Spectra Plus - Introduction02Current limiting1The limiting capacity of a circuit breaker is the expression of the breaker’s capacity.In the event of a short circuit, it reduces the let through current to a lower value than theprospective fault current.This characteristic is expressed by the following limiting curves:1. Icc unlimited peak2. Icc limited peak (actual)2The great limiting capacity of Spectra Plus circuit breaker is a result of the optimalcombination of:A light moving part, reducing inertia.A strong current loop, to generate maximum force of repulsion.A slot motor with strong electro-magnetic field to accelerate the opening of thecontact.Contact materials combining good conductivity and high durability.An arc chamber combining a high energy absorption capacity, speed in breaking ofarc and cooling of gases.This combination has enabled an exceptional breaking capacity/volume ratio. Theuse of Spectra Plus circuit breaker enables a great reduction in stresses that normallydevelop during a short-circuit:Reduction in thermal constraints in conductors, increasing their life.Reduction in mechanical constraints due to the reduction of the electrodynamicforces of repulsion between conductors, which reduces the risk of deformation orrupture of the wiring.Reduction in electro-magnetic effects. The electro-magnetic field reduces and causesless damage to neighboring devices and sensors.UseSpectra Plus circuit breakers provide a solution for standard and high performance levelsupto 50kA breaking capacity in 3 frames SE160, SF250 & SG400/630.Suitability for visible isolationSpectra Plus circuit breakers are ideal for fully visible isolation selection. With the handlefree, the indication “open” (green display) is only possible when the main contacts areseparated by a distance of >20mm. Spectra Plus circuit breaker conforms to standards:IEC947-3, IS13947-3 recommended for isolation.Double forward facing insulationSpectra Plus circuit breakers are provided with forward facing spaces designed forinsertion of internal electrical auxiliaries. These spaces are completely insulated from thepower circuit.Accreditation / CertificationIEC947-2, EN60 947.2, IS13947,Lloyd’s Register of Shipping, RINA.


03 Spectra Plus - IntroductionHigh performance electronic protectionThe current sensor output signal for each phase is sampled more than 30 times percycle in order to establish the true RMS value, independent of the network, the natureof the load and the environment of the installation. Hence, Spectra Plus guarantees“correct protection”.Power sourceThe power source can be connected either from upline or downline of the Spectra Pluscircuit breaker, and up to the maximum voltage for use (690V).OrientationA fixed circuit breaker can be mounted as follows:


