvap. Cooler Basic DownturnMixing Box Cooling Coil Basic DownturnEvap. Cooler Cooling Coil Basic DownturnEvap. Cooler Mixing Box Basic DownturnEvap. Cooler Mixing Box Cooling Coil Basic Downturn• Design the system toyour specifications• Available in sixteen configurations• Optional Main FilterRack is in Base Cabinetor Cooling Coil Module• Coil Cabinets, MixingBoxes, EvaporativeCoolers and/or DownturnPlenums are FactoryInstalled on the Unitand Shipped as One AssemblyNote: Outside <strong>air</strong> hoodsare shipped separately,broken down, for fieldinstallationForm C- PREEVA Page 15


COMBUSTIBLE AND SERVICE CLEARANCESCOMBUSTIBLE MATERIAL CLEARANCESVentControl SideOppositeControl Side Front Rear Top BottomConnector atUnit* Vent Pipe*Model Size in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mmAll Sizes 20 508 6 152 48 1,219 18 457 6 152 0 0 18 457 6 152RECOMMENDED SERVICE CLEARANCESControl SideOpposite Control SideControl Sidewith MixingBoxwith CoolingCoilOppositeControl Sidewith MixingBoxwith CoolingCoil TopModel Size in. mm in. mm in. mm in. mm in. mm in. mm in. mm75/100 20 508 30 762 42 1067 6 152 25 635 25 635 18 457125/150 20 508 34 864 52 1321 6 152 25 635 25 635 18 457175/200/225 20 508 30 762 42 1067 6 152 25 635 25 635 24 610250/300 20 508 42 1067 58 1473 6 152 25 635 25 635 24 610350/400A 20 508 52 1321 66 1676 6 152 25 635 25 635 24 610* Models PDH and SDH only.OperatingParametersOptionRequirementsOPERATING LIMITS FOR MAKEUP AIR AND SPACE HEATINGAllowable Discharge Air TemperatureRange:40° to 120°F 40° to 175°F 100° - 160°FMaximum Temperature Rise: 120°F 100°F 70°FPermissible Inlet or Return AirTemperature Range:minus 40° to 80°F minus 40° to 90°F 50° to 90°FTo operate within the operating limits thelisted control option is required to maintain DG6 1,2 No control option No control optionrestriction applies.ETL certification.restriction applies. 1,2To operate within the operating limits thelisted heat exchanger option is required tomaintain ETL certification.Stainless Steel HeatExchanger OnlyStainless Steel HeatExchanger OnlyAluminized orStainless Steel HeatExchanger1All makeup <strong>air</strong> control options have a maximum permissible discharge <strong>air</strong> temperature setting of 120°F.2An <strong>air</strong> flow rate through the heater must be specified that maintains the operating temperature limits shown.Page 16 Form C-PREEVA


MIXING BOX MODULE AND INLET AIR OPTIONSMixing Box Inlet Air Configurations - Option GDSide Views - Arrows re<strong>pre</strong>sent inlet <strong>air</strong>flow.GD1 GD2 GD3GD4GD5Flanged Openings(With or WithoutDampers)Flanged R/AOpening and30% O/A OpeningGD6RDHOnlyPDHSDHOnlyPDHSDHOnlyAppliestoModel(s) Option Dampers/Motor* Option GD3 and GD5 apply to Models PDH and SDH only.Damper Arrangements - Option GEDamperDial inUnitRemoteDamperDialHeat ModeMixed AirControlBuildingPressureControlEnthalpy Control(CoolingOperation)WarmupControlUse With DamperConfigurationRDH GE1 Manual 30% O/A GD6RDH GE2 2 Position 30% O/A GD6All GE3 2 Position 100% O/A GD1, GD2, GD3*All GE4 3 Position 100% O/A X GD1, GD2, GD3*All GE5 Manual O/A & R/A GD4, GD5*All GE6 2 Position O/A & R/A GD4, GD5*AllGE72 Position O/A & R/AASHRAE Cycle IXGD4, GD5*All GE8 3 Position O/A & R/A X GD4, GD5*All GE10 Modulating O/A & R/A X GD4, GD5*All GE11 Modulating O/A & R/A X GD4, GD5*All GE12 Modulating O/A & R/A X X GD4, GD5*All GE13Modulating O/A & R/AASHRAE Cycle IIIX X GD4, GD5*All GE14Modulating O/A & R/AASHRAE Cycle IIX X X GD4, GD5*All GE15 Null Position O/A & R/A X GD4, GD5*All GE16 DDC Modulating O/A & R/A GD4, GD5*All GE212 Position O/A & R/Awith Enthalpy ControllerX GD4, GD5*All GE22Modulating O/A & R/Awith Dual ReferenceEnthalpy ControllerX GD4, GD5*Form C- PREEVA Page 17


MIXING BOX MODULE AND INLET AIR OPTIONS (cont’d)DescriptionMixing Box Duct Flange Dimensions• Duct flange connections are the same sizefor all mixing box configurations - D x 18-3/8” (467mm) opening with 3/4” (19mm)flanges.• Top and bottom openings are symmetrical.* Centerline of opening is at 1/2 of 18-3/8” = 9-3/4”3/16” (1/2 of 467mm = 233.5)(19mm)** Centerline of opening is at 1/2 of D. DimensionE applies to location of opening for allconfigurations.9-13/16”249mmPage 18 Form C-PREEVAThe mixing box module is factory installed upstream of the blower cabinet and allows for a variety of outside<strong>air</strong> and return <strong>air</strong> configurations with and without dampers. Dampers are available with a selection of actuatorsand controllers.On indoor Model PDH and SDH the mixing box is available in single wall construction or double wallconstruction with either standard insulation (R value 3.8) or high density insulation (R value 4.4).On outdoor Model RDH the mixing box is available in double wall only with either standard insulation (Rvalue 3.8) or high density insulation (R value 4.4).Model PDH or Mixing Box Dimension CodesSDH A B C D E** F*Dimensions (inches)75, 100 33 3/4 36 7/8 34 1/2 22 7/8 16 7/8 20 1/4125, 150 43 3/4 36 7/8 34 1/2 26 1/2 21 7/8 20 1/4175, 200, 225 33 3/4 46 1/8 43 3/4 22 7/8 16 7/8 24 7/8250, 300 50 46 1/8 43 3/4 34 3/4 25 24 7/8350, 400A 58 46 1/8 43 3/4 45 3/4 29 24 7/8Dimensions (mm)75, 100 857 938 877 581 430 515125, 150 1,111 938 877 673 557 515175, 200, 225 857 1,173 1,112 581 430 633250, 300 1,270 1,173 1,112 883 636 633350, 400A 1,473 1,173 1,112 1,164 738 633SIZE lbs kg75-100 18 8125-150 20 9175-225 20 9250-300 26 12350-400A 31 149-1/8”232mm5-3/4”147mm12-3/8”314mmMIXINGBOX*ofopeningSizes 75-150AMIXINGBOXFSizes 175-400A**RearInlet AirOpeningDAof openingETopInlet AirOpeningPDH/SDHOnly2-3/8”(60mm)3/4”(19mm)18-3/8”(467mm)3/4”(19mm)Model RDH Only - 30% O/A Opening w/Small Intake Hood inBack, 100% R/A Opening in Bottom - Option GD6Must be ordered with mixing box Option MXB13/4” (19mm)BC*15-1/2”(395mm)of openingTopInlet AirOpeningPDH/SDHOnlyHingedAccessPanels(Both Sides)AirflowBottomInlet AirOpening15-1/2”(395mm) * C L of openingMixing Box Weight• Add weight below to unit weight in Technical Data TablesModelThis end isattached atthe factoryto either theBlowerCabinet or theCooling CoilModule.E** CL of openingNet Weight - lbs.Model75,Model Size 100125,150175,200,225250,300350,400APDH/SDH OnlyOne Opening (Single Wall) 115 127 130 154 169Two Openings (Single Wall) 119 132 134 159 174One Damper (Double Wall) 146 166 166 201 219RDH/PDH/SDHTwo Dampers (Double Wall) 146 166 166 199 216PDH/SDH OnlyRDH/PDH/SDHNet Weight - kgOne Opening (Single Wall) 52 58 59 70 77Two Openings (Single Wall) 54 60 61 72 79One Damper (Double Wall) 66 75 75 91 99Two Dampers (Double Wall) 66 75 75 90 98


Inlet Air Options (Option GE) by Mixing Box Configuration (Option GD)ControlOptionDamper(s) Damper Actuator Damper Actuator ControlOption GE Description/ApplicationControlOptionConfiguration(see page 10)GE1100% Return Air Inlet, 30% Outside Air Inlet with Hood (see Outside Air Hood section) and Manual Outside Air Damper -Supplies constant 30% or less outside <strong>air</strong> to recirculating heating system. Outside <strong>air</strong> hood is shipped separately for fieldGD6 A GE12 Position (30%) Outside Air Dampers GE22 Position (open/closed) Outside Air Damper 2-Position Damper Motor Unit controller GE3Damper position dial (potentiometer) in the Unit GE4Modulating DamperMotor with <strong>pre</strong>set stops3 Position (2 open settings/closed) Outside AirDamperinstallation.100% Return Air Inlet, 30% Outside Air Inlet with Hood (see Outside Air Hood section) and Motorized Outside AirDamper - Supplies 30% outside <strong>air</strong> to a recirculating heating system at specific times, as controlled by a time clock orswitch. On shutdown, the outside <strong>air</strong> damper closes. Outside <strong>air</strong> hood is shipped separately for field installation.100% outside <strong>air</strong> inlet with 2-position (open/closed) motorized damper. Provides tempered makeup <strong>air</strong> intermittently,usually in unison with a building exhauster. Outside <strong>air</strong> damper opens when unit is on; closes when unit is off.(Comparable to Reznor Option AR8)100% outside <strong>air</strong> inlet with 3-position (full/partial/closed) motorized damper and potentiometer. Provides for low andhigh <strong>air</strong> flow damper positions to control the supply of makeup <strong>air</strong>, usually wired in unison with a 2-speed exhauster.Motor and drive selections must be based on high <strong>air</strong>flow. On shutdown, the outside <strong>air</strong> damper closes. (Comparable toGD6 A GE2GE3GD1, GD2,or GD3 BGE4Field SuppliedReznor Option AR9)STD Outside and return <strong>air</strong> openings without dampers. Designed for installation of field-supplied damper system.Manual GE5Manual, LockingQuadrantOutside Air and Return Air DampersGE5Unit controller GE62 Position Outside Air and Return Air Dampers(either100% outside or 100% return <strong>air</strong>)GE7Unit controller plus warmup (or cooldown) setting(return <strong>air</strong> temperature) to delay opening of outside<strong>air</strong> damper2-Position Damper Motor2 Position Outside Air and Return Air Dampers(100% return <strong>air</strong> or 100% outside <strong>air</strong> after 100%return <strong>air</strong> warmup or cooldown)Damper position dial (potentiometer) in the Unit GE8Modulating DamperMotor with <strong>pre</strong>set stops3 Position (2 mixed settings/outside <strong>air</strong> closed)Outside Air and Return Air DampersGE10Remote damper position dial (potentiometer shippedseparately)Outside <strong>air</strong> and return <strong>air</strong> inlets with dampers and a manual quadrant. Provides manually fixed position for constant mix ofreturn <strong>air</strong> and makeup <strong>air</strong>. (Comparable to Reznor Option AR11)Outside <strong>air</strong> and return <strong>air</strong> inlets with dampers and a 2-position damper motor. Provides 100% return <strong>air</strong> or 100% outside<strong>air</strong> as controlled by the unit controller programming. On shutdown, the outside <strong>air</strong> damper closes. (Comparable to ReznorOption AR17)Outside <strong>air</strong> and return <strong>air</strong> inlets with dampers and a 2-position damper motor and warmup (or cooldown) control (ASHRAECycle I). Provides 100% return <strong>air</strong> or 100% outside <strong>air</strong> as controlled by the return <strong>air</strong> temperature. On shutdown, theoutside <strong>air</strong> damper closes. (Comparable to Reznor Option AR14)Outside <strong>air</strong> and return <strong>air</strong> inlets with dampers with a 3-position (2 mixed settings/outside <strong>air</strong> dampers closed) motorizeddamper and potentiometer. Provides for low and high <strong>air</strong> flow damper position to control the supply of makeup <strong>air</strong>,usually wired in unison with a 2-speed exhauster. Motor and drive selections must be based on high <strong>air</strong>flow. Onshutdown, the outside <strong>air</strong> damper closes.Outside <strong>air</strong> and return <strong>air</strong> inlets with dampers with a modulating damper motor and potentiometer. Provides for mixture ofoutside and return <strong>air</strong> as controlled by a manually set remote potentiometer. On shutdown, the outside <strong>air</strong> damper closes.(Comparable to Reznor Option AR18)Outside <strong>air</strong> and return <strong>air</strong> inlets with dampers with a modulating damper motor and discharge <strong>air</strong> mixed <strong>air</strong> controller.GE6GE7GE8GE10GE11Heat or cool mode mixed <strong>air</strong> controller (discharge <strong>air</strong>temperature)Provides for mixture of outside and return <strong>air</strong> as controlled by discharge <strong>air</strong> temperature setting. On shutdown, the outside<strong>air</strong> damper closes. (Comparable to Reznor Option AR12)GE11GE12Unit-Mounted damper position dial (potentiometer)and heat or cool mode mixed <strong>air</strong> controller (discharge<strong>air</strong> temperature)Outside <strong>air</strong> and return <strong>air</strong> inlets with dampers with a modulating damper motor, a discharge <strong>air</strong> mixed <strong>air</strong> controller, and apotentiometer. Provides for mixture of outside and return <strong>air</strong> as controlled by discharge <strong>air</strong> temperature setting with aminimum amount of outside <strong>air</strong> as determined by the poteniometer setting. On shutdown, the outside <strong>air</strong> damper closes.GE12GD4 orGD5 BGE13Warmup (or cooldown) setting (return <strong>air</strong>temperature) to delay opening of outside <strong>air</strong> damperplus heat or cool mode mixed <strong>air</strong> controller (outsideModulating DamperMotorModulating Outside Air and Return Air Dampers(provide a mixture of outside and return <strong>air</strong> asdetermined by control)(Comparable to Reznor Option AR13)Outside <strong>air</strong> and return <strong>air</strong> inlets with dampers and a modulating damper motor and warmup (or cooldown) control(ASHRAE Cycle III). Provides 100% return <strong>air</strong> on warmup (or cooldown) and mixture of outside and return <strong>air</strong> ascontrolled by mixed inlet <strong>air</strong> temperature setting. On shutdown, the outside <strong>air</strong> damper closes. (Comparable to ReznorOption AR16)GE13GE14<strong>air</strong> temperature)Warmup (or cooldown) setting (return <strong>air</strong>temperature) to delay opening of outside <strong>air</strong> damperplus heat or cool mode mixed <strong>air</strong> controller (outside<strong>air</strong> temperature) plus override from unit-mounteddamper position dial (poteniometer)Outside <strong>air</strong> and return <strong>air</strong> inlets with dampers and a modulating damper motor, potentiometer, and warmup (or cooldown)control (ASHRAE Cycle II). Provides 100% return <strong>air</strong> on warmup and mixture of outside and return <strong>air</strong> as controlled bymixed inlet <strong>air</strong> temperature setting with a minimum amount of outside <strong>air</strong> after warmup (or cooldown) as determined bythe poteniometer setting. On shutdown, the outside <strong>air</strong> damper closes. (Comparable to Reznor Option AR15)GE14Null switch (building <strong>pre</strong>ssure) GE15GE16DDC control from field-supplied automated buildingcontrolModulating DamperMotor with DDC ControlUnit Controller & Economizer Logic Module GE21Outside <strong>air</strong> and return <strong>air</strong> inlets with dampers and a modulating damper motor and a <strong>pre</strong>ssure null switch. Provides aGE15 mixture of return and outside <strong>air</strong> as automatically controlled by building <strong>air</strong> <strong>pre</strong>ssure. On shutdown, the outside <strong>air</strong>damper closes. (Comparable to Reznor Option AR23)Outside <strong>air</strong> and return <strong>air</strong> inlets with dampers and a modulating damper motor with an interface to accept 0-10 volt or 4-GE16 20mA signal from a field-supplied DDC system. Provides a mixture of return and outside <strong>air</strong> as controlled by thebuilding's automated environmental control system.GE21 2 - Position Damper Motor with Enthalpy ControllerUnit Controller & Economizer Logic Module GE222- Position DamperMotorModulating DamperMotorModulating Outside Air and Return Air Dampers(provide a mixture of outside and return <strong>air</strong> asdetermined by control)GE22 Modulating Damper with Dual Reference Enthalpy ControllerAOption GD6 for Model RDH OnlyBOption GD3 and GD5 for Models PDH and SDH onlyForm C- PREEVA Page 19


DescriptionEvaporative cooling provides cooling based on two principles:(1) water in direct contact with a moving <strong>air</strong>stream willevaporate if the droplets have long enough exposure; and (2)that evaporation will lower the temperature of the <strong>air</strong>stream.This evaporative cooler uses rigid cellulose media to retain themoisture providing the <strong>air</strong>stream with time for evaporation. Usingevaporative cooling when cooling needs are limited will helpto reduce the cost of traditional cooling, or may also be used as a<strong>pre</strong>cooler in conjunction with a traditional cooling coil to reducethe tonnage required for a specific application.Evaporative cooling module is factory assembled to ModelRDH, and located upstream from the blower cabinet. Any additionaloptional modules (i.e. cooling coil cabinet or mixing boxcabinet) will be positioned between the evaporative cooling moduleand the blower cabinet.The thermally protected water pump features a heavy duty,fan cooled motor with moisture proof windings along with acorrosion resistant one piece motor shaft. The snap-out base allowsfor simple access to the impeller for easy cleaning. Thepump is wired to allow for manual or automatic thermostatswitching to call for cooling. Standard equipment includes anelectrically activated, pump-protector, float switch to ensure thatan adequate amount of water is in the reservoir prior to the pumpbeing energized. An automatic fill float and constant bleed linemaintains the proper reservoir level while allowing the appropriatebleed-off to <strong>pre</strong>vent accumulation of scale deposits includingcalcium and magnesium salts. All water-carrying <strong>com</strong>ponentsare designed from plastics to prohibit corrosion andextend the life of the cooler <strong>com</strong>ponents.The optional AquaSaver water metering system is designedto decrease water usage by automatically regulating water flowby time and temperature and to decrease maintenance requirementsby eliminating the pump and float switches.MODULE for EVAPORATIVE COOLERStandard Features• Easily accessible, self-cleaning, high-efficiency evaporative mediaof 6” rigid cellulose media• Thermally protected water pump• Electrical motor-protection float switch with stainless steel ball, floatand arm• PVC float valve and bleed line• 115 volt supply voltage• Terminal block wiring• Overflow and drain connections in cabinet bottom• 300 Series Grade stainless steel water reservoir• Pre-coat white gloss finish, 60 gloss minimum and RAL 9001, meetsASTM B117 specification for salt spray for 1,000 hoursOptional Features• Stainless steel cabinet• 12” rigid cellulose media, 6” or 12” rigid glass fiber media fire-ratedto UL900, Class II• 208 or 230 volt power supply capability• Automatic fill and drain kit• Microprocessor based AquaSaver water metering system• Water hammer arrestor• 1” or 2 “ metal <strong>pre</strong>-filtersEvaporative Cooler Technical DataRDH Model Size 75 100 125 150 175 200 225 250 300 350 400ACoolingEffectiveness6" Media12" Media68%90%MaximumCFM 1,406 1,875 2,344 2,813 3,281 3,750 3,950 4,688 5,625 6,563 7,000EvaporativeCooling Airflow M 3 /hr (2,389) (3,186) (3,982) (4,779) (5,574) (6,371) (6,711) (7,965) (9,557) (11,150) (11,893)Maximum FaceFPM 500Velocitymm/s (2,540)Pump HP Pump & Float1/50 HPAmps @115/1 Water Supply 0.92Media Face(Total)DimensionsSq Ft29.25 x 31.56.429.25 x 41.58.536 x 31.57.936 x 47.751236 x 55.7514Page 20 Form C-PREEVA


