Source: US-Canada Blackout Final Report April 2004<br />

System Enhancement & Elimination of Bottlenecks<br />

● On-Line Monitoring and Real-Time Security Assessment<br />

● Increase of Reserve Capacity<br />

Fig. 16: Conclusions of the US-Canada Blackout Final Report April 2004<br />

X/Ohm<br />

100<br />

50<br />

x<br />

x<br />

Conventional (not digital) Relays lead to unselective<br />

Tripping under high Load Conditions<br />

Sammis-Star: unselective Trip<br />

50 100 R/Ohm<br />

Load Flow <strong>–</strong> Steady State<br />

The Solution …<br />

Digital Protection: T-Bone or MHO-Characteristic with<br />

incorporated Load Blocking<br />

Fig. 17: Avoidance of Outages through Investments in new Technologies <strong>–</strong><br />

Example of System Protection<br />