Evaporative Cooler OptionsWater SupplyMediaPre-FilterFill & Drain KitsOption ECD2 - Pump and float systemOption ECD1 - AquaSaver ® timed water distribution6" Rigid Cellulose (Option ASC3)12" Rigid Cellulose (Option ASC4)6" UL Cellulose (Option ASC5)12" UL Cellulose (Option ASC8)1" or 2" Permanent Aluminum Air Filter (Option PF4 or PF5)Provides "automatic" draining and filling of reservoir (pump system)Freeze Protection KitTemperature based automatic draining of reservoirbased on ambient temperatureWater Hammer Arrestor Reduces water noise (Option ECB1)(apply toAquaSaver system)Evaporative Cooler DimensionsEND VIEWHADUCTOPENINGSIDE VIEWAIR FLOW DIRECTIONREMOVABLE PANEL(FILTER AND MEDIA ACCESS)WATER CONNECTION1/2” NPT MALE(CAN BE ORDEREDON EITHER SIDE)6-1/8 in.(156mm)7-15/16 in.(202mm)DDUCT OPENINGBEFEvaporative Cooler DimensionsListed by Model and Size (± 1/8” 3mm)Indoor PDH/SDHSize A B C D E F G H75, 100125, 150175, 200, 225250, 300350, 400Ain 27 1/4 33 3/4 15 3/8 29 13/16 31 1/16 5/16 22 1/16 34 1/2(mm) (693) (857) (391) (757) (789) (7) (560) (876)in 27 1/4 43 3/4 20 3/8 39 13/16 31 1/16 5/16 22 1/16 34 1/2(mm) (693) (1,111) (518) (1,011) (789) (7) (560) (876)in 36 1/2 33 3/4 15 3/8 29 13/16 31 1/16 5/16 22 1/16 43 3/4(mm) (928) (857) (391) (757) (789) (7) (560) (1,111)in 36 1/2 50 23 1/2 46 1/16 31 1/16 5/16 22 1/16 43 3/4(mm) (928) (1,270) (597) (1,170) (789) (7) (560) (1,111)in 36 1/2 58 27 1/2 54 1/16 31 1/16 5/16 22 1/16 43 3/4(mm) (928) (1,473) (699) (1,373) (789) (7) (560) (1,111)Outdoor RDHSize B C E F G H75, 100125, 150175, 200, 225250, 300350, 400Aininininin33 3/443 3/433 3/4505815 3/820 3/815 3/823 1/227 1/227 3/427 3/427 3/427 3/427 3/41 3/81 3/81 3/81 3/81 3/820 7/820 7/820 7/820 7/820 7/836 3/436 3/4464646(mm)(mm)(mm)(mm)(mm)(857)(1,111)(857)(1,270)(1,473)(391)(518)(391)(597)(699)(705)(705)(705)(705)(705)(34)(34)(34)(34)(34)(531)(531)(531)(531)(531)(933)(933)(1,168)(1,168)(1,168)C3 in. (76mm)BOTTOMVIEWOVERFLOWCONNECTION3/4” NPT MALEGDRAINCONNECTION3/4” NPT MALE2-1/2 in.(64mm)Evaporative Cooler Module Weight• Add weight below to unit weight in Technical Data Tables6 INCH MEDIA 12 INCH MEDIATOTALTOTAL"DRY" "WET" "DRY" "WET"WEIGHT WEIGHT WEIGHT WEIGHTSIZES lbs. (kg) lbs. (kg) lbs. (kg) lbs. (kg)75,100 108 (49) 250 (113) 120 (54) 262 (119)125, 150 124 (56) 246 (112) 141 (64) 263 (119)175, 200, 225 124 (56) 206 (93) 136 (62) 218 (99)250, 300 153 (69) 260 (118) 172 (78) 279 (127)350, 400 167 (76) 249 (113) 190 (86) 272 (123)Note: “Wet” weight applies to unit with 3” of waterin reservoir.Form C- PREEVA Page 21


COOLING COIL MODULEDimensions - Draw-Through Cooling Coil Module for Chilled Water CoilApplies to Models PDH and SDH OnlyChilled WaterModel PDH orCooling CabinetDimension CodesChilled Water Cooling CoilDimension CodesSDH A B C D E F G HDimensions (inches)75, 100 22 7/8 11 1/8 30 3/4 31 26-1/4 25 24 1 5/8125, 150 26 1/2 11 1/8 30 3/4 41 26-1/4 25 34 1 7/8175, 200, 225 22 7/8 15 3/4 40 1/2 31 36-1/4 35 24 1 7/8250, 300 34 3/4 15 3/4 40 1/2 47-1/4 36-1/4 35 40-1/4 1 7/8350, 400A 45 3/4 15 3/4 40 1/2 55-1/4 36-1/4 35 48-1/4 1 7/8Dimensions (mm)75, 100 581 283 781 787 667 635 610 40125, 150 673 283 781 1,041 667 635 864 46175, 200, 225 581 400 1,029 787 921 889 610 46250, 300 883 400 1,029 1,200 921 889 1,022 46350, 400A 1,164 400 1,029 1,403 921 889 1,226 46* Optional Duct Flange.If a mixing box is included,it will beshipped attached tothis end of the coolingcoil cabinet.AInlet AirView(with ductflange)*3/4” (19mm)duct flangeChilled Water Coil Cabinet Net WeightModel Net WeightSize lbs kg75, 100 146 66125, 150 166 75175, 200, 225 166 75250, 300 201 91350, 400A 219 991-1/2” MPT3/4” (19mm)duct flange18-3/8”(467mm)1” MPTDrainB* 2-3/8”(61mm)12-21/64”(313mm)14-21/64” (364mm)17-47/64” (450mm)• Coil Cabinet weights shown are forcabinet only and must be added toweight of base unit (found in the TechnicalData Tables for Model PDH andSDH) and any other modules ordered.Cabinet weight does do not includecoil. For coil weights contact yourReznor Re<strong>pre</strong>sentative.Sideview2-1/2”(64mm)C11-1/8”(2,594mm)This end isattachedto theBlowerCabinet atthe factory.2-3/8” (60mm)typical2-19/64” (58mm)3-5/16”(84mm)DTop View1-3/4”(44mm)Fin PackLocation10”(254mm)2-19/64” (58mm)2” (50mm)7/8” (22mm)5-7/8” (148mm)2-1/2”(64mm)Chilled Water CoilMaximum Face AreaMaximum Face Area = FxGDimensions (Sq. Feet)75, 100 4.17125, 150 5.90175, 200, 225 5.84250, 300 9.78350, 400A 11.73Dimensions (Sq. Meters)75, 100 0.39125, 150 0.55175, 200, 225 0.54250, 300 0.91350, 400A 1.09Page 22 Form C-PREEVAEHSide View1-1/2”MPTH1/4”NPTVent1/4”NPTDrainF - Fin PackHeightG - Fin PackLengthFront View


COOLING COIL MODULEDimensions - Draw-Through Cooling Coil Module for Chilled Water CoilApplies to Models RDH OnlyModel RDHChilled WaterCooling CabinetDimension CodesChilled Water Cooling CoilDimension CodesIn A B C D E F G H75, 100 22 7/8 11 1/8 33 1/4 31 26-1/4 25 24 1 5/8125, 150 26 1/2 11 1/8 33 1/4 41 26-1/4 25 34 1 7/8175, 200, 225 22 7/8 15 3/4 42 1/2 31 36-1/4 35 24 1 7/8250, 300 34 3/4 15 3/4 42 1/2 47-1/4 36-1/4 35 40-1/4 1 7/8350, 400A 45 3/4 15 3/4 42 1/2 55-1/4 36-1/4 35 48-1/4 1 7/8mm A B C D E F G H75, 100 581 283 844 787 667 635 610 40125, 150 673 283 844 1,041 667 635 864 46175, 200, 225 581 400 1,079 787 921 889 610 46250, 300 883 400 1,079 1,200 921 889 1,022 46350, 400A 1,164 400 1,079 1,403 921 889 1,226 46Chilled Water Coil Cabinet Net WeightModel Net WeightSize lbs kg75, 100 146 66125, 150 166 75175, 200, 225 166 75250, 300 201 91350, 400A 219 99• Coil Cabinet weights shown are forcabinet only and must be added toweight of base unit (found in the TechnicalData Tables for Model RDH) andany other modules ordered. Cabinetweight does do not include coil. Forcoil weights contact your Reznor Re<strong>pre</strong>sentative.* Optional Duct Flange(Most RDH units willhave a module attachedor outside <strong>air</strong>hood field installed.)AInlet AirView(with ductflange)*3/4” (19mm)duct flange18-3/8”(467mm)SideViewThis end isattachedto the BlowerCabinet at thefactory.CChilled Water CoilMaximum Face AreaMaximum Face Area = FxGDimensions (Sq. Feet)75, 100 4.17125, 150 5.90175, 200, 225 5.84250, 300 9.78350, 400A 11.73Dimensions (Sq. Meters)75, 100 0.39125, 150 0.55175, 200, 225 0.54250, 300 0.91350, 400A 1.093/4” (19mm)duct flangeEHSide ViewBØ2-3/8” (60mm)typical2-16/64” (58mm)2-16/64” (58mm)H2” (50mm)1-1/2”MPT15-5/8”(371mm)16-7/8”(428mm)20”(509mm)1/4”NPTVent1/4”Drain3-5/16”(84mm)7/8” (22mm)5-7/8” (148mm)7-13/16”10-1/8”(199mm)(257mm)CondensateDrainDTop ViewF - Fin PackHeightG - Fin PackLengthFront View1-3/4”(44mm)Fin PackLocation10”(254mm)2-1/2”(64mm)Form C- PREEVA Page 23


COOLING COIL MODULEDimensions - Draw-Through Cooling Coil Module for DX CoilApplies to Models PDH and SDH OnlyModelPDH/SDHDX Cooling Cabinet DimensionCodesDX Cooling Coil DimensionCodesInches B C D E F G H J K L M75, 100 22 7/8 11 1/8 30 1/4 25 3/4 17 3/4 31 26 1/4 8 10 25 24125, 250 26 1/2 11 1/8 30 1/4 25 3/4 17 3/4 41 26 1/4 8 10 25 34175, 200,22522 7/8 11 1/8 30 1/4 25 3/4 17 3/4 31 36 1/4 12 12 35 24250, 300 34 3/4 15 3/4 35 30 3/8 22 3/8 47 1/4 36 1/4 12 10 35 40 1/4350, 400A 54 3/4 15 3/4 35 30 3/8 22 3/8 55 1/4 36 1/4 14 12 35 48 1/4mm B C D E F G H J K L M75, 100 581 282 770 655 452 787 667 203 254 635 610125, 250 673 282 770 655 452 1,041 667 203 254 635 864175, 200,225581 282 770 655 452 787 921 305 305 889 610250, 300 883 400 888 773 569 1,200 921 305 254 889 1,022350, 400A 1,391 400 888 773 569 1,403 921 356 305 889 1,226BInlet AirView(with ductflange)*3/4” (19mm)duct flange18-3/8”(467mm)C* 2-3/8”(61mm)ø 1-3/8”SuctionLines1”MPTDrainSideviewDX Coil Cabinet Net WeightModel Net WeightSize lbs kg75, 100 146 66125, 150 166 75175, 200, 225 166 75250, 300 201 91350, 400A 219 99ø 3/8” HotGas Bypassø 7/8”LiquidLinesFDE• Coil Cabinet weightsshown are for cabinetonly and must be addedto weight of base unit(found in the TechnicalData Tables for ModelPDH and SDH) and anyother modules ordered.Cabinet weight does donot include coil. For coilweights contact yourReznor Re<strong>pre</strong>sentative.This end isattachedto theBlowerCabinet atthe factory.3/4” (19mm)duct flange1-1/8”(29mm)* Optional Duct Flange. If a mixing box isincluded, it will be shipped attached tothis end of the cooling coil cabinet.10-5/8”(270mm)12-1/2”(318mm)12-3/4”(325mm) 24-3/4”(630mm)1-5/8” (41mm)1-5/8” (41mm)3-3/4” (94mm)7/8” (22mm)10-1/8”(257mm)7-7/8”(200mm)2-1/2”(64mm)1-3/4”(44mm)Fin PackLocationDX CoilMaximum Face AreaMaximum Face Area = ExFDimensions (Sq. Feet)75, 100 4.17125, 150 5.90175, 200,2255.84250, 300 9.78350, 400A 11.73Dimensions (Sq. Meters)75, 100 0.39125, 150 0.55175, 200,2250.54250, 300 0.91350, 400A 1.09Page 24 Form C-PREEVASide ViewH2-1/4”(58mm)10-1/2”(267mm) 3-1/2”(89mm)10”(254mm)2-3/4” (71mm) 2-1/2”(64mm)GJK1-3/8” (35mm)1-3/8” (35mm)1-7/8” (48mm)Top ViewL - Fin PackHeightM - Fin PackLengthFrontView


COOLING COIL MODULEDimensions - Draw-Through Cooling Coil Module for DX CoilApplies to Models RDH OnlyModelRDHDX Cooling Coil CabinetDimensions DX Cooling Coil DimensionsInches A B C G H J K L M75, 100 31 9/16 25 9/16 22 1/16 31 26 1/4 8 10 25 24125, 150 31 9/16 25 9/16 22 1/16 41 26 1/4 8 10 25 34175, 200,22540 13/16 34 13/16 23 5/16 31 36 1/4 12 12 35 24250, 300 40 13/16 34 13/16 23 5/16 47 1/4 36 1/4 12 10 35 40 1/4350, 400A 40 13/16 34 13/16 23 5/16 55 1/4 36 1/4 14 12 35 48 1/4mm A B C G H J K L M75, 100 802 649 560 787 667 203 254 635 610125, 150 802 649 560 1,041 667 203 254 635 864175, 200,2251,037 884 592 787 921 305 305 889 610250, 300 1,037 884 592 1,200 921 305 254 889 1,022350, 400A 1,037 884 592 1,403 921 356 305 889 1,226DX Coil Cabinet Net WeightModel Net WeightSize lbs kg75, 100 146 66125, 150 166 75175, 200, 225 166 75250, 300 201 91350, 400A 219 99• Coil Cabinet weights shown are forcabinet only and must be added toweight of base unit (found in the TechnicalData Tables for Model RDH) andany other modules ordered. Cabinetweight does do not include coil. Forcoil weights contact your Reznor Re<strong>pre</strong>sentative.Inlet AirViewSideViewCBAThis endisattachedto theBlowerCabinet atthefactory.1-1/8”(29mm)3-3/4” (94mm)Ø1-5/8” (41mm)Ø1-5/8” (41mm)CondensateDrain7/8” 22mm)13-9/16”(345mm)15-7/16”(392mm)16-13/16”(427mm)27-5/16”(693mm)1-3/4”(44mm)Fin PackLocation12-1/2”(318mm)10-5/16”(261mm)7-13/16”(199mm)H2-1/4”(58mm)10-1/2”(267mm)3-1/2”(89mm)2-3/4” (71mm)JKØ1-3/8” (35mm)Ø1-3/8” (35mm)1-7/8” (48mm)Side ViewTop ViewGL - Fin PackHeightM - Fin PackLengthFront View10”(254mm)2-1/2”(64mm)DX CoilMaximum Face AreaMaximum Face Area = ExFDimensions (Sq. Feet)75, 100 4.17125, 150 5.90175, 200,2255.84250, 300 9.78350, 400A 11.73Dimensions (Sq. Meters)75, 100 0.39125, 150 0.55175, 200,2250.54250, 300 0.91350, 400A 1.09Form C- PREEVA Page 25


COOLING COILMODULE WITH DX ORCHILLED WATER COILDescription• Reznor Coil Selection Softwareis downloadable fromwww.RezSpec.<strong>com</strong>Cooling Coil ModuleOptionsPREEVA units have a wide selection of factory installed custom designed DX and ChilledWater coils tailor made to the application, from 100% outside <strong>air</strong> in severe climates to 100%return <strong>air</strong> in mild climates. Coil application is designed by Reznor Software such as RezQuoteor RezPro ® Toolbox. The performance data is in <strong>com</strong>pliance with ARI Standard 410. Design/Performance Data Sheets are generated by the software or are available from your ReznorRe<strong>pre</strong>sentative by submitting the Request Form found later in this <strong>catalog</strong>.The double wall insulated draw-through coil cabinet is factory assembled to the systemblower cabinet. Both DX and Chilled Water Coil cabinets are available. Both sides of thecooling coil section have easily removable door panels for routine coil inspection and cleaning.The removable stainless steel drain pan has an exterior 1” NPT connection.Primary considerations are:1) Sizing the PREEVA unit to meet both heating and cooling requirements.2) Deciding on condenser capacity and staging.3) Specifying cooling controlsApproximate cooling <strong>air</strong>flow ranges and capacity ranges (sea level at 45° suction and 45°chilled water) are shown in the DX and Chilled Water Performance Range Tables. Somewhathigher or lower capacities will result from changes in elevation, operating temperatures, flowrates, etc.DX Coil Single CircuitCircuiting 50-50 Dual Circuit1/3 - 2/3 Split CircuitCoil Casing Galvanized SteelStainless SteelRefrigerant R22, R134a, R407c,CoilMaterialCoilCopper Tube withAluminum FinsCopper Tube with CopperFinsElectroFin PolymericCoating CoatingOptions R410a Cabinet Double wall w/ insulationFilters 1", 2", or 4" Pleated Double wall with high1" Permanent density insulation1" DisposableElectroFin is a registered trademark of AST ElectroFin, Inc.Unit Sizing Example An outdoor makeup <strong>air</strong> unit is required for 3500 SCFM of continuous <strong>ventilation</strong> (100%outside <strong>air</strong> during occupied hours) for an auto rep<strong>air</strong> shop. Outdoor design is 18 ºF Winter and100/78 DB/WB ºF Summer, elevation near sea level. A 55 ºF discharge temperature is desired(no reheat) whenever the cooling circuit is enabled (above 85 ºF outdoor ambient) and a 65 ºFdischarge temperature is desired whenever the outside <strong>air</strong> temperature is below 65 ºF.Looking at the heating side, 177 MBH output is needed to raise 3000 SCFM from 18 ºF to65 ºF. Looking at the Technical Data Table for Model RDH, an RDH-225 has an output of 182MBH and a cfm range of 1688 to 4219.Running an enthalpy equation shows that reducing 3500 SCFM from 100/78 to 55/55 willrequire 168.5 MBH sensible and 108.7 MBH latent, or 277.2 MBH of total cooling. Lookingat the DX Coil Performance Range Table (on the following page), maximum re<strong>com</strong>mendedcooling <strong>air</strong> flow (500 fpm face) is 2917 SCFM for the RDH-225. Upsizing to an RDH-250allows up to 4892 SCFM, and the maximum coil output at 95/75 is 321 MBH at 500 fpm. Itshould be possible to meet the cooling requirement with the RDH-250, and in fact, the coilselection software shows that a 6 row/12 fin coil for the RDH-250 will produce the requiredcooling output at 100/78.The important thing to note is, in this case, the cooling requirement governs the RDH sizeselection, not the unit blower or heating capacity.Page 26 Form C-PREEVA


Cooling Coil Performance Tables(For General Sizing Purposes)DX Coil Performance Range Table R-22 @ 45º F Sat Suction, Sea Level2 Row, 8 Fin (minimum) 6 Row, 14 Fin (maximum)PreevaUnit Size75, 100 80/67125, 150175, 200,225250, 300350, 400APreevaUnit Size75, 100125, 150175, 200,225250, 300350, 400AEn te ri n gAirWB/DBºF80/6780/6780/6780/67En te ri n gAirWB/DBºF95/7595/7595/7595/7595/75FinHeight (in.) (scfm) (sfpm)WC) (lbs)WC) (lbs)20 833 250 20 / 16 * 62.3 / 59.8 0.09 38 43 / 27 49.6 / 49.6 0.25 7725 2083 500 27 / 25 68.8 / 63.2 0.19 42 86 / 59 53.6 / 53.6 0.74 9320 1181 250 26 / 20 64.7 / 60.4 0.06 43 58 / 38 50.5 / 50.5 0.32 9425 2951 500 44 / 37 68.3 / 62.7 0.20 51 125 / 85 53.3 / 53.3 0.74 12030 1250 250 30 / 24 * 62.3 / 59.8 0.09 53 64 / 41 49.6 / 49.6 0.25 10935 2917 500 38 / 35 68.8 / 63.2 0.19 56 121 / 83 53.6 / 53.6 0.74 12430 2096 250 47 / 35 64.5 / 60.2 0.06 64 103 / 67 50.4 / 50.4 0.32 14935 4892 500 75 / 60 68.6 / 62.5 0.17 76 210 / 142 53.1 / 53.1 0.74 18230 2513 250 57 / 42 64.4 / 60.1 0.06 72 130 / 83 49.4 / 49.4 0.25 18535 5864 500 94 / 74 68.3 / 62.3 0.17 85 249 / 169 53.3 / 53.3 0.74 2112 Row, 8 Fin (minimum)6 Row, 14 Fin (maximum)FinHeighCoolingAirflowCoolingAirflowFaceVelFaceVelTotal/SensMBHTotal/SensMBHLeavingWB/DB ºFLeavingWB/DB ºFAPD(in.APD(in.t (in.) (scfm) (sfpm)WC) (lbs)WC) (lbs)20 833 250 27 / 20 73.1 / 66.5 0.06 36 64 / 39 51.7 / 51.7 0.25 7725 2083 500 46 / 38 78.1 / 69.4 0.20 42 134 / 86 56.7 / 56.7 0.74 9320 1181 250 41 / 28 73.1 / 66.0 0.05 45 93 / 56 50.9 / 50.9 0.25 10025 2951 500 72 / 53 78.2 / 68.9 0.17 53 196 / 125 55.9 / 55.9 0.74 12030 1250 250 41 / 30 73.1 / 66.5 0.06 49 96 / 58 51.7 / 51.7 0.25 10935 2917 500 65 / 53 78.1 / 69.4 0.20 56 187 / 121 56.7 / 56.7 0.74 12430 2096 250 76 / 51 72.5 / 65.5 0.05 68 166 / 100 50.7 / 50.7 0.25 16035 4892 500 124 / 90 77.9 / 68.6 0.17 76 321 / 205 56.2 / 56.2 0.74 18230 2513 250 94 / 62 72.2 / 65.2 0.05 76 198 / 120 50.9 / 50.9 0.25 18535 5864 500 152 / 109 77.8 / 68.5 0.17 85 391 / 249 55.8 / 55.8 0.74 211CoilWtCoilWtTotal/SensMBHTotal/SensMBHLeavingWB/DB ºFLeavingWB/DB ºF* Refrigerant velocity below 1,000 fpm with 3/8" tube for 2 row/8-10 fpi coils. 2 row, 12 fpi coil performance shown.Note: All coils are optimized for specific conditions, up to 120 ºF DB entering <strong>air</strong>. Higher capacities may be obtainedwhen entering enthalpy is above 95/75.APD(in.APD(in.CoilWtCoilWtChilled Water Coil Performance Range Table, 45º Water, Sea Level (no glycol)4 Row, 6 Fin (minimum)PreevaUnit Size75, 100125, 150175, 200,225250, 300350, 400APreevaUnit Size125, 150175, 200,225250, 300350, 400AEn te ri n gAirWB/DBºF80/6780/6780/6780/6780/67En te ri n gAir ºFWB/DB75, 100 95/7595/7595/7595/7595/75FinHeight (in.)2525353535FinHeight (in.)2525353535CoolingAirflowFaceVelTotal/SensMBH(scfm) (sfpm)WC) (lbs)WC) (lbs)1042 250 35 / 24 59.3 / 56.4 0.09 53.3 62 82 48 / 32 51.7 / 51.6 0.25 56.6 93 1212083 500 54 / 38 63.1 / 59.1 0.28 51.4 62 82 88 / 60 53.5 / 53.3 0.74 55.5 93 1211476 250 51 / 34 59.0 / 56.1 0.09 53.6 78 103 65 / 44 52.6 / 52.5 0.25 56.0 120 1572951 500 79 / 56 62.7 / 58.7 0.28 51.7 78 103 130 / 88 52.7 / 52.6 0.74 56.0 120 1571458 250 49 / 33 59.3 / 56.4 0.09 53.3 82 110 67 / 45 51.7 / 51.6 0.25 56.6 124 1642917 500 75 / 54 63.1 / 59.1 0.28 51.4 82 110 123 / 85 53.5 / 53.3 0.74 55.5 124 1642446 250 80 / 55 59.5 / 56.6 0.09 53.2 114 155 110 / 75 52.1 / 52.1 0.25 56.3 182 2414892 500 133 / 93 62.6 / 58.6 0.28 51.8 114 155 218 / 147 52.5 / 52.3 0.74 56.1 182 2422932 250 98 / 66 59.3 / 56.4 0.09 53.3 130 178 136 / 91 51.7 / 51.6 0.25 56.6 211 2805864 500 162 / 113 62.4 / 58.4 0.28 51.9 130 178 256 / 174 52.8 / 52.7 0.74 55.9 211 280CoolingAirflowFaceVelTotal/SensMBHLeavingWB/DB ºF4 Row, 6 Fin (minimum)APD(in.LeavingWB/DB ºFAPD(in.LWTºFLWTºFDryWtDryWtFluidWt (lbs)FluidWt (lbs)Total/SensMBHTotal/SensMBH6 Row, 14 Fin (maximum)LeavingWB/DB ºFLeavingWB/DB ºF(scfm) (sfpm)WC) (lbs)WC) (lbs)1042 250 57 / 36 63.7 / 59.7 0.09 52.7 62 82 74 / 47 54.0 / 53.8 0.25 55.1 93 1212083 500 89 / 58 69.5 / 63.6 0.28 51.0 62 82 148 / 93 54.4 / 54.1 0.74 55.0 93 1211476 250 79 / 50 64.2 / 60.1 0.09 52.5 78 103 118 / 72 50.7 / 50.5 0.25 56.3 120 1572951 500 124 / 82 69.6 / 63.7 0.28 50.9 78 103 208 / 131 54.5 / 54.3 0.74 54.9 120 1571458 250 80 / 50 63.7 / 59.7 0.09 52.7 82 110 104 / 65 54.0 / 53.8 0.25 55.1 124 1632917 500 124 / 81 69.5 / 63.6 0.28 51.0 82 110 207 / 130 54.4 / 54.1 0.74 55.0 124 1642446 250 133 / 83 63.9 / 59.9 0.09 52.6 114 155 178 / 111 53.5 / 53.4 0.25 55.2 182 2454892 500 211 / 137 69.4 / 63.4 0.28 51.1 114 155 339 / 215 54.9 / 54.6 0.74 54.8 182 2412932 250 162 / 100 63.7 / 59.6 0.09 52.8 130 178 219 / 135 52.8 / 52.7 0.25 55.5 211 2845864 500 250 / 164 69.5 / 63.6 0.28 51.0 130 177 396 / 253 55.6 / 55.3 0.74 54.5 211 284APD(in.LWTºF6 Row, 14 Fin (maximum)APD(in.LWTºFDryWtDryWtFluidWt (lbs)FluidWt (lbs)Note: Some variation in capacity is possible by varying circuiting (Quarter, Half, Three-Quarter, and Single serpentine available), Flow Rateand Fluid Pressure Drop. Values shown re<strong>pre</strong>sent a requested fluid temperature rise of 10 ºF with a requested maximum fluid PD of 18 ft. w.c.All circuit types are re<strong>pre</strong>sented.Form C- PREEVA Page 27


Coil Selection SoftwareThe Reznor Coil Selection Software (DX selection, shown above) that is part of RezQuoteand RezPro ® Toolbox packages will optimally design heating and cooling coils for your specificapplication for all Reznor models utilizing custom coils.Exact design and performance are shown on coil data sheets output by Reznor coil selectionsoftware. You may request or download a copy of the software or submit the coil requestform (found at the end of this section on cooling) to your Reznor Re<strong>pre</strong>sentative, who can thenprovide you with a detailed coil run.DX Coil Controls andCircuitsDX coils are available for one, two, or three stage operation. Two or three stage operationis generally re<strong>com</strong>mended for makeup <strong>air</strong>, where the load on the coil may vary considerably.PREEVA digital control options DG5 and DG6 are ideally suited to sense makeup <strong>air</strong> dischargetemperature and provide two or three stages of capacity, as required. Up to 3:1 cooling turndownmakes hot gas bypass unnecessary or keeps hot gas bypass operation to a minimum.Two stage DX cooling operation is ac<strong>com</strong>plished by two equal capacity interlaced coilcircuits for connection to a two stage condensing unit or two equal capacity single stagecondensers. Three stage operation is ac<strong>com</strong>plished by two unequal interlaced circuits, withapproximately 1/3 of the coil tubes on the first circuit and 2/3 of the coil tubes on the second.Two condensing units of unequal capacity are used – one 5 ton and one 10 ton for example.The first circuit is connected to the smaller condenser and the second to the larger. The 3 stagedigital cooling control system in the PREEVA will activate the first condenser on first stage. Onsecond stage, the first condenser is deactivated and the larger second condenser is activated.On third stage, both condensers are activated. The 3 stage digital cooling control (OptionDG1, DG2, DG5, or DG6) in the PREEVA actually makes 3 separate staging relays, so otherlogics are configurable. TXV’s, liquid line solenoids, any desired hot gas bypass valves, andcondensing units are provided by others. Alternate analog heating controls are available forcooling controls by others or heating/cooling by room thermostat only. Call your ReznorRe<strong>pre</strong>sentative for special requirements.Page 28 Form C-PREEVA


Coil Design – DX CoilsCoil Design – Chilled WaterCoilsIndividual coils are custom designed and internally circuited by Reznor coilselection/design software to optimize for the exact conditions specified. Variablesare:External Circuiting: Single (one stage), Dual 50-50 (2 stage), Dual 1/3-2/3 (3 stage)Refrigerants: R22, R134a, R407c, or R410aRows: 2, 3, 4, or 6Fins per Inch: 8, 10, 12, or 14Tube OD:Fin Height:1/2” (standard) or 3/8” (low load)20”, 22.5”, or 25” (75 to 150 sizes)30”, 32.5”, or 35” (175 to 400A sizes)Internal Circuiting: The number of internal coil circuits is thermodynamicallyoptimized, but circuits may be increased to decrease refrigerant <strong>pre</strong>ssure drop ordecreased to increase refrigerant velocity. Refrigerant velocity should be above 1000fpm and refrigerant <strong>pre</strong>ssure drop should be less than 8 psi. When coil loads arelight and refrigerant velocity would be less than 1100 fpm with 1/2” tube, 3/8” tubeis used to improve refrigerant velocity . Note that higher refrigerant velocities areavailable with 20”, 25”, 30” and 35” height coils and lower refrigerant <strong>pre</strong>ssure dropwith optimal thermodynamic efficiency are available with 22.5” and 32.5” heightcoils (due to internal circuiting). In general, <strong>pre</strong>ference is given to coils having thelowest <strong>air</strong> <strong>pre</strong>ssure drop, which favors taller fin heights.Individual coils are custom designed and internally circuited by Reznor coilselection/design software to optimize for the exact conditions specified. Variablesare:Refrigerants: Water, Ethylene Glycol(%), or Propylene Glycol(%)Rows: 4 or 6Fins per Inch: 6, 8, 10, 12, or 14Tube OD: 1/2Fin Height: 25” (75 to 150 sizes) or 35” (175 to 400A sizes)Internal Circuiting:Quarter, Half, Three Quarter, or Single serpentineQuarter circuit coils are used for low flow rates and have high <strong>pre</strong>ssure drops.Full circuit coils are for high flow rates and have low <strong>pre</strong>ssure drops. Half and ThreeQuarter circuit coils are in between. The best circuiting for a given application canbe optimized based on flow rate, <strong>pre</strong>ssure drop and output requirements.Chilled water coil performance is significantly diminished by glycol, higherpercentages causing lower performance. The unit size/coil face may have to be increasedto achieve adequate cooling performance with glycol in some cases. Seeapproximate derates in the table below:Chilled Water Coil Output Derate (from pure water) for GlycolGlycol Type % Glycol by Wt 12% 20% 28% 36% 40%EthylenePropyleneDerateDerate2.7%3.9%4.2%7.0%6.4%13.6%10.1%22.9%11.7%28.2%Freezing Point ºFFreezing Point ºF24.724.917.919.29.22.2-1.50.8-8.1-6.0Form C- PREEVA Page 29


Coil Option Specification Request FormInstructions: Copy and <strong>com</strong>plete this form and submit it to your Reznor Sales Re<strong>pre</strong>sentative. The specific information will beprocessed, and this form will be returned to you indicating which coil option selection meets your requirements (bottom of page).Information MUST be <strong>com</strong>plete before this request form can be processed.Heater Model and Size: ______________________Cabinet Option : AU5L__; AU5R__; AU6L__; AU6R__Date _______________________Sales Office _________________Coil Type: __Chilled Water; __ R22 (DX); Fax __________________________ R134a (DX); __ R407c (DX); __R410a (DX)Entering Conditions : ______/_____ (DB/WB)Contact ____________________Job # ______________________Capacity Requirement : ______/______ (MBH/Tons)Supply Airflow* : __________ (SCFM) or ___________ (ACFM);Elevation ___________ft.*Actual and standard CFM and elevation factors are explained on <strong>pre</strong>vious pagesChilled Water Coils (Option LC)Entering Fluid Temperature (default = 45°F) _______°FFlow Rate _______ gpm or Fluid Temperature Gain (default = 10°F) _______°FRefrigerant (DX) Coils (Option LX) Single Circuit Dual (50-50) Circuit Dual (1/3 - 2/3) CircuitEvaporator (Suction) Temperature (default = 45°F) ________°FLiquid Temperature (default = 100°F)_______°FSpecial Options (Place an X beside selected special options; fill in required information.) Glycol Percentage by Volume (standard = 35%) _______ % Glycol Type [Ethylene_____, Propylene _____] Coil Coating (Note: Coating extends delivery time by a minimum of three weeks.) Coil Casing (Standard = Galvanized_____); Optional [ Stainless Steel _____] Fin Material (Standard = Aluminum_____); Optional [ Copper_____]DO NOT WRITE IN BOX BELOW -- Information will be provided by your Reznor Sales Re<strong>pre</strong>sentative________Refrigerant Feeder Tube/ Chilled Water(DX) Coil Option No.: LX ______ Nozzle No.: F ________________ Coil Option No.: LC ______ActualLeavingCapacity______________; Conditions______°F______°F;ADP ________________ ; FPD ______________; GPM_____________Instructions: If Option Code above is LC25-64 or Option Code LX65-84 with an F Code, enter that in your RezProsoftware for coil pricing (or contact your Reznor Sales Re<strong>pre</strong>sentative). If any special options are ordered, coil optioncode will be LC99 or LX99 indicating special pricing.Option Code LC99 or LX99 Special Pricing: $_______________(List)Extended Lead time ____________________________________Page 30 Form C-PREEVA


PRESSURE DROP TABLEDisp.Filters APerm.Alum.Filters APleatedDisposableFilters AMixingBoxO/AIntakeEvaporativeCoolerMedia1"Pre-Filter(Opt. PF4)2"Pre-Filter(Opt. PF5)UnitMixingDownturn DischSize CFM 1'' 2'' 1'' 2'' 1'' 2'' 4'' Box Dampers Hood 6'' 12'' Plenum Damper569 0.02 0.04 0.01 0.01 0.11 0.04 0.01 0.00 0.01 0.03 0.01 0.01 0.00 0.01 0.01 0.0175 1000 0.04 0.06 0.01 0.02 0.15 0.07 0.03 0.01 0.01 0.03 0.02 0.04 0.01 0.01 0.01 0.02100 1500 0.06 0.09 0.02 0.04 0.21 0.11 0.06 0.02 0.01 0.06 0.04 0.07 0.02 0.01 0.02 0.041898 0.09 0.13 0.03 0.06 0.26 0.15 0.10 0.03 0.02 0.08 0.05 0.11 0.03 0.02 0.03 0.06949 0.03 0.05 0.01 0.01 0.13 0.05 0.02 0.01 0.01 0.03 0.01 0.02 0.01 0.01 0.01 0.011250 0.04 0.06 0.01 0.02 0.15 0.07 0.03 0.01 0.01 0.03 0.02 0.03 0.01 0.01 0.01 0.02125 1500 0.05 0.07 0.01 0.03 0.18 0.08 0.04 0.02 0.01 0.04 0.02 0.04 0.02 0.01 0.01 0.03150 2000 0.07 0.10 0.02 0.05 0.23 0.12 0.07 0.02 0.02 0.06 0.04 0.07 0.02 0.02 0.02 0.052500 0.10 0.14 0.03 0.07 0.28 0.17 0.11 0.03 0.03 0.09 0.05 0.11 0.03 0.03 0.03 0.072847 0.13 0.17 0.04 0.08 0.32 0.20 0.14 0.03 0.04 0.11 0.07 0.13 0.03 0.04 0.04 0.081329 0.03 0.06 0.01 0.02 0.14 0.06 0.03 0.02 0.01 0.05 0.02 0.04 0.02 0.01 0.01 0.021650 0.04 0.07 0.01 0.03 0.17 0.08 0.04 0.02 0.02 0.07 0.03 0.06 0.02 0.02 0.01 0.03175 2000 0.06 0.09 0.02 0.04 0.20 0.10 0.05 0.03 0.02 0.09 0.04 0.08 0.03 0.02 0.02 0.04200 2500 0.08 0.12 0.03 0.05 0.24 0.14 0.08 0.03 0.04 0.15 0.06 0.12 0.03 0.04 0.03 0.05225 3000 0.11 0.15 0.04 0.07 0.29 0.18 0.11 0.04 0.06 0.22 0.08 0.16 0.04 0.06 0.04 0.073500 0.14 0.18 0.05 0.09 0.35 0.22 0.15 0.04 0.08 0.31 0.11 0.21 0.04 0.08 0.05 0.094000 0.18 0.22 0.06 0.12 0.40 0.28 0.20 0.05 0.11 0.42 0.13 0.27 0.05 0.11 0.06 0.124271 0.20 0.25 0.07 0.13 0.44 0.31 0.22 0.05 0.13 0.50 • • 0.05 0.13 0.07 0.131898 0.03 0.05 0.01 0.02 0.14 0.06 0.02 0.02 0.01 0.04 0.02 0.04 0.02 0.01 0.01 0.022050 0.03 0.06 0.01 0.02 0.15 0.06 0.03 0.02 0.01 0.05 0.02 0.04 0.02 0.01 0.01 0.022500 0.04 0.07 0.01 0.03 0.17 0.08 0.04 0.02 0.02 0.07 0.03 0.06 0.02 0.02 0.01 0.03250 3000 0.06 0.09 0.02 0.04 0.20 0.10 0.05 0.03 0.02 0.09 0.04 0.08 0.03 0.02 0.02 0.04300 3500 0.07 0.11 0.02 0.05 0.23 0.12 0.07 0.03 0.03 0.13 0.05 0.11 0.03 0.03 0.02 0.054000 0.09 0.13 0.03 0.06 0.26 0.15 0.09 0.04 0.04 0.17 0.07 0.13 0.04 0.04 0.03 0.064500 0.11 0.15 0.04 0.07 0.29 0.18 0.11 0.04 0.05 0.22 0.08 0.16 0.04 0.05 0.04 0.075000 0.13 0.17 0.04 0.09 0.33 0.21 0.14 0.04 0.07 0.28 0.10 0.19 0.04 0.07 0.04 0.095500 0.15 0.20 0.05 0.10 0.36 0.24 0.17 0.04 0.08 0.35 0.11 0.23 0.04 0.08 0.05 0.105694 0.16 0.21 0.05 0.11 0.38 0.25 0.18 0.05 0.09 0.38 0.12 0.24 0.05 0.09 0.05 0.112657 0.04 0.06 0.01 0.02 0.16 0.07 0.03 0.02 0.01 0.06 0.03 0.05 0.02 0.01 0.01 0.023300 0.05 0.08 0.02 0.03 0.19 0.09 0.05 0.02 0.02 0.09 0.04 0.07 0.02 0.02 0.02 0.033500 0.06 0.09 0.02 0.04 0.20 0.10 0.05 0.02 0.02 0.10 0.04 0.08 0.02 0.02 0.02 0.044000 0.07 0.10 0.02 0.04 0.22 0.12 0.07 0.03 0.02 0.13 0.05 0.10 0.03 0.02 0.02 0.04350 4500 0.08 0.12 0.03 0.05 0.25 0.14 0.09 0.03 0.03 0.17 0.06 0.12 0.03 0.03 0.03 0.05400A 5000 0.10 0.14 0.03 0.07 0.28 0.16 0.10 0.03 0.04 0.21 0.07 0.15 0.03 0.04 0.03 0.075500 0.12 0.16 0.04 0.08 0.31 0.19 0.13 0.04 0.05 0.27 0.09 0.17 0.04 0.05 0.04 0.086000 0.14 0.18 0.04 0.09 0.34 0.22 0.15 0.04 0.05 0.32 0.10 0.20 0.04 0.05 0.04 0.096500 0.16 0.20 0.05 0.10 0.37 0.25 0.17 0.04 0.07 0.39 0.12 0.23 0.04 0.07 0.05 0.107000 0.18 0.22 0.06 0.12 0.40 0.28 0.20 0.04 0.08 0.47 0.13 0.26 0.04 0.08 0.06 0.127400 0.19 0.24 0.06 0.13 0.43 0.30 0.22 0.05 0.09 0.53 • • 0.05 0.09 0.06 0.137593 0.20 0.25 0.07 0.14 0.45 0.32 0.23 0.05 0.09 0.57 • • 0.05 0.09 0.07 0.14Add CoilPD fromCoil DataSheet BExternalPD(DuctSystem)TotalAdjustedPressureDropARun RezQuote or RezPro ® Toolbox Coil Selection Software or call your Reznor Re<strong>pre</strong>sentative.BSee tables in coil section for <strong>pre</strong>ssure drop at specified conditions, run coil selection software or call your Reznor Re<strong>pre</strong>sentative.Form C- PREEVA Page 31


BHP/RPM CHARTSUnitSizeTe m pTotal Static PressureCFM Rise 0.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25 2.50 2.75 3.00563 100 ºF 490/0.06 689/0.11 845/0.18 965/0.25 1090/0.33 1165/0.40 1251/0.50 1351/0.59 1408/0.70 1469/0.76 N/A N/A625 90 ºF 487/0.06 682/0.12 833/0.20 962/0.27 1071/0.35 1172/0.45 1250/0.51 1339/0.64 1442/0.74 1500/0.80 1563/0.95 1630/1.04703 80 ºF 496/0.07 680/0.14 844/0.21 981/0.30 1082/0.39 1172/0.46 1278/0.56 1361/0.68 1454/0.78 1506/0.91 1562/0.98 1622/1.0675 804 70 ºF 508/0.09 689/0.16 832/0.24 965/0.33 1096/0.42 1177/0.52 1269/0.62 1378/0.74 1462/0.84 1508/0.95 1608/1.09 1663/1.17937 60 ºF 521/0.11 694/0.19 839/0.28 969/0.37 1081/0.48 1196/0.58 1278/0.70 1371/0.78 1442/0.92 1519/1.04 1606/1.17 1654/1.321125 50 ºF 553/0.15 711/0.24 854/0.34 978/0.45 1089/0.54 1184/0.66 1274/0.79 1378/0.91 1467/1.05 1534/1.16 1607/1.28 1688/1.431406 40 ºF 603/0.24 753/0.35 879/0.45 992/0.58 1096/0.70 1188/0.84 1278/0.98 1361/1.10 1454/1.24 1534/1.41 1592/1.54 1687/1.69750 100 ºF 500/0.08 682/0.14 833/0.21 978/0.30 1098/0.38 1184/0.47 1286/0.56 1364/0.68 1452/0.76 1500/0.89 1607/1.00 1667/1.12833 90 ºF 510/0.09 694/0.16 833/0.24 980/0.32 1087/0.41 1190/0.52 1282/0.61 1388/0.70 1470/0.81 1515/0.94 1612/1.04 1666/1.16937 80 ºF 525/0.11 694/0.18 839/0.27 969/0.35 1081/0.45 1196/0.56 1278/0.65 1371/0.77 1479/0.87 1519/1.00 1606/1.10 1654/1.27100 1071 70 ºF 545/0.13 714/0.22 846/0.31 974/0.41 1089/0.51 1190/0.62 1285/0.72 1367/0.83 1460/0.97 1530/1.10 1607/1.19 1691/1.361250 60 ºF 573/0.18 728/0.28 862/0.38 987/0.49 1087/0.60 1190/0.71 1271/0.84 1364/0.95 1471/1.10 1531/1.22 1630/1.37 1705/1.481500 50 ºF 621/0.26 769/0.38 891/0.49 1000/0.62 1111/0.74 1200/0.87 1286/1.00 1364/1.12 1452/1.27 1525/1.40 1607/1.54 1667/1.711875 40 ºF 694/0.45 827/0.58 945/0.72 1051/0.85 1148/1.00 1236/1.15 1324/1.30 1389/1.48 1480/1.65 1541/1.79 1607/1.95 1679/2.13938 100 ºF 561/0.09 811/0.19 966/0.28 1113/0.38 1239/0.48 1340/0.58 1459/0.68 1563/0.80 1642/0.91 1728/1.05 1824/1.15 N/A1042 90 ºF 570/0.11 810/0.21 986/0.32 1122/0.41 1236/0.52 1351/0.64 1459/0.74 1552/0.86 1658/0.97 1737/1.10 1824/1.25 1870/1.371172 80 ºF 590/0.13 804/0.23 988/0.36 1124/0.48 1243/0.59 1367/0.71 1465/0.84 1578/0.97 1641/1.09 1746/1.22 1823/1.38 1908/1.50125 1339 70 ºF 617/0.17 794/0.27 987/0.41 1143/0.55 1267/0.67 1378/0.80 1488/0.93 1562/1.06 1674/1.21 1736/1.35 1838/1.50 1913/1.681562 60 ºF 663/0.23 816/0.35 976/0.46 1139/0.63 1271/0.79 1402/0.95 1498/1.10 1585/1.27 1682/1.39 1764/1.58 1853/1.74 1918/1.861875 50 ºF 733/0.35 869/0.47 994/0.61 1122/0.75 1262/0.93 1396/1.15 1509/1.34 1620/1.52 1705/1.69 1798/1.90 1875/2.07 1930/2.262344 40 ºF 850/0.61 965/0.74 1072/0.89 1180/1.07 1282/1.25 1379/1.44 1492/1.63 1609/1.86 1709/2.14 1803/2.36 1908/2.61 1977/2.891125 100 ºF 592/0.12 804/0.22 993/0.34 1151/0.46 1282/0.57 1387/0.67 1511/0.80 1607/0.91 1688/1.04 1776/1.16 1841/1.29 N/A1250 90 ºF 608/0.15 798/0.24 987/0.37 1148/0.50 1293/0.63 1406/0.75 1520/0.89 1607/1.01 1705/1.14 1786/1.25 1875/1.39 1940/1.541406 80 ºF 633/0.18 811/0.28 981/0.41 1150/0.56 1291/0.71 1406/0.85 1525/0.99 1622/1.13 1710/1.27 1808/1.43 1889/1.57 1947/1.73150 1607 70 ºF 666/0.24 841/0.36 984/0.47 1130/0.63 1280/0.81 1404/0.97 1522/1.14 1625/1.30 1722/1.48 1808/1.60 1903/1.79 1981/1.961875 60 ºF 727/0.34 879/0.47 1010/0.60 1133/0.73 1259/0.90 1395/1.10 1520/1.31 1623/1.50 1722/1.69 1815/1.91 1918/2.06 1985/2.282250 50 ºF 823/0.53 938/0.66 1066/0.82 1184/0.99 1282/1.14 1387/1.32 1489/1.50 1607/1.76 1716/1.99 1808/2.26 1910/2.48 N/A2812 40 ºF 981/0.95 1068/1.10 1161/1.25 1265/1.45 1368/1.67 1454/1.87 1543/2.07 1622/2.26 1699/2.47 1782/2.71 1875/2.99 N/A1313 100 ºF 492/0.14 646/0.24 788/0.36 927/0.49 1037/0.62 1125/0.76 1212/0.92 1291/1.07 1382/1.20 1432/1.36 1515/1.55 1576/1.721458 90 ºF 509/0.17 653/0.27 788/0.40 921/0.54 1029/0.69 1136/0.83 1215/0.99 1306/1.16 1389/1.30 1458/1.50 1508/1.65 1591/1.811641 80 ºF 535/0.21 670/0.32 794/0.46 912/0.60 1026/0.76 1132/0.92 1216/1.10 1313/1.28 1387/1.45 1470/1.62 1538/1.80 1588/1.96175 1875 70 ºF 568/0.28 699/0.40 809/0.54 915/0.70 1014/0.87 1114/1.04 1210/1.23 1308/1.40 1389/1.61 1461/1.81 1541/2.01 1607/2.222187 60 ºF 619/0.39 737/0.53 841/0.67 937/0.84 1025/1.03 1112/1.21 1204/1.40 1286/1.61 1381/1.83 1458/2.03 1526/2.27 1600/2.492625 50 ºF 694/0.61 799/0.77 895/0.94 984/1.11 1064/1.30 1141/1.50 1212/1.72 1291/1.94 1370/2.17 1445/2.43 1514/2.68 1591/2.913281 40 ºF 813/1.06 907/1.28 989/1.49 1070/1.68 1145/1.88 1215/2.11 1278/2.35 1339/2.57 1406/2.83 1458/3.13 1526/3.35 1588/3.661500 100 ºF 513/0.18 656/0.28 784/0.41 909/0.55 1026/0.72 1121/0.86 1212/1.03 1304/1.20 1379/1.38 1446/1.54 1519/1.74 1579/1.911667 90 ºF 536/0.22 674/0.33 794/0.46 907/0.61 1018/0.78 1121/0.94 1212/1.13 1295/1.31 1375/1.48 1450/1.65 1533/1.84 1588/2.061875 80 ºF 568/0.28 694/0.40 806/0.53 915/0.68 1014/0.85 1111/1.04 1210/1.23 1293/1.43 1376/1.61 1456/1.81 1531/2.01 1596/2.22200 2143 70 ºF 610/0.37 730/0.51 832/0.65 932/0.80 1020/0.98 1113/1.16 1199/1.37 1289/1.58 1372/1.79 1441/2.05 1517/2.24 1587/2.462500 60 ºF 671/0.54 778/0.70 877/0.86 966/1.02 1047/1.19 1130/1.39 1205/1.59 1282/1.80 1361/2.06 1439/2.31 1504/2.56 1575/2.793000 50 ºF 759/0.85 857/1.04 945/1.23 1026/1.42 1106/1.61 1176/1.82 1244/2.03 1311/2.24 1379/2.48 1446/2.75 1509/3.01 1569/3.303750 40 ºF 904/1.52 987/1.77 1064/2.01 1136/2.22 1205/2.48 1266/2.73 1333/2.97 1389/3.20 1449/3.45 1508/3.73 1563/3.97 1613/4.231688 100 ºF 541/0.22 675/0.34 791/0.46 904/0.61 1020/0.77 1125/0.96 1225/1.15 1310/1.32 1394/1.54 1461/1.71 1535/1.91 N/A1875 90 ºF 568/0.28 697/0.40 807/0.54 907/0.68 1010/0.85 1110/1.04 1214/1.23 1298/1.43 1383/1.65 1467/1.86 1534/2.06 1607/2.282109 80 ºF 606/0.36 727/0.50 833/0.64 926/0.79 1015/0.97 1110/1.15 1201/1.36 1291/1.57 1375/1.78 1460/1.99 1531/2.24 1609/2.46225 2411 70 ºF 656/0.49 769/0.65 868/0.80 956/0.97 1038/1.14 1119/1.33 1199/1.53 1276/1.74 1356/2.00 1437/2.21 1517/2.45 1584/2.732812 60 ºF 727/0.72 830/0.90 924/1.07 1008/1.25 1086/1.45 1156/1.65 1229/1.87 1298/2.07 1361/2.30 1430/2.57 1498/2.82 1572/3.103375 50 ºF 830/1.15 920/1.36 1006/1.58 1085/1.81 1155/2.02 1225/2.23 1287/2.48 1350/2.72 1413/2.94 1467/3.19 1526/3.47 1582/3.714219 40 ºF 994/2.09 1073/2.37 1144/2.62 1213/2.89 1278/3.17 1337/3.43 1396/3.73 1455/4.00 1513/4.23 1563/4.56 1616/4.84 N/A1875 100 ºF 492/0.24 647/0.38 773/0.53 882/0.71 980/0.89 1071/1.08 1154/1.25 1230/1.47 1304/1.65 1376/1.81 1442/2.01 N/A2083 90 ºF 513/0.30 656/0.44 782/0.61 891/0.79 986/0.99 1075/1.19 1157/1.39 1234/1.61 1312/1.80 1377/2.01 1449/2.21 1515/2.432344 80 ºF 542/0.39 672/0.54 795/0.72 902/0.90 997/1.10 1084/1.33 1165/1.54 1242/1.80 1311/2.03 1379/2.25 1454/2.50 1512/2.74250 2679 70 ºF 582/0.53 698/0.70 812/0.89 916/1.08 1011/1.30 1099/1.52 1178/1.76 1253/2.03 1323/2.30 1392/2.53 1458/2.79 1520/3.093125 60 ºF 641/0.77 744/0.96 842/1.18 940/1.39 1029/1.62 1116/1.85 1196/2.12 1269/2.37 1337/2.66 1404/2.95 1471/3.22 1524/3.523750 50 ºF 733/1.21 817/1.45 904/1.69 984/1.93 1064/2.20 1145/2.48 1220/2.73 1293/3.02 1364/3.30 1429/3.61 1493/3.91 1546/4.234688 40 ºF 882/2.23 945/2.50 1014/2.80 1084/3.11 1150/3.42 1214/3.73 1280/4.02 1344/4.35 1410/4.71 N/A N/A N/AUnitSizeCFM Te m p 0.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25 2.50 2.75 3.00RiseTotal Static Pressure* Total adjusted external static <strong>pre</strong>ssure should include external static <strong>pre</strong>ssure and accessory/option static <strong>pre</strong>ssures. “Base unit” internalresistance has been included in these tables. BHP includes drive losses.Page 32 Form C-PREEVA


BHP/RPM CHARTS (cont’d)UnitSizeTe m pTotal Static PressureCFM Rise 0.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25 2.50 2.75 3.002250 100 ºF 529/0.35 666/0.52 789/0.68 889/0.86 983/1.05 1071/1.25 1154/1.49 1236/1.71 1308/1.94 1380/2.21 1442/2.43 N/A2500 90 ºF 559/0.44 683/0.62 801/0.81 906/1.00 996/1.20 1078/1.40 1157/1.63 1238/1.88 1309/2.11 1381/2.39 1445/2.66 1515/2.922812 80 ºF 597/0.58 710/0.77 820/0.98 922/1.19 1015/1.41 1094/1.63 1167/1.85 1239/2.08 1314/2.36 1385/2.63 1449/2.91 1512/3.22300 3214 70 ºF 652/0.80 753/1.01 848/1.24 943/1.48 1037/1.74 1120/1.97 1195/2.22 1260/2.47 1328/2.73 1391/2.98 1454/3.31 1516/3.573750 60 ºF 732/1.20 817/1.42 901/1.67 984/1.94 1065/2.22 1147/2.50 1221/2.79 1293/3.09 1359/3.38 1420/3.66 1476/3.92 1531/4.274500 50 ºF 851/1.95 916/2.21 989/2.51 1059/2.80 1128/3.11 1197/3.43 1264/3.80 1331/4.12 1398/4.48 1461/4.82 N/A N/A5625 40 ºF 1036/3.61 1086/3.96 1139/4.27 1194/4.61 1253/4.99 N/A N/A N/A N/A N/A N/A N/A2625 100 ºF 529/0.29 698/0.50 840/0.75 955/0.99 1055/1.24 1154/1.49 1243/1.76 1321/2.01 1400/2.29 1469/2.58 1544/2.89 N/A3088 90 ºF 561/0.38 712/0.61 852/0.89 969/1.17 1074/1.47 1165/1.76 1248/2.03 1328/2.35 1404/2.63 1479/2.93 1554/3.28 1615/3.583500 80 ºF 593/0.49 735/0.74 862/1.02 979/1.33 1085/1.67 1176/2.00 1261/2.31 1340/2.64 1414/2.96 1489/3.30 1556/3.66 1628/4.02350 3917 70 ºF 629/0.62 761/0.89 878/1.18 992/1.51 1096/1.87 1191/2.25 1279/2.60 1357/2.97 1431/3.34 1499/3.70 1567/4.06 1632/4.434375 60 ºF 669/0.79 794/1.09 904/1.41 1009/1.74 1108/2.10 1203/2.52 1292/2.93 1373/3.34 1446/3.76 1515/4.14 1584/4.56 1643/4.945250 50 ºF 753/1.23 864/1.56 963/1.93 1058/2.30 1144/2.69 1228/3.10 1313/3.55 1395/4.02 1469/4.50 N/A N/A N/A6563 40 ºF 885/2.17 981/2.58 1069/2.98 1151/3.43 1230/3.91 1303/4.38 1374/4.88 N/A N/A N/A N/A N/A3000 100 ºF 552/0.37 706/0.60 848/0.87 964/1.15 1067/1.44 1159/1.73 1244/2.01 1326/2.30 1404/2.62 1481/2.93 1548/3.24 1611/3.603333 90 ºF 578/0.45 721/0.69 857/0.97 977/1.28 1075/1.60 1169/1.92 1252/2.23 1333/2.56 1411/2.89 1481/3.23 1550/3.55 1616/3.923750 80 ºF 615/0.57 744/0.83 867/1.12 987/1.45 1091/1.80 1181/2.16 1266/2.51 1345/2.87 1422/3.24 1493/3.60 1563/3.97 1622/4.35400A 4285 70 ºF 663/0.77 783/1.05 893/1.37 999/1.71 1106/2.08 1199/2.49 1284/2.87 1366/3.28 1440/3.70 1510/4.12 1572/4.50 1640/4.945000 60 ºF 730/1.11 842/1.43 941/1.77 1034/2.14 1127/2.53 1220/2.95 1307/3.39 1389/3.86 1465/4.34 1533/4.81 N/A N/A6000 50 ºF 829/1.75 932/2.13 1021/2.52 1103/2.93 1182/3.35 1260/3.80 1337/4.28 1412/4.77 N/A N/A N/A N/A7500 40 ºF 984/3.13 1073/3.62 1154/4.11 1230/4.58 N/A N/A N/A N/A N/A N/A N/A N/AUnitSizeCFM Te m p 0.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25 2.50 2.75 3.00RiseTotal Static PressureNOTE: Blower curves can be found on the Reznorweb site www.RezSpec.<strong>com</strong>. From the RezSpec homepage, click on the “Manuals & Media” tab. On thedrop down menu, click on “Product Literature” then“Product Submittals.” On the “Product Submittal”page click on the PREEVA link.* Total adjusted external static <strong>pre</strong>ssure should include external static<strong>pre</strong>ssure and accessory/option static <strong>pre</strong>ssures. “Base unit” internalresistance has been included in these tables. BHP includes drivelosses.Form C- PREEVA Page 33


HEATING AND HEATING/COOLING CONTROLSOption Description / Application ControllersHeating or Heating/Makeup Air ANALOG ControlsAG1 Single-stage heatingSingle-stage room thermostat, either Option CL1, CL3, CL10, CL52, or field suppliedAG2 Two-stage heating (70% and 100%) Two-stage room thermostat, either Option CL7, CL8, CL11, CL33, or field suppliedAG3Two-stage ductstat, 50-120°F (discharge <strong>air</strong> temperature)Two-stage makeup <strong>air</strong> heating (70%Remote temperature dialAG15Electronic 2-stage discharge <strong>air</strong> sensor with remote setpoint, 50-120°Fand 100%)supplied as part of AG15,AG16Same as AG15 plus digital discharge temperature displayAG16, AG61, and AG62;AG60Makeup <strong>air</strong> with constant discharge Two-stage ductstat, 50-120°F (discharge <strong>air</strong> temperature)Two-stage room<strong>air</strong> temperature and constantthermostat, either OptionAG61 thermal efficiency with 33% low fire Electronic discharge <strong>air</strong> sensor with remote setpoint, 50-120°FCL7, CL8, CL11, CL33 orcapacity - natural gas, 40% low fireAG62 capacity - propaneSame as AG61 plus digital discharge temperature displayfield suppliedAG40Electronic modulation heating(25% low fire - natural gas;40% low fire -propane)Includes signal conditioner that accepts an input signal of either 4-20milliamps or 0-10 volts from a field-supplied controller and converts itto the 0-20 volt DC current required to control the modulating valve.Temperature selection or building system management is fromcustomer-supplied software.Heating/Cooling DIGITAL ControlsAll heating/cooling controls (Options DG1, DG2, DG5, and DG6) have a unit-mounted digital controller that is programmed with individual andadjustable heating and cooling setpoints, adjustable changeover setpoint, and low ambient cutoff setpoint. Depending on which option is selected,the digital controller provides either adjustable room or discharge temperature setpoint. Both room <strong>com</strong>mand modules (below) include "heat-ventcooland auto-off" blower switches and unoccupied override push button.2-stage heating (33% low fire capacity - natural gas, 40% low fireDG1capacity - propane) / 3-stage coolingSpace Temperature ControlElectronic modulation heating (25% low fire - natural gas, 40% low fire -DG2propane) / 3-stage coolingDG5DG6Makeup Air Control2-stage heating (33% low fire capacity - natural gas, 40% low firecapacity - propane) / 3-stage coolingElectronic modulation heating (25% low fire - natural gas, 40% low fire -propane) / 3-stage coolingRoom-mounted <strong>com</strong>mandmodule with 45-95°F spacetemperature setpoint.Room-mounted <strong>com</strong>mandmodule sensing dischargetemperature (45-95°F).Discharge setpoint can beadjusted ±6°F.Ductstat in OptionsAG3 and AG60Electronic Ductstat inOptions AG15, AG16,AG61, and AG62DuctstatStage AdderDisplay ModuleDigital Controller and Room Command Modules in Options DG1, DG2, DG5, and DG6FX05ProgrammableControllerPage 34 Form C-PREEVASpace TemperatureRoom-Mounted Command Modulepart of DG1 and DG2Makeup Air (Discharge Temperature)Room-Mounted Command Modulepart of DG5 and DG6


HEATING AND HEATING/COOLING CONTROLSFX05 SEQUENCE OF OPERATIONINTRODUCTIONAvailable with the new Reznor PREEVA indirect-fired seriesis an optional factory installed and <strong>pre</strong>-programmed <strong>com</strong>pletedigital heating and cooling master control. Control optionsDG1, DG2, DG5, and DG6 <strong>com</strong>e <strong>com</strong>pete with a JohnsonControl’s FX-05 advanced controller and room <strong>com</strong>mand moduleproviding total unit control.Option DG1is programmed for 2-stage gas heat & 3-stage cooling with a space temperaturecontroller (45 to 95°F)Option DG2is programmed for electronic modulatinggas heat for 4:1 turndown capacity onNatural gas (2.5:1 on Propane gas) & 3-stage cooling with a space temperaturecontroller (45 to 95°F)Option DG5is programmed for 2-stage gas heat & 3-stage cooling with a discharge <strong>air</strong>temperature controller that can adjust thedischarge <strong>air</strong> ± 6 °F from setpoint.Option DG6is programmed for electronic modulating gasheat for 4:1 turndown capacity on Natural gas(2.5:1 on propane gas) & 3-stage cooling witha discharge <strong>air</strong> temperature controller that canadjust the discharge <strong>air</strong> ± 6 °F from setpoint.All control options include a separate room <strong>com</strong>mand modulefrom which the unit can be turned on or off, set to heat, ventor cool mode has an unoccupied override push button. The pushbuttonwhen activated will immediately <strong>com</strong>mand the unit totemporarily lock the controller to the occupied setpoints for 60minutes. Additionally, the advanced controller can be fitted witha real 7-day time clock card for energy savings and better managementof the specific application or a serial <strong>com</strong>municationcard for <strong>com</strong>patibility with either the LON or N2open BASprotocols.KEY FACTORY DEFAULT SETPOINTS FOR ALL DG OPTIONS• Occupied Heating Setpoint (HSP) is 68°F. Only operable when sliderswitch is in “heat” position• Occupied Cooling Setpoint (CSP) is 72°F. Only operable when sliderswitch is in “cool” position• Offset temperature setpoint (DB) is 2°F. Only operable when sliderswitch is in “auto” position• Unoccupied Heating Setpoint is the Occupied Heating setpoint minusthe adjustable default value of 10°F or 58°F.• Unoccupied Cooling setpoint is the Occupied Cooling setpoint plusthe adjustable default value of 10°F or 82°F.• Heating deadband (HDB) for occupied and unoccupied mode is adjustable,but factory set at 0°F.• Heating Prop Band (HPB) for occupied and unoccupied mode isadjustable, but factory set at 10°F.• Cooling Prop Band (CPB) for occupied and unoccupied mode isadjustable, but factory set at 10°F.• Boost Setting: When option CL56 (automatic room override thermostat)contacts are closed an immediate boost mode will add anadjustable amount (default 5°F) to the occupied heating setpointand subtracted from the occupied cooling setpoint to bring the spaceto the temperature setting of the thermostat. Boost is inoperable inthe Auto mode.• Second Stage Heat Energizing (SSH) is adjustable, but is factoryset at a default of 90% of the prop band or 9°F.• Second Stage Heating Disable (SSO) is adjustable, but is factoryset at a default of 5% of the prop band or 0.5°F.DG1 AND DG2 HEATING SEQUENCE OF OPERATIONAs noted above the controller <strong>com</strong>es <strong>com</strong>plete with a simple<strong>pre</strong>programmed sequence of operation and factory set parametersthat are typical for most heating and cooling applications.Options DG1 and DG2 use the value at the room <strong>com</strong>mandmodule dial as the heating setpoint, when the switch is set toheating only mode. It is used as the cooling setpoint when theswitch is set to cooling only mode. In the Auto Mode, thesetpoint dial is the point from which the value of the offset (± 2°F default) is added and subtracted to achieve the working heatingand working cooling setpoints. (For example: if the dial isset is at 72°F, with the value of the offset at 2°F, then the workingheating setpoint is 70°F and the working cooling setpoint is74°F. Either heating or cooling can occur when the switch is inthis mode.In a typical sequence of operation, with the module switchset to heating, the unit will initiate heating if the temperaturesensed in the space falls below the heating setpoint (HSP) andthe heating deadband (HDB). When this occurs on units withoption DG1, the ignition sequence is energized, as is the firstor low stage valve. If required, the second or high stage valvewill close at the SSH setting (default 90% of the prop band or9°F.) The second or high stage gas valve will open when theproportional band is below the SSO setting (default 5% of theprop band or 0.5°F). The first or low stage valve will openwhen the space is above the heating setpoint (HSP) plus theheating deadband (HDB).Using the defaults as an example, if the space temperaturedrops below 68°F, the first stage of the two stage gas valvewill be energized.If the space temperature continues to drop to 59°F, the secondstage will be energized.The second stage remains energized until the space temperaturereaches 67.5°F, then is de-energized.The first stage is de-energized when the space temperaturereaches the setpoint of 68°F.For units with option DG2, upon a call for heat the ignitionsequence is energized as is the safety valve ahead of themodulating valve. The analog output signal will allow the modulatinggas valve to fully open for 80 seconds to ensure properForm C- PREEVA Page 35


HEATING AND HEATING/COOLING CONTROLS (cont’d)FX05 SEQUENCE OF OPERATION (cont’d)burner ignition. The gas valve will then modulate to a position,linearly with the HSP and the HPB to maintain the spacetemperature on the room <strong>com</strong>mand module.For example, when the space temperature drops to 67°F,the modulating valve will be fully open for 80 secondsthen modulate to the minimum flow position (approximately6 VDC). If the temperature continues to drop to58°F, the valve would be in the full open position (approximately3 VDC). The modulating valve will de-energizewhen the space temperature reaches the heating setpoint.DG5 AND DG6 HEATING SEQUENCE OF OPERATIONAs noted above the controller <strong>com</strong>es <strong>com</strong>plete with a simple<strong>pre</strong>programmed sequence of operation and factory set parametersthat are typical for most heating and cooling applications.Options DG5 and DG6 use the working setpoint value, definedas the heating setpoint (68°F default) plus or minus the settingof the room <strong>com</strong>mand module dial. The dial can change thedischarge <strong>air</strong> setpoint ± 6°F or from 62° to 74°F when usingthe default setting.In a typical sequence of operation, with the module switchset to heating, the unit will initiate heating if the discharge ductsensor temperature falls below the working setpoint temperatureand the heating deadband. When this occurs on units withoption DG5, the ignition sequence is energized, as is the firstor low stage valve. If required, the second or high stage valvewill close at the SSH setting (default 90% of the prop band or9°F.) The second or high stage gas valve will open when theproportional band is below the SSO setting (default 5% of theprop band or 0.5°F). The first or low stage valve will openwhen the discharge temperature is above the working setpointtemperature (HSP) plus the heating deadband (HDB).Using the defaults as an example, if the discharge temperaturedrops below 68°F, the first stage of the two-stagegas valve will be energized.If the discharge temperature continues to drop to 59°F, thesecond stage will be energized.The second stage remains energized until the dischargetemperature reaches 67.5°F then is de-energized.The first stage is de-energized when the discharge temperaturereaches the setpoint of 68°F.For units with option DG6, upon a call for heat the ignitionsequence is energized as is the safety valve ahead of themodulating valve. The analog output signal will allow the modulatinggas valve to fully open for 80 seconds to ensure properburner ignition. The gas valve will then modulate to a position,linearly with the HSP and the HPB to maintain the workingsetpoint temperature.For example, when the working discharge temperaturedrops to 67°F, the modulating valve will be fully open for80 seconds then modulate to the minimum flow position(approximately 6 VDC).If the temperature continued to drop to 58°F, the valvewould be in the full-open position (approximately 3 VDC).The modulating valve will de-energize when the dischargetemperature reaches the working heating setpoint.Page 36 Form C-PREEVADG1, DG2, DG5 AND DG6 COOLING SEQUENCE OF OP-ERATIONIn a typical sequence of operation, with the module switchset to cooling, the unit will initiate cooling if the space temperature(DG1 or DG2) or the discharge duct sensor temperature(DG5 or DG6) climbs above the cooling setpoint temperature(CSP) or the working cooling setpoint temperature intothe cooling prop band. At this point the stage one cooling isenergized when the space or discharge temperature reaches 10%of the cooling prop band. The second stage of cooling will beenergized when the temperature reaches 40% of the coolingprop band and third stage will be energized when the temperaturereaches 99% of the prop band.For example, if the working cooling setpoint on a DG5system (WCSP) is 72°F, Stage 1 cooling is energized whendischarge <strong>air</strong> temperature increases to 73°F (10% of the10°F CPB).Stage 2 is energized when space temperature increases to76°F (40% of the 10°F CPB).Stage 3 is energized when the space temperature increasesto 81.9°F (99% of the 10°F CPB).As the space temperature moves back towards WCSP, stage3 is de-energized at 40% call for cooling, stage 2 is deenergizedat 10% call for cooling, and stage 1 is de-energizedat 5%.Com<strong>pre</strong>ssor Interstage Delay time and Com<strong>pre</strong>ssor MinimumOn time are controlled by the built in time delay which isdefaulted at 240 seconds. This means that if stage 1 has justbegun, stage 2 cannot start for 240 seconds. Once stage 1 hasbegun, it must run for 240 seconds before it will be turned off.BLOWER MODES OF OPERATION• With the module switch set to the fan or vent position, the blowerwill run continuously, and heating and cooling modes cannot function.• When the unit is in the occupied mode and the switch is in eitherthe heat or cool mode, the blower will run continuously. In the unoccupiedmode, the fan will only run when there is a call for heatingor cooling.• Proof of fan operation is always monitored via the <strong>air</strong>-proving switch.If fan proof is lost for 3 seconds, the heating or cooling functionswill be shutdown.• If the mode switch is moved to the off position or the normal heatingor cooling cycle ends, the fan will run for a post-purge of 30seconds.SAFETY MODES OF OPERATION• If the controller’s discharge <strong>air</strong> or space sensor reads a temperaturevalue below 36°F for seven continuous minutes, the unit will stopall heating, cooling, or vent functions.• If the unit’s outdoor <strong>air</strong> sensor reads 68°F or below, mechanicalcooling will not function.• If the unit’s outdoor <strong>air</strong> sensor reads 62°F or above, heating will notfunction.


®REMOTE CONSOLEOPTIONAL ON INDIRECT FIRED PACKAGED HEATING/MAKEUP AIR SYSTEMSSTANDARD FEATURES• 16 Gauge steel box• Wiring terminal blocks• Engraved plastic cover• Stainless steel mounting ring• Designed for either recessed or wall mountingBLOWERONBURNERONCONTROL SWITCHON OFF®DIRTYFILTERDESCRIPTIONA Reznor remote console is designed to allow remote control ofthe system as well as provide indicator safety lights. The console is<strong>com</strong>prised of a 16-gauge steel box with knockouts for field wiring,wiring terminal blocks suited to <strong>com</strong>ponents, and a custom engravedplastic cover. The engraved lettering on the cover indicates the functionand position of the switch and the message of the indicator light.The box may be either recessed or wall mounted. A mounted ring isincluded for wall mounting. In place of the standard plastic cover, anoptional stainless steel cover is available (requires extended lead time).The remove console option is available with twelve <strong>pre</strong>-selected<strong>com</strong>binations of factory-installed switches, indicator lights and controls.The available <strong>com</strong>binations of <strong>com</strong>ponents are illustrated below.Each of the consoles may be ordered with one additional factory-mountedcontrol. Controls available are a one- or two-stage heatingthermostat, a one- two-stage heating/cooling thermostat, or aMaxitrol Temperature Selector. If the installation requires any <strong>com</strong>ponentsor <strong>com</strong>ponent <strong>com</strong>binations that are not available with OptionsRC1-12, it is necessary to specify a custom-built remote console(see Remote Console Section).Option RC1BLOWERON®BURNERONLights• Blower On• Burner OnOption RC5BLOWER BURNERON ONCONTROL SWITCHSUMMER WINTEROFF®Lights• Blower On• Burner OnSwitch• Summer/Off/WinterOption RC2BLOWERON®BURNERONDIRTYFILTERLights• Blower On• Burner On• Dirty FilterOption RC6BLOWERON®BURNERONCONTROL SWITCHSUMMER WINTEROFFDIRTYFILTERLights• Blower On• Burner On• Dirty FilterSwitch• Summer/Off/WinterOption RC3BLOWER BURNERON ONCONTROL SWITCHON OFFOption RC4BLOWER BURNERON ONCONTROL SWITCHON OFF®®DIRTYFILTERLights• Blower On• Burner OnSwitch• On/OffLights• Blower On• Burner On• Dirty FilterSwitch• On/OffOption RC7BLOWER BURNERON ONCONTROL SWITCHON OFFOption RC8®®COOLONSYSTEM SWITCHHEAT COOLVENTBLOWER BURNER DIRTYON ON FILTERCONTROL SWITCH SYSTEM SWITCHON OFF HEAT COOLVENTLights• Blower On• Burner On• Cool OnSwitch• On/Off• Heat/Vent/CoolLights• Blower On• Burner On• Dirty FilterSwitch• On/Off• Heat/Vent/CoolForm C- PREEVA Page 37


REMOTE CONSOLEOPTIONAL ON INDIRECT FIRED PACKAGED HEATING/MAKEUP AIR SYSTEMS (cont’d)Option RC9BLOWERONOPENDAMPERCLOSEPOTENTIOMETER®BURNERONOption RC10®COOLONBLOWER BURNERON ONCONTROL SWITCHSUMMER WINTEROFFLights• Blower On• Burner On• Cool OnLights• Blower On• Burner OnSwitch• Summer/Off/WinterControl• Potentiometer*Option RC11OPENDAMPERCLOSEPOTENTIOMETER®BLOWER BURNERON ONCONTROL SWITCHON OFFBLOWERONOption RC12®BURNERONCONTROL SWITCHON OFFDIRTYFILTERCOOLONCOOLONSYSTEM SWITCHHEAT COOLVENTSYSTEM SWITCHHEAT COOLVENTLights• Blower On• Burner On• Dirty Filter• Cool OnSwitch• On/Off• Heat/Vent/CoolLights• Blower On• Burner On• Cool OnSwitch• On/Off• Heat/Vent/CoolControl• Potentiometer** Must order Damper Arrangement Option GE10 to get a remote potentiometer (see Air Control System section).NOTE: To coordinate option selection, see Mixing Box Module and Air Inlet Options section for damper arrangement options and Heatingand Heating/Cooling Controls section for control selection.Remote ConsoleIncluded OptionsComponents Function RC1 RC2 RC3 RC4 RC5 RC6 RC7 RC8 RC9 RC10 RC11 RC12Blower On Indicator Light Lights when blower is operating X X X X X X X X X X X XBurner On Indicator Light Lights when burners are lit X X X X X X X X X X X XLights when the <strong>pre</strong>ssure switch indicates that filters need to beDirty Filter Indicator Light cleaned or replacedN/A X N/A X N/A X N/A X N/A N/A N/A XOn/Off Control Switch "On" position energizes the unit for thermostat control"Off" position de-energizes the unit and closes optionalautomatically controlled outside <strong>air</strong> dampersN/A N/A X X N/A N/A X X N/A N/A X XSummer/Winter/Off "Summer" position operates the blower onlyControl Switch"Winter" position energizes the unit for thermostat control"Off" position de-energizes the unit and closes optionalN/A N/A N/A N/A X X N/A N/A N/A X N/A N/Aautomatically controlled outside <strong>air</strong> dampersHeat/Vent/Cool"Heat" position energizes the unit for thermostat control.System Switch"Vent" position operates the blower and opens automaticallycontrolled outside <strong>air</strong> dampers"Cool" position energizes the blower, the dampers and cooling unitN/A N/A N/A N/A N/A N/A X X N/A N/A X XCooling Indicator Light Lights when cooling system is operating N/A N/A N/A N/A N/A N/A X N/A X N/A X X®Wires:Console Minimum No. Minimum No.Option of Wires Console Option of WiresRC1 3 RC10 7-9RC2 4 RC11 9-10RC3 5-6 RC12 8RC4 6-7 1-Stage Heating Thermostat +2RC5 5-6 2-Stage Heating Thermostat +3RC6 6-7 1-Stage Heating/Cooling Thermostat +4RC7 7 2-Stage Heating/Cooling Thermostat +5RC8 8 Maxitrol Temperature Selector +2RC9 4CAUTION: The minimum number of wires listed should be used only as a guideline. Do NOTuse for actual wiring. The required number of wires varies depending upon the circuit and thefunction of the switch and can only be accurately determined from the wiring diagram designedfor the specific installation.Page 38 Form C-PREEVAMinimumConsole Feature No. of Wires1 Light 22 Lights 33 Lights 44 Lights 5NOTE: For cooling light, add one wire.1 DPDT (3-position) Switch 4-61 SPDT Swtch 31 DPST Swtich 3-41 SPST Swtich 21 2-Stage Thermostat 3-91 1-Stage Thermostat 2-81 Potentiometer 3CAUTION: The minimum number of wireslisted should be used only as a guideline.Do NOT use for actual wiring. Therequired number of wires varies dependingupon the circuit and the function of theswitch and can only be accuratelydetermined from the wiring diagramdesigned for the specific installation.


®®®®SYSTEM ONTEMPORARYTHERMOSTATS FOR WALL OR CONSOLE MOUNTING1-Stage Heating Thermostat (Wall Mount Option CL1,Console Mount Option RCT1)(If console mounted, select one per console)1-Stage Heating/Cooling Thermostat (Wall Mount OptionCL3, Console Mount Option RCT3)60 70 8050904010040 50 60 70 80OFF40-80°F Range,30 V.A.C Maximum,.15 to 1.0 AmpsAdjustable Anticipator(Cross reference: P/N 91919)Use with Remote Consoles RC1-1240-90°F Range, 30 V.A.C. Maximum, .1 to1.2 Amps, Adjustable Anticipator(Cross reference: P/N 39581 with subbaseP/N 103352)Use with Remote Consoles RC1, 2, 92-Stage Heating Thermostat (Wall Mount Option CL7,Console Mount Option RCT2)50 60 70 8010 15 20 25°F °COFF AUTO®40-90°F Range,30 V.A.C. Maximum,.1 to 1.2 Amps,Adjustable Anticipator,Subbase with Off/Auto System Switch(Cross reference: Same thermostat asOption CL7, P/N 93435)2-Stage Heating/Cooling Thermostat (Wall Mount OptionCL11, Console Mount Option RCT4)40-90°F Range, 30 V.A.C. Maximum,.1 to 1.2 Amps, Adjustable Anticipator,HEAT 10 15 20 2550 60 70 80 °F°C10 15 20 25 Subbase with Auto/On Fan Switch and50 60 70 80 °F°C COOLOff/Heat/Auto/Cool System Switch50 60 70 8010 15 20 25°F °C®(Cross reference: P/N 93437)Use with Remote Consoles RC1, 2, 9Use with Remote Consoles RC1-12Programmable 2-Stage Heating/Cooling Thermostat (WallMount Option CL33, Console Mount Option RCT5*)7-Day programmableLCD DisplayLCD Display24VAC/50/60 Hz SupplyCover ClosedMicroprocessor ControlSelectable Output Staging:1) 1 Heat — 1 Cool2) 1 Heat — 2 Cool3) 2 Heat — 1 CoolLCD Display4) 2 Heat — 2 CoolSub/Base has Auto/Cool/Off/Heat System switch and Auto/On (fan) SwitchCover Open(Cross reference: P/N 110158)Use with Remote ConsolesRC1, RC2 or RC91-Stage Digital Control Override Thermostat (Wall MountOption CL56, Use with Digital Control Option DG5 or DG6)(Pictured below)1-Stage Heating/Cooling Thermostat (Wall Mount OptionCL10, Console Mount Option RCT3)40-90°F Range, 24-Volt, includes subbasewith fan auto/on and cool/off/heat switches.(Cross reference: P/N 39581 with subbaseP/N 103352)Use with Remote Consoles RC1, 2, 9* RCT5 contains most switching functions that are likely to be needed.Any switches on the panel limit the number of lights and/or potentiometerthat can be installed due to space limitations and affectscontrol sequence. Consult your Reznor Re<strong>pre</strong>sentative.1 Stage Heating/Cooling Thermostat on Panel (Wall MountOption CL52, Console Mount Option RCT9)5 Day/2 Day ProgrammableLCD Display(battery required)with Fan Auto/On andCool/Off/Heat Switches(Cross reference: P/N 205396)Use with Remote ConsolesRC1, RC2 or RC9Console Mounted Room Command Module (ConsoleMount Option RD4)Room-Mounted CommandModule for Space Temperaturecontrol (45° - 95°F). See optionsDG1 and DG2 on Heating/CoolingControl page.Use with Remote ConsolesRC1, RC2 or RC9Room-Mounted CommandModule for Makeup Air DischargeTemperature control(±6°F). See options DG5 andDG6 on Heating/Cooling Controlpage.Use with Remote ConsolesRC1, RC2 or RC945-Fan70Auto•Auto OffSetpointSet Time Temp EnterClock/DayScheduleOn•+Auto Off95RunProgramHoldTempSystem Cool Off Heat• • •Form C- PREEVA Page 39


REMOTE CONSOLEOPTIONAL ON INDIRECT FIRED PACKAGED HEATING/MAKEUP AIR SYSTEMS (cont’d)®Dimensions Length Height DepthWall Mounted - Remote Console with wallmounting ring in. mm in. mm in. mmConsoles RC1-RC10 and RC12 without anoptional control10 3/4 273 7 5/8 194 2 5/8 67Consoles RC-10 and RC12 with an optionalcontrol and RC11 with or without an optional 15 3/4 400 7 5/8 194 2 5/8 67controlRecessed - Size of the body; do not usemounting ring in. mm in. mm in. mmConsoles RC1-RC10, RC12 without anoptional control10 3/4 273 6 5/8 168 2 5/8 67Consoles RC-10 and RC12 with an optionalcontrol and RC11 with or without an optional 15 3/4 400 6 5/8 168 2 5/8 67control15-3/4” (400 mm)10-3/4” (274 mm)®LIGHTLABELLIGHTLABELSWITCH SWITCHLABEL LABELLIGHTLABELSWITCH SWITCHLABEL LABELLABEL®4050 60 7080CUSTOM BUILT REMOTE MONITORING CONSOLELIGHTLABELLIGHTLABELSWITCH SWITCHLABEL LABELLIGHTLABELSWITCH SWITCHLABEL LABELLABELOFFOPTIONAL CONTROLDESCRIPTIONIf <strong>com</strong>ponents or <strong>com</strong>ponent <strong>com</strong>binations are required that are not included in the standard remote console option offering, select acustom-built remote console. Custom design the console by selecting from the light label, switch label, and control selections listed below.Specific functions of all switches and lights must be included on the order.Custom REMCON - C - D - E - F - G - H - J - K - M - ZEngraved PlasticCustom Plastic Cover (<strong>com</strong>binationsLights Qty 2 3 4 2 3 4 2 3 4Cover on Metalor engraving not listed) - call ReznorBox with Switches (2 positionRe<strong>pre</strong>sentative for approval andQty 0 0 0 1 1 1 2 2 2Mounting Ring or 3 position)pricing.40 50 60 70 80LIGHT LABEL TO BEENGRAVED ON PLASTICCOVER(number of selections mustagree with quantity of lightsavailable on the REMCONmodel ordered)BURNEREB1BLOWEREB2DIRTY FILTER (LIGHTEB3with SWITCH IN UNIT)COOLEB4SAFETY LOCKOUT EB21Custom Label - 14SPECcharacters maximumPage 40 Form C-PREEVASWITCH LABELS TO BE ENGRAVED ON COVERSelect REMCON Size -C through -M based on number of lights and switches selected.Switches selected cannot have duplicate function.SUMMER/OFF/WINTER EB5A ON/OFF (SPDT System Switch) EB7XHEAT/OFF/VENT EB5B SUMMER/WINTER EB7AON/OFF/AUTO EB5C HEAT/VENT EB7BHEAT/VENT/COOL EB5D AUTO/ON EB7CDAY/OFF/NIGHT EB5E HEAT/COOL EB7DOCCUPIED/OFF/UNOCCUPIED EB5F DAY/NIGHT EB7ELOCAL/OFF/REMOTE EB5G OCCUPIED/UNOCCUPIED EB7FHIGH/OFF/LOW EB5H LOCAL/REMOTE EB7GHIGH/MED/LOW EB5I HIGH/LOW EB7HHAND/OFF/AUTO EB5J SPRAY/DRY EB7JHEAT/OFF/COOL EB5K FILL/DRAIN EB7KON/OFF (DPST System Switch) EB6X DAMPER OPEN/CLOSED EB7LCustom Label - 22 characters maximumSPEC


MODEL PDH/SDH ACCESSORIESDUCT FLANGE DIMENSIONSThe optional discharge duct flange is 4" (102mm) deep with a3/4" (19mm) wide flange on all sides.The optional inlet duct flange on the blower cabinet is 1-1/2"(38mm) deep with a 3/4" (19mm) wide flange on all sides.X3/4”(19mm)3/4”(19mm)DischargeOpeningwith Duct FlangeOption AX43/4”(19mm)Y3/4”(19mm)XBlower CabinetInlet Air Openingwith Duct FlangeOption AR53/4”(19mm)3/4”(19mm)Y3/4”(19mm)3/4”(19mm)Dimensions of Optional Discharge Duct FlangeModelXYSize inches mm inches mm75, 100 19 484 15 1/8 383125, 150 29 738 15 1/8 383175, 200,22522 1/4 565 24 3/8 618250, 300 30 1/8 765 24 3/8 618350, 400A 29 3/4 757 24 3/8 618DISCHARGE AIR NOZZLE DIMENSIONSDimensions of Optional Inlet Air Duct FlangeModelXYSize inches mm inches mm75, 100 26 660 26 5/8 675125, 150 36 914 26 5/8 675175, 200,22526 660 38 7/8 986250, 300 42 1/4 1073 38 7/8 986350, 400A 50 1/4 1276 38 7/8 986With 25-65°downturnnozzle withhorizontallouvers(OptionCD2)With 50-90°downturnnozzle withhorizontallouvers(OptionCD3)With 25-65°downturnnozzle withhorizontaland verticallouvers(OptionCD4)With 50-90°downturnnozzle withhorizontaland verticallouvers(OptionCD5)ZZZZDimension ZModel Sizes 75, 100, 125, 150 175, 200, 225, 250, 300, 350, 400AOption inches mm inches mmCD2 9 229 13 5/8 345CD3 15 5/8 398 23 5/8 600CD4 12 1/2 318 17 1/8 435CD5 18 7/8 481 25 5/8 652Option CD5 - Nozzlewith Horizontal andVertical LouversForm C- PREEVA Page 41


MODEL RDH ACCESSORIESOPTIONAL WEATHER HOOD - Dimensions100% Outside Air Screened Intake Hood w/Rain Baffles - Option AS2Weather hood shipped separately, knocked down, for field installation.4-13/16”123mm42”1,066mmSizes 75-150SIZE lbs kg75-100 70 32125-150 76 34175-225 76 34250-300 87 39350-400A 96 4413/16”21mm13/16”21mm7-9/16”192mm40-1/2”1029mm15-5/16”389mmSizes 175-400A7-9/16”192mmOPTIONAL ENERGY RECOVERY ARRANGEMENTFor more information, see the Energy Recovery Catalog, Form C-ER.Model XBWUField Supplied TransitionModel RDHField ConfiguredBottom R/AOptions (AR5/ARA6) and BB8ARRANGEMENT FOR USE WITHENERGY RECOVERY MODULEMODEL RDH ROOF CURBModel RDH outdoor systems are designed to be mounted on aroof or a cement slab. The system may be set directly on a slab withoutany additional support. When on a roof, either a manufacturerdesignedroof curb, a field-supplied roof curb, or other field-suppliedsupport is required. NOTE: A roof curb is re<strong>com</strong>mended with adownturn plenum and/or bottom return <strong>air</strong> to provide a weatherproofinstallation.The system is equipped with a load-bearing curb cap which formsthe integral part of the unit. The curb cap has bolted seams and isdesigned so that it may be set directly on a cement slab, on perpendicularsupports, or over a roof curb.6-1/4”(159mm)Curb Cap BaseMUST be sealedbetween curb capand roof curbUnit Base maybe set directly ona cement slab orperpendicularsupports.Wood NailerInsulationUnit Bottom(insulationretainer)Optional orField-SuppliedRoof CurbPage 42 Form C-PREEVA


MODEL RDH ROOF CURB DIMENSIONSOption Inches (±1/8) mm (±3) Weight?Configuration Code RDH Size A B C D A B C D lbs kg75, 100 51 13/16 29 13/16 48 1/16 26 1/16 1,316 757 1,221 662 90 41125, 150 51 13/16 39 13/16 48 1/16 36 1/16 1,316 1,011 1,221 916 101 46Model RDH Basic Unit ONLY CJ8A 175, 200, 225 67 1/2 29 13/16 63 3/4 26 1/16 1,715 757 1,619 662 107 49250, 300 67 1/2 46 1/16 63 3/4 42 5/16 1,715 1,170 1,619 1,075 125 57350, 400A 67 1/2 54 1/16 63 3/4 50 5/16 1,715 1,373 1,619 1,278 134 61?Basic unt PLUS one optional 75, 100 79 9/16 29 13/16 75 13/16 26 1/16 2,021 757 1,926 662 120 54module -- 125, 150 79 9/16 39 13/16 75 13/16 36 1/16 2,021 1,011 1,926 916 131 59- Downturn Plenum, OR CJ8B 175, 200, 225 95 1/4 29 13/16 91 1/2 26 1/16 2,419 757 2,324 662 138 63- Mixing Box, OR 250, 300 95 1/4 46 1/16 91 1/2 42 5/16 2,419 1,170 2,324 1,075 155 70- Cooling Cabinet 350, 400A 95 1/4 54 1/16 91 1/2 50 5/16 2,419 1,373 2,324 1,278 164 74?Basic unt PLUS two optional 75, 100 107 5/16 29 13/16 103 9/16 26 1/16 2,726 757 2,631 662 151 68modules -- 125, 150 107 5/16 39 13/16 103 9/16 36 1/16 2,726 1,011 2,631 916 162 73- Downturn Plenum & Mixing CJ8C 175, 200, 225 123 29 13/16 119 1/4 26 1/16 3,124 757 3,029 662 168 76Box or Cooling Cabinet, OR 250, 300 123 46 1/16 119 1/4 42 5/16 3,124 1,170 3,029 1,075 186 84- Mixing Box & Cooling Cabinet 350, 400A 123 54 1/16 119 1/4 50 5/16 3,124 1,373 3,029 1,278 195 88Basic unt PLUS three optional 75, 100 135 1/16 29 13/16 131 5/16 26 1/16 3,431 757 3,335 662 181 82modules -- 125, 150 135 1/16 39 13/16 131 5/16 36 1/16 3,431 1,011 3,335 916 192 87-Downturn Plenum, AND CJ8D 175, 200, 225 150 3/4 29 13/16 147 26 1/16 3,829 757 3,734 662 199 90- Mixing Box, AND 250, 300 150 3/4 46 1/16 147 42 5/16 3,829 1,170 3,734 1,075 216 98-Cooling Cabinet 350, 400A 150 3/4 54 1/16 147 50 5/16 3,829 1,373 3,734 1,278 225 102Locations of Duct Openings in Optional Roof Curb Opening -• Duct openings should be 1" (25mm) larger than the duct size for installation clearance.KKSize F Hwithout acooling coilmodulewith acooling coilmodule Size F Hwithout acooling coilmodulewith acooling coilmodule75, 100 22-7/8 1-9/16 81-5/8 109-3/8 75, 100 581 40 2,073 2,778125, 150 26-1/2 4-3/4 81-5/8 109-3/8 125, 150 673 121 2,073 2,778165, 200, 225 22-7/8 1-9/16 97-3/8 125-1/8 165, 200, 225 581 40 2,473 3,178250, 300 34-3/4 3-3/4 97-3/8 125-1/8 250, 300 883 96 2,473 3,178350, 400A 45-13/16 2-1/4 97-3/8 125-1/8 350, 400A 1164 57 2,473 3,178ACHHB DOptionalReturn AirOpening inMixing Box(has a 3/4”duct flange)18-3/8”(467mm)FAirflowDirectionFOptionalDownturnDischargeOpening(has a 3/4”duct flange)1-3/4” (44mm)10-15/16”(278mm)cLof openingHReznor Optional RoofCurb - 1-7/8” (48mm)top width of all curb railsKH18-3/8”(467mm)cLof opening1-3/4”(44mm)10-15/16”(278mm)• Curb is 16” high.Form C- PREEVA Page 43


HIGH ALTITUDE CAPACITY CHANGES - U.S.The input and/or the capacity of the heater changes with altitude. The table below lists inputs andcapacities at altitudes from sea level to 9,000 ft (2,745M) for installations in the United States. The tableon the following page lists inputs and capacities at altitudes from sea level to 4,500 ft (1373M) forinstallations in Canada.BTUH Inputs and Capacities by Altitude in the UNITED STATES for Models PDH, RDH & SDH2-Stage with Venter ModulationMotor Controller Minimum InputThermalThermalNormalM inimum Input (applies (applies to NormalALTITUDEOutputOutputInputto AG60, AG61, AG62, Options DG2, InputCapacityCapacity2-StageM inimumInput (appliesto AG2,AG3, AG15,AG16)2-StageMinimumInput (appliesto AG2,2-Stage with VenterMotor ControllerMinimum Input (appliesto AG60, AG61, AG62,M odulationM inimum Input(applies toOptions DG2,DG1, DG5)DG6)AG3, AG15, DG1, DG5)DG6)Natural Propane Natural Propane AG16) Natural Propane Natural PropaneFeet MetersSize 75Size 1000-2000 0-610 75,000 60,750 52,500 24,750 30,000 18,750 30,000 100,000 81,000 70,000 33,000 40,000 25,000 40,0002001-3000 611-915 70,500 57,105 49,350 23,265 28,200 17,625 28,200 94,000 76,140 65,800 31,020 37,600 23,500 37,6003001-4000 916-1220 69,000 55,890 48,300 22,770 27,600 17,250 27,600 92,000 74,520 64,400 30,360 36,800 23,000 36,8004001-5000 1221-1525 67,500 54,675 47,250 22,275 27,000 16,875 27,000 90,000 72,900 63,000 29,700 36,000 22,500 36,0005001-6000 1526-1830 66,000 53,460 46,200 21,780 26,400 16,500 26,400 88,000 71,280 61,600 29,040 35,200 22,000 35,2006001-7000 1831-2135 64,500 52,245 45,150 21,285 25,800 16,125 25,800 86,000 69,660 60,200 28,380 34,400 21,500 34,4007001-8000 2136-2440 63,000 51,030 44,100 20,790 25,200 15,750 25,200 84,000 68,040 58,800 27,720 33,600 21,000 33,6008001-9000 2441-2745 61,500 49,815 43,050 20,295 24,600 15,375 24,600 82,000 66,420 57,400 27,060 32,800 20,500 32,800Feet MetersSize 125Size 1500-2000 0-610 125,000 101,250 87,500 41,250 50,000 31,250 50,000 150,000 121,500 105,000 49,500 60,000 37,500 60,0002001-3000 611-915 117,500 95,175 82,250 38,775 47,000 29,375 47,000 141,000 114,210 98,700 46,530 56,400 35,250 56,4003001-4000 916-1220 115,000 93,150 80,500 37,950 46,000 28,750 46,000 138,000 111,780 96,600 45,540 55,200 34,500 55,2004001-5000 1221-1525 112,500 91,125 78,750 37,125 45,000 28,125 45,000 135,000 109,350 94,500 44,550 54,000 33,750 54,0005001-6000 1526-1830 110,000 89,100 77,000 36,300 44,000 27,500 44,000 132,000 106,920 92,400 43,560 52,800 33,000 52,8006001-7000 1831-2135 107,500 87,075 75,250 35,475 43,000 26,875 43,000 129,000 104,490 90,300 42,570 51,600 32,250 51,6007001-8000 2136-2440 105,000 85,050 73,500 34,650 42,000 26,250 42,000 126,000 102,060 88,200 41,580 50,400 31,500 50,4008001-9000 2441-2745 102,500 83,025 71,750 33,825 41,000 25,625 41,000 123,000 99,630 86,100 40,590 49,200 30,750 49,200Feet MetersSize 175 Size 2000-2000 0-610 175,000 141,750 122,500 57,750 70,000 43,750 70,000 200,000 162,000 140,000 66,000 80,000 50,000 80,0002001-3000 611-915 164,500 133,245 115,150 54,285 65,800 41,125 65,800 188,000 152,280 131,600 62,040 75,200 47,000 75,2003001-4000 916-1220 161,000 130,410 112,700 53,130 64,400 40,250 64,400 184,000 149,040 128,800 60,720 73,600 46,000 73,6004001-5000 1221-1525 157,500 127,575 110,250 51,975 63,000 39,375 63,000 180,000 145,800 126,000 59,400 72,000 45,000 72,0005001-6000 1526-1830 154,000 124,740 107,800 50,820 61,600 38,500 61,600 176,000 142,560 123,200 58,080 70,400 44,000 70,4006001-7000 1831-2135 150,500 121,905 105,350 49,665 60,200 37,625 60,200 172,000 139,320 120,400 56,760 68,800 43,000 68,8007001-8000 2136-2440 147,000 119,070 102,900 48,510 58,800 36,750 58,800 168,000 136,080 117,600 55,440 67,200 42,000 67,2008001-9000 2441-2745 143,500 116,235 100,450 47,355 57,400 35,875 57,400 164,000 132,840 114,800 54,120 65,600 41,000 65,600Feet MetersSize 225 Size 2500-2000 0-610 225,000 182,250 157,500 74,250 90,000 56,250 90,000 250,000 202,500 175,000 82,500 100,000 62,500 100,0002001-3000 611-915 211,500 171,315 148,050 69,795 84,600 52,875 84,600 235,000 190,350 164,500 77,550 94,000 58,750 94,0003001-4000 916-1220 207,000 167,670 144,900 68,310 82,800 51,750 82,800 230,000 186,300 161,000 75,900 92,000 57,500 92,0004001-5000 1221-1525 202,500 164,025 141,750 66,825 81,000 50,625 81,000 225,000 182,250 157,500 74,250 90,000 56,250 90,0005001-6000 1526-1830 198,000 160,380 138,600 65,340 79,200 49,500 79,200 220,000 178,200 154,000 72,600 88,000 55,000 88,0006001-7000 1831-2135 193,500 156,735 135,450 63,855 77,400 48,375 77,400 215,000 174,150 150,500 70,950 86,000 53,750 86,0007001-8000 2136-2440 189,000 153,090 132,300 62,370 75,600 47,250 75,600 210,000 170,100 147,000 69,300 84,000 52,500 84,0008001-9000 2441-2745 184,500 149,445 129,150 60,885 73,800 46,125 73,800 205,000 166,050 143,500 67,650 82,000 51,250 82,000Feet MetersSize 300Size 3500-2000 0-610 300,000 243,000 210,000 99,000 120,000 75,000 120,000 350,000 283,500 245,000 115,500 140,000 87,500 140,0002001-3000 611-915 282,000 228,420 197,400 93,060 112,800 70,500 112,800 329,000 266,490 230,300 108,570 131,600 82,250 131,6003001-4000 916-1220 276,000 223,560 193,200 91,080 110,400 69,000 110,400 322,000 260,820 225,400 106,260 128,800 80,500 128,8004001-5000 1221-1525 270,000 218,700 189,000 89,100 108,000 67,500 108,000 315,000 255,150 220,500 103,950 126,000 78,750 126,0005001-6000 1526-1830 264,000 213,840 184,800 87,120 105,600 66,000 105,600 308,000 249,480 215,600 101,640 123,200 77,000 123,2006001-7000 1831-2135 258,000 208,980 180,600 85,140 103,200 64,500 103,200 301,000 243,810 210,700 99,330 120,400 75,250 120,4007001-8000 2136-2440 252,000 204,120 176,400 83,160 100,800 63,000 100,800 294,000 238,140 205,800 97,020 117,600 73,500 117,6008001-9000 2441-2745 246,000 199,260 172,200 81,180 98,400 61,500 98,400 287,000 232,470 200,900 94,710 114,800 71,750 114,800Feet MetersSize 400A0-2000 0-610 400,000 324,000 280,000 132,000 160,000 100,000 160,0002001-3000 611-915 376,000 304,560 263,200 124,080 150,400 94,000 150,4003001-4000 916-1220 368,000 298,080 257,600 121,440 147,200 92,000 147,2004001-5000 1221-1525 360,000 291,600 252,000 118,800 144,000 90,000 144,0005001-6000 1526-1830 352,000 285,120 246,400 116,160 140,800 88,000 140,8006001-7000 1831-2135 344,000 278,640 240,800 113,520 137,600 86,000 137,6007001-8000 2136-2440 336,000 272,160 235,200 110,880 134,400 84,000 134,4008001-9000 2441-2745 328,000 265,680 229,600 108,240 131,200 82,000 131,200Page 44 Form C-PREEVA


HIGH ALTITUDE CAPACITY CHANGES - CANADABTUH Inputs and Capacities by Altitude in CANADA for Models PDH, RDH & SDH2-Stage 2-Stage with Venter ModulationM inimum Motor Controller Minimum InputThermalNormalInput (applies M inimum Input (applies (applies toALTITUDEOutputInputto AG2, to AG60, AG61, AG62, Options DG2,CapacityAG3, AG15,AG16)DG1, DG5)DG6)AG3, AG15, DG1, DG5)DG6)Natural Propane Natural Propane AG16) Natural Propane Natural PropaneFeet MetersSize 75Size 1000-2000 0-610 75,000 60,750 52,500 24,750 30,000 18,750 30,000 100,000 81,000 70,000 33,000 40,000 25,000 40,0002001-4500 611-1373 67,500 54,675 47,250 22,275 27,000 16,875 27,000 90,000 72,900 63,000 29,700 36,000 22,500 36,000Feet MetersSize 125Size 1500-2000 0-610 125,000 101,250 87,500 41,250 50,000 31,250 50,000 150,000 121,500 105,000 49,500 60,000 37,500 60,0002001-4500 611-1373 112,500 91,125 78,750 37,125 45,000 28,125 45,000 135,000 109,350 94,500 44,550 54,000 33,750 54,000Feet MetersSize 175Size 2000-2000 0-610 175,000 141,750 122,500 57,750 70,000 43,750 70,000 200,000 162,000 140,000 66,000 80,000 50,000 80,0002001-4500 611-1373 157,500 127,575 110,250 51,975 63,000 39,375 63,000 180,000 145,800 126,000 59,400 72,000 45,000 72,000Feet MetersSize 225 Size 2500-2000 0-610 225,000 182,250 157,500 74,250 90,000 56,250 90,000 250,000 202,500 175,000 82,500 100,000 62,500 100,0002001-4500 611-1373 202,500 164,025 141,750 66,825 81,000 50,625 81,000 225,000 182,250 157,500 74,250 90,000 56,250 90,000Feet MetersSize 300 Size 3500-2000 0-610 300,000 243,000 210,000 99,000 120,000 75,000 120,000 350,000 283,500 245,000 115,500 140,000 87,500 140,0002001-4500 611-1373 270,000 218,700 189,000 89,100 108,000 67,500 108,000 315,000 255,150 220,500 103,950 126,000 78,750 126,000Feet MetersSize 400A0-2000 0-610 400,000 324,000 280,000 132,000 160,000 100,000 160,0002001-4500 611-1373 360,000 291,600 252,000 118,800 144,000 90,000 144,000NormalInputThermalOutputCapacity2-StageMinimumInput (appliesto AG2,2-Stage with VenterMotor ControllerMinimum Input (appliesto AG60, AG61, AG62,M odulationM inimum Input(applies toOptions DG2,FULL LOAD AMP (FLA) TABLEMotor Motor MotorHP Type F.L.A. RPM Voltage PH0.25 OPEN 5.1 1750 120 10.25 OPEN 2.1 1750 208 10.25 OPEN 2.3 1750 240 10.25 OPEN 1.1 1750 208 30.25 OPEN 1.4 1750 240 30.25 OPEN 0.75 1750 480 30.25 TEFC 3.6 1750 120 10.25 TEFC 2.2 1750 208 10.25 TEFC 1.9 1750 240 10.25 TEFC 1.6 1750 208 30.25 TEFC 1.4 1750 240 30.25 TEFC 0.7 1750 480 30.33 OPEN 5.5 1750 120 10.33 OPEN 3.2 1750 208 10.33 OPEN 2.8 1750 240 10.33 OPEN 1.4 1750 208 30.33 OPEN 1.6 1750 240 30.33 OPEN 0.8 1750 480 30.33 TEFC 4.6 1750 120 10.33 TEFC 2.3 1750 208 10.33 TEFC 2.4 1750 240 10.33 TEFC 1.2 1750 208 30.33 TEFC 1.2 1750 240 30.33 TEFC 0.6 1750 480 30.50 OPEN 8.8 1750 120 10.50 OPEN 5.1 1750 208 10.50 OPEN 4.4 1750 240 10.50 OPEN 2.1 1750 208 30.50 OPEN 2 1750 240 30.50 OPEN 1 1750 480 30.50 TEFC 7 1750 120 10.50 TEFC 3.4 1750 208 10.50 TEFC 3.5 1750 240 10.50 TEFC 2.3 1750 208 30.50 TEFC 2 1750 240 30.50 TEFC 1 1750 480 30.50 TEFC 0.7 1750 575 30.75 OPEN 11 1750 120 10.75 OPEN 6.3 1750 208 10.75 OPEN 5.5 1750 240 10.75 OPEN 2.9 1750 208 30.75 OPEN 2.6 1750 240 30.75 OPEN 1.3 1750 480 30.75 TEFC 11 1750 120 10.75 TEFC 5.4 1750 208 10.75 TEFC 5.5 1750 240 10.75 TEFC 2 1750 208 30.75 TEFC 2.2 1750 240 30.75 TEFC 1.1 1750 480 30.75 TEFC 0.8 1750 575 3Motor Motor MotorHP Type F.L.A. RPM Voltage PH1.00 OPEN 13 1750 120 11.00 OPEN 7.5 1750 208 11.00 OPEN 6.5 1750 240 11.00 OPEN 3.7 1750 208 31.00 OPEN 3.2 1750 240 31.00 OPEN 1.6 1750 480 31.00 OPEN 1.4 1750 575 31.00 TEFC 13 1750 120 11.00 TEFC 6.5 1750 240 11.00 TEFC 3.3 1750 208 31.00 TEFC 3.4 1750 240 31.00 TEFC 1.7 1750 480 31.00 TEFC 1.4 1750 575 31.00 EE 3.1 1750 208 31.00 EE 2.7 1750 240 31.00 EE 1.35 1750 480 31.00 EE 1.1 1750 575 31.50 TEFC 16.4 1750 120 11.50 TEFC 9.5 1750 208 11.50 TEFC 8.2 1750 240 11.50 TEFC 4.3 1750 208 31.50 TEFC 4.4 1750 240 31.50 TEFC 2.2 1750 480 31.50 TEFC 1.8 1750 575 31.50 EE 4.5 1750 208 31.50 EE 3.9 1750 240 31.50 EE 1.95 1750 480 31.50 EE 1.6 1750 575 31.50 OPEN 15 1750 120 11.50 OPEN 8.3 1750 208 11.50 OPEN 7.5 1750 240 11.50 OPEN 5.6 1750 208 31.50 OPEN 5 1750 240 31.50 OPEN 2.7 1750 480 31.50 OPEN 2 1750 575 32.00 OPEN 20.4 1750 120 12.00 OPEN 10 1750 208 12.00 OPEN 10.2 1750 240 12.00 OPEN 7 1750 208 32.00 OPEN 6.6 1750 240 32.00 OPEN 3.3 1750 480 32.00 OPEN 2.4 1750 575 32.00 TEFC 24 1750 120 12.00 TEFC 12 1750 240 12.00 TEFC 6.5 1750 208 32.00 TEFC 5.6 1750 240 32.00 TEFC 2.8 1750 480 32.00 TEFC 2.2 1750 575 32.00 EE 6 1750 208 32.00 EE 5.2 1750 240 32.00 EE 2.6 1750 480 32.00 EE 2.1 1750 575 3Motor Motor MotorHP Type F.L.A. RPM Voltage PH3.00 OPEN 14 3600 208 13.00 OPEN 12.4 3600 240 13.00 OPEN 9.1 3600 208 33.00 OPEN 8.4 3600 240 33.00 OPEN 4.2 3600 480 33.00 OPEN 3.6 3600 575 13.00 TEFC 30 3600 120 13.00 TEFC 15 3600 240 33.00 TEFC 8.5 3600 208 33.00 TEFC 8.2 3600 240 33.00 TEFC 4.1 3600 480 33.00 TEFC 3.1 3600 575 33.00 EE 8.6 3600 208 33.00 EE 7.8 3600 240 33.00 EE 3.9 3600 480 33.00 EE 3 3600 575 35.00 OPEN 28 3600 208 15.00 OPEN 26 3600 240 15.00 OPEN 13.4 3600 208 35.00 OPEN 13.2 3600 240 35.00 OPEN 6.6 3600 480 35.00 OPEN 5.4 3600 575 35.00 TEFC 13.2 3600 208 35.00 TEFC 12 3600 240 35.00 TEFC 6 3600 480 35.00 TEFC 4.8 3600 575 35.00 TEFC 22.8 3600 240 15.00 EE 13.9 3600 208 35.00 EE 12.6 3600 240 35.00 EE 6.3 3600 480 35.00 EE 4.8 3600 575 35/2.2 2 SPD 17.2/11.3 1800/1200 208 35/2.3 2 SPD 15.5/10.2 1800/1200 230 35/2.4 2 SPD 7.1/14.8 1800/1200 460 37.50 OPEN 35 1750 208 17.50 OPEN 32 1750 240 17.50 OPEN 22 1750 208 37.50 OPEN 21 1750 240 37.50 OPEN 10.5 1750 480 37.50 OPEN 8.4 1750 575 37.50 TEFC 34 1750 240 17.50 TEFC 23 1750 208 37.50 TEFC 21 1750 240 37.50 TEFC 10.5 1750 480 37.50 TEFC 8.4 1750 575 37.50 EE 22.5 1750 208 37.50 EE 19.6 1750 240 37.50 EE 9.8 1750 480 37.50 EE 7.5 1750 575 3Motor Motor MotorHP Type F.L.A. RPM Voltage PH7.5/3.3 2 SPD 21.6/13.6 1800/1200 208 37.5/3.3 2 SPD 19.5/12.3 1800/1200 230 37.5/3.3 2 SPD 9.75/6.2 1800/1200 460 310.00 OPEN 42 1750 208 110.00 OPEN 38 1750 240 110.00 OPEN 30 1750 208 310.00 OPEN 26 1750 240 310.00 OPEN 13 1750 480 310.00 OPEN 10.4 1750 575 310.00 OPEN 9.9 1750 575 310.00 TEFC 39 1750 240 110.00 TEFC 30 1750 208 310.00 TEFC 26 1750 240 310.00 TEFC 13 1750 480 310.00 TEFC 10.4 1750 575 310.00 EE 28 1750 208 310.00 EE 24.4 1750 240 310.00 EE 12.2 1750 480 310.00 EE 9.7 1750 575 310/4.4 2 SPD 31/19.4 1800/1200 208 310/4.4 2 SPD 28/17.5 1800/1200 230 310/4.4 2 SPD 13.5/7.5 1800/1200 460 315.00 OPEN 43.1 1750 208 315.00 OPEN 39 1750 240 315.00 OPEN 19.5 1750 480 315.00 OPEN 16 1750 575 315.00 TEFC 38 1750 240 315.00 TEFC 19 1750 480 315.00 TEFC 15 1750 575 315.00 EE 40 1750 208 315.00 EE 36 1750 240 115.00 EE 18 1750 480 315.00 EE 14.5 1750 575 320.00 OPEN 58.7 1750 208 320.00 OPEN 53 1750 240 320.00 OPEN 26.5 1750 480 320.00 OPEN 21.2 1750 575 320.00 TEFC 52 1750 240 320.00 TEFC 26 1750 480 320.00 TEFC 20.6 1750 575 320.00 EE 52.9 1750 208 320.00 EE 48 1750 240 320.00 EE 24 1750 480 320.00 EE 19.2 1750 575 3Form C- PREEVA Page 45


SAMPLE SPECIFICATIONModel SDH, INDOOR HEATING AND MAKEUP AIR UNITS(SEPARATED COMBUSTION)Provide packaged, indoor heating and makeup <strong>air</strong> unitswith separated <strong>com</strong>bustion as Reznor ® brand equipment. Theunits shall be the SDH series, minimum 81% efficiency, withseparated-<strong>com</strong>bustion gas furnace, designed for ceiling suspensionor floor or slab mounting. The gas furnace is to be arrangedfor ducted inlet <strong>com</strong>bustion <strong>air</strong> and flue gas exhaust.The unit must have single point wall or roof penetration forentry of <strong>com</strong>bustion <strong>air</strong> and exhaust of flue gases by the use ofa concentric adapter. Separated <strong>com</strong>bustion is to be used innegative building <strong>pre</strong>ssures and/or dirty or corrosive atmospheres.All units shall be equipped for use with (natural gas) (propane);(115/1) (208/1) (230/1) (208/3) (230/3) (460/3) (575/3)supply voltage with (unit mounted, non-fusible, lockable disconnectswitch); 24-volt control transformer; protective <strong>air</strong>proving switch; resiliently (rubber) (spring) isolated venter motor;and a high temperature limit control. Operation shall becontrolled through an integrated circuit board. The circuit boardshall monitor heater operation and have LED diagnostic indicatorlights to identify abnormalities in control functions. Unitshall have a (one-stage gas control) (two-stage gas control) (twostagegas makeup <strong>air</strong> control) (33% low fire capacity makeup<strong>air</strong> control) (2-stage heating/3-stage cooling digital control[space temperature] [discharge temperature]); or (electronicmodulation heating 25% low fire - natural gas, 40% low fired- propane/3-stage cooling digital control [space temperature][discharge temperature]).The gas furnace shall have a Reznor TCORE 2® heat exchangerand single burner <strong>com</strong>bustion system. The heat exchangershall be of (aluminized) (409 stainless) (316 stainless)steel. The furnace shall be equipped with all required safetyelements.The (single wall, [uninsulated] [insulated]) (double wall[insulated] [high density insulated]) blower section shall be suppliedwith (horizontal supply opening) (screened horizontal supplyopening) (horizontal supply <strong>air</strong> inlet opening with ductflanges) (screened horizontal supply <strong>air</strong> inlet opening with ductflanges). The blower section shall include an adjustable beltdriven(rubber) (spring) vibration isolated centrifugal blowerand (open dripproof) (totally enclosed) (<strong>pre</strong>mium efficiency)(2-speed) [rubber] [spring] vibration isolated motor with(contactor) (motor starter) (variable frequency drive). (Unit mayinclude [1” or 2” disposable] [1” or 2” permanent] [1”, 2”, or4” pleated] filters).Packaged unit may have factory-attached modules:- (mixing box for inlet <strong>air</strong> with selection of outside andreturn entering <strong>air</strong> configurations [top, bottom, rear <strong>com</strong>binationswith or without screens], outside or outside and return<strong>air</strong> dampers [manual, 2-position, 3-position, modulating, DDCcontrolled] with direct-coupled 24VAC actuators and a varietyof controls [unit mounted or remote dial; mixed <strong>air</strong> controllerwith or without warm-up; building <strong>pre</strong>ssure null switch]. Constructionof mixing box will be (single wall, [uninsulated] [insulated])(double wall, [insulated] [high density insulated]).- (draw-through cooling coil module with factory installed[dx coil] [chilled water coil]. Construction of cooling coil modulewill be double wall with [standard (R value 3.8)] [high density(R value 4.4)] insulation). (Cooling coil cabinet to include UVCgermicidal lamp for neutralization of VOCs and microorganizmsfor improved IAQ).- (evaporative cooling module. Construction of evaporativecooling cabinet will be [white <strong>pre</strong>-painted] [300 series stainlesssteel] with 300 series stainless steel reservoir [and (1”)(2”) aluminum <strong>pre</strong>-filter]. Water system to include [recirculatingfloat and pump] [AquaSaver microprocessor-based timeddistribution system] . Evaporative media to consist of [6”] [12”][Glacier-Core®] [Glas-dek® UL900 Class I non<strong>com</strong>bustible]media.The packaged system shall have a <strong>pre</strong>-coat RAL 1001 whitepaint finish. Finish shall be a minimum 80 gloss on G30 galvanizedsteel.Cabinet shall have through-the-base utility knockouts. Control,burner, and blower service <strong>com</strong>partment doors shall behinged. Blower door hardware shall be heavy duty stainless.Control and burner door hardware shall have heavy duty externalhardware.The following features will be factory installed: (ductflanges); (discharge louvers [horizontal] [horizontal and vertical]);(convenience outlet); (firestat); (discharge temperaturelow limit), (over/under voltage or phase loss protection); (highambient limit); (high, low, or high and low gas <strong>pre</strong>ssureswitches); (heat section condensate drain); and (relays).The following accessories will be provided: horizontal orvertical vent/<strong>com</strong>bustion <strong>air</strong> kit; (downturn nozzle [25-65° withor without vertical louvers] [50-90° with or without verticallouvers]); (thermostat selection to match all analog control systems),(gas <strong>pre</strong>ssure regulator); (remote console); and (fuseddisconnect switch).The packaged heating and makeup <strong>air</strong> system shall be design-certifiedto ANSI Z83.8 and CSA 2.6 Standards. The energyusage shall be designed to meet ASHRAE Standard 90.1.See specific information for sizes and capacities.Product manufacturer must have minimum of 40 years ofexperience with separated <strong>com</strong>bustion heating equipment.Page 46 Form C-PREEVA


SAMPLE SPECIFICATIONModel PDH, INDOOR, POWER-VENTED HEATING AND MAKEUP AIR UNITSProvide packaged, indoor heating and makeup <strong>air</strong>, powerventedunits as Reznor ® brand equipment. The units shall bethe PDH series, minimum 81% efficiency, designed for ceilingsuspension or slab or floor mounting. The gas furnace is to bearranged for ducted flue gas exhaust.All units shall be equipped for use with (natural gas) (propane);(115/1) (208/1) (230/1) (208/3) (230/3) (460/3) (575/3)supply voltage with (unit mounted, non-fusible, lockable disconnectswitch); 24-volt control transformer; protective <strong>air</strong>proving switch; resiliently (rubber) (spring) isolated ventermotor; and a high temperature limit control. Operation shallbe controlled through an integrated circuit board. The circuitboard shall monitor heater operation and have LED diagnosticindicator lights to identify abnormalities in control functions.Unit shall have a (one-stage gas control) (two-stage gas control)(two-stage gas makeup <strong>air</strong> control) (33% low fire capacitymakeup <strong>air</strong> control) (2-stage heating/3-stage cooling digital control[space temperature] [discharge temperature]); or (electronicmodulation heating 25% low fire - natural gas, 40% low fired- propane/3-stage cooling digital control [space temperature][discharge temperature]).The gas furnace shall have a Reznor TCORE 2® heat exchangerand single burner <strong>com</strong>bustion system. The heat exchangershall be of (aluminized) (409 stainless) (316 stainless)steel.The furnace shall be equipped with all required safety elements.The (single wall, [uninsulated] [insulated]) (double wall[insulated] [high density insulated]) blower section shall be suppliedwith (horizontal supply opening) (screened horizontal supplyopening) (horizontal supply <strong>air</strong> inlet opening with ductflanges) (screened horizontal supply <strong>air</strong> inlet opening with ductflanges). The blower section shall include an adjustable beltdriven(rubber) (spring) vibration isolated centrifugal blowerand (open dripproof) (totally enclosed) (<strong>pre</strong>mium efficiency)(2-speed) [rubber] [spring] vibration isolated motor with(contactor) (motor starter) (variable frequency drive). (Unit mayinclude [1” or 2” disposable] [1” or 2” permanent] [1”, 2”, or4” pleated] filters).Packaged unit may have factory-attached modules:- (mixing box for inlet <strong>air</strong> with selection of outside andreturn entering <strong>air</strong> configurations [top, bottom, rear <strong>com</strong>binationswith or without screens], outside or outside and return<strong>air</strong> dampers [manual, 2-position, 3-position, modulating, DDCcontrolled] with direct-coupled 24VAC actuators and a varietyof controls [unit mounted or remote dial; mixed <strong>air</strong> controllerwith or without warm-up; building <strong>pre</strong>ssure null switch]. Constructionof mixing box will be (single wall, [uninsulated] [insulated])(double wall, [insulated] [high density insulated]).- (draw-through cooling coil module with factory installed[dx coil] [chilled water coil]. Construction of cooling coil modulewill be double wall with [standard (R value 3.8)] [high density(R value 4.4)] insulation). (Cooling coil cabinet to include UVCgermicidal lamp for neutralization of VOCs and microorganizmsfor improved IAQ).- (evaporative cooling module. Construction of evaporativecooling cabinet will be [white <strong>pre</strong>-painted] [300 series stainlesssteel] with 300 series stainless steel reservoir [and (1”)(2”) aluminum <strong>pre</strong>-filter]. Water system to include [recirculatingfloat and pump] [AquaSaver microprocessor-based timeddistribution system] . Evaporative media to consist of [6”] [12”][Glacier-Core®] [Glas-dek® UL900 Class I non<strong>com</strong>bustible]media.The packaged system shall have a <strong>pre</strong>-coat RAL 1001 whitepaint finish. Finish shall be a minimum 80 gloss on G30 galvanizedsteel.Cabinet shall have through-the-base utility knockouts. Control,burner, and blower service <strong>com</strong>partment doors shall behinged. Blower door hardware shall be heavy duty stainless.Control and burner door hardware shall have heavy duty externalhardware.The following features will be factory installed: (ductflanges); (discharge louvers [horizontal] [horizontal and vertical]);(convenience outlet); (firestat); (discharge temperaturelow limit), (over/under voltage or phase loss protection); (highambient limit); (high, low, or high and low gas <strong>pre</strong>ssureswitches); and (relays).The following features will be factory installed: (ductflanges); (discharge louvers [horizontal] [horizontal and vertical]);(convenience outlet); (firestat); (discharge temperaturelow limit), (over/under voltage or phase loss protection); (highambient limit); (high, low, or high and low gas <strong>pre</strong>ssureswitches); (heat section condensate drain); and (relays).The following accessories will be provided: (vent cap);(downturn nozzle [25-65° with or without vertical louvers] [50-90° with or without vertical louvers]); (thermostat selection tomatch all analog control systems), (gas <strong>pre</strong>ssure regulator); (remoteconsole); and (fused disconnect switch).The packaged heating and makeup <strong>air</strong> system shall be design-certifiedto ANSI Z83.8 and CSA 2.6 Standards. The energyusage shall be designed to meet ASHRAE Standard 90.1.See specific information for sizes and capacities.Product manufacturer must have minimum of 40 years ofexperience with makeup <strong>air</strong> heating equipment.Form C- PREEVA Page 47


SAMPLE SPECIFICATIONModel RDH, ROOFTOP, POWER-VENTED HEATING AND MAKEUP AIR UNITSProvide packaged, rooftop heating and makeup <strong>air</strong>, powerventedunits as Reznor ® brand equipment. The units shall bethe RDH series, minimum 81% efficiency, designed for rooftopor slab mounting.All units shall be equipped for use with (natural gas) (propane);(115/1) (208/1) (230/1) (208/3) (230/3) (460/3) (575/3)supply voltage with (unit mounted, non-fusible, lockable disconnectswitch); 24-volt control transformer; protective <strong>air</strong>proving switch; resiliently (rubber) (spring) isolated ventermotor; and a high temperature limit control. Operation shallbe controlled through an integrated circuit board. The circuitboard shall monitor heater operation and have LED diagnosticindicator lights to identify abnormalities in control functions.Unit shall have a (one-stage gas control) (two-stage gas control)(two-stage gas makeup <strong>air</strong> control) (33% low fire capacitymakeup <strong>air</strong> control) (2-stage heating/3-stage cooling digital control[space temperature] [discharge temperature]); or (electronicmodulation heating 25% low fire - natural gas, 40% low fired- propane/3-stage cooling digital control [space temperature][discharge temperature]).The gas furnace shall have a Reznor TCORE 2® heat exchangerand single burner <strong>com</strong>bustion system. The heat exchangershall be of (aluminized) (409 stainless) (316 stainless)steel.The furnace shall be equipped with all required safety elements.The double wall (insulated) (high density insulated) blowersection shall be supplied with (horizontal supply opening) (horizontalsupply <strong>air</strong> inlet opening with duct flanges). The blowersection shall include an adjustable belt-driven (rubber) (spring)vibration isolated centrifugal blower and (open dripproof) (totallyenclosed) (<strong>pre</strong>mium efficiency) (2-speed) [rubber] [spring]vibration isolated motor with (contactor) (motor starter) (variablefrequency drive). (Unit may include [1” or 2” disposable][1” or 2” permanent] [1”, 2”, or 4” pleated] filters) (100% O/Aweatherhood with rain baffles will be supplied for field installation).Packaged unit may have factory-attached modules:- (mixing box for inlet <strong>air</strong> with selection of outside andreturn entering <strong>air</strong> configurations [bottom, rear <strong>com</strong>binationswith or without screens], outside or outside and return <strong>air</strong> dampers[(30% O/A hood for use with mixing box) (100% O/Aweatherhood with rain baffles will be supplied for field installation)][manual, 2-position, 3-position, modulating, DDC controlled]with direct-coupled 24VAC actuators and a variety ofcontrols [unit mounted or remote dial; mixed <strong>air</strong> controller withor without warm-up; building <strong>pre</strong>ssure null switch]. Constructionof mixing box will be double wall [insulated] [high densityinsulated])- (draw-through cooling coil module with factory installed[dx coil] [chilled water coil]. Construction of cooling coil modulewill be double wall with [standard (R value 3.8)] [high density(R value 4.4)] insulation). (Cooling coil cabinet to include UVCgermicidal lamp for neutralization of VOCs and microorganizmsfor improved IAQ).- (downturn plenum cabinet. Construction of downturnplenum will be double wall with [standard (R value 3.8)] [highdensity (R value 4.4)] insulation).- (evaporative cooling module. Construction of evaporativecooling cabinet will be [white <strong>pre</strong>-painted] [300 series stainlesssteel] with 300 series stainless steel reservoir [and (1”)(2”) aluminum <strong>pre</strong>-filter]. Water system to include [recirculatingfloat and pump] [AquaSaver microprocessor-based timeddistribution system] . Evaporative media to consist of [6”] [12”][Glacier-Core®] [Glas-dek® UL900 Class I non<strong>com</strong>bustible]media.The packaged system shall have a <strong>pre</strong>-coat RAL 9001 whitepaint finish. Finish shall be a minimum 60 gloss. Finish shallmeet ASTM B117 specifications for salt spray at 1,000 hours.Cabinet shall have through-the-base utility knockouts. Control,burner, and blower service <strong>com</strong>partment doors shall behinged. Blower door hardware shall be heavy duty stainless.Control and burner door hardware shall have heavy duty externalhardware.The following optional features will be factory installed:(duct flanges); (convenience outlet); (firestat); (discharge temperaturelow limit), (over/under voltage or phase loss protection);(high ambient limit); (high, low, or high and low gas<strong>pre</strong>ssure switches); (heat section condensate drain); and (relays).The following accessories will be provided: (vertical ventextension kit); (thermostat selection to match all analog controlsystems), (gas <strong>pre</strong>ssure regulator); (remote console); and(fused disconnect switch) (16” roof curb) ([100% O/Aweatherhood with rain baffles]) (<strong>com</strong>patible energy recoverymodule with appropriate wiring connections) (photoelectric <strong>air</strong>duct smoke detector); (matching energy recovery module).The packaged heating and makeup <strong>air</strong> system shall be design-certifiedto ANSI Z83.8 and CSA 2.6 Standards. The energyusage shall be designed to meet ASHRAE Standard 90.1.See specific information for sizes and capacities.Product manufacturer must have minimum of 40 years ofexperience with makeup <strong>air</strong> heating equipment.Page 48 Form C-PREEVA


WARRANTYREZNOR ® PRODUCT LIMITED WARRANTYThomas & Betts Corporation warrants to the original owner-user that this Reznor product will be free from defects inmaterial or workmanship. This warranty is limited to twelve (12) months from the date of original installation, whether or notactual use begins on that date, or eighteen (18) months from date of shipment by Thomas & Betts Corporation, whicheveroccurs first.Optional Extended WarrantyExtended warranties on <strong>com</strong>ponents of Models RDH, SDH and PDH may be purchased. Warranties include:Option XW2 - Limited 5-year Heat Exchanger WarrantyOption XW3 - Limited 10-year Heat Exchanger WarrantyLIMITATIONS AND EXCLUSIONSThomas & Betts Corporation’s obligations under this warranty and the sole remedy for its breach are limited to rep<strong>air</strong>, atits manufacturing facility, of any part or parts of its Reznor products which prove to be defective; or, in its sole discretion,replacement of such products. All returns of defective parts or products must include the product model number and serialnumber, and must be made through an authorized Reznor distributor or arranged through Reznor Customer Service. Authorizedreturns must be shipped <strong>pre</strong>paid. Rep<strong>air</strong>ed or replacement parts will be shipped by Thomas & Betts F.O.B. shippingpoint.1. The warranty provided herein does not cover charges for labor or other costs incurred in the troubleshooting, rep<strong>air</strong>, removal, installation,service or handling of parts or <strong>com</strong>plete products.2. All claims under the warranty provided herein must be made within ninety (90) days from the date of discovery of the defect. Failure tonotify Thomas & Betts of a warranted defect within ninety (90) days of its discovery voids Thomas & Betts's obligations hereunder.3. The warranty provided herein shall be void and of no effect in the event that (a) the product has been operated outside its designed outputcapacity (heating, cooling, <strong>air</strong>flow); (b) the product has been subjected to misuse, neglect, accident, improper or inadequate maintenance,corrosive environments, environments containing <strong>air</strong>borne contaminants (silicone, aluminum oxide, etc.), or excessive thermal shock; (c)unauthorized modifications are made to the product; (d) the product is not installed or operated in <strong>com</strong>pliance with the manufacturer’sprinted instructions; (e) the product is not installed and operated in <strong>com</strong>pliance with applicable building, mechanical, plumbing andelectrical codes; or (f) the serial number of the product has been altered, defaced or removed.4. The warranty provided herein is for rep<strong>air</strong> or replacement only. Thomas & Betts Corporation shall not be liable for any loss, cost, damage,or expense of any kind arising out of a breach of the warranty. Further, Thomas & Betts Corporation shall not be liable for any incidental,consequential, exemplary, special, or punitive damages, nor for any loss of revenue, profit or use, arising out of a breach of this warrantyor in connection with the sale, maintenance, use, operation or rep<strong>air</strong> of any Reznor product. In no event will Thomas & Betts be liable forany amount greater than the purchase price of a defective product. The disclaimers of liability included in this paragraph 4 shall remain ineffect and shall continue to be enforceable in the event that any remedy herein shall fail of its essential purpose.5. THIS WARRANTY IS THE SOLE AND EXCLUSIVE WARRANTY FOR REZNOR PRODUCTS, AND IS IN LIEU OF ALL OTHEREXPRESS AND IMPLIED WARRANTIES. THOMAS & BETTS CORPORATION SPECIFICALLY DISCLAIMS ALL OTHER EX-PRESS AND IMPLIED WARRANTIES, INCLUDING, BUT NOT LIMITED TO, ALL IMPLIED WARRANTIES OF MERCHANTABIL-ITY AND FITNESS FOR A PARTICULAR PURPOSE. No person or entity is authorized to bind Thomas & Betts Corporation to any otherwarranty, obligation or liability for any Reznor product. Installation, operation or use of the Reznor product for which this warranty isissued shall constitute acceptance of the terms hereof.Form C- PREEVA Page 49


Reznor ® is your global source for heating,ventilating and <strong>air</strong> conditioning equipment.®For more information on Reznor HVAC Equipment,contact your local Reznor Re<strong>pre</strong>sentative by calling800-695-1901.Or, find us on the internet atwww.RezSpec.<strong>com</strong>In keeping with our policy of continuous product improvement, wereserve the right to alter, at any time, the design, construction,dimensions, weights, etc., of equipment information shown here.©2006 Thomas & Betts Corporation, All rights reserved. Printed in the U.S.A.Trademark Note: Reznor ® is registered in the United States and other countries.1206 POD OG Form C-PREEVA (Version A.9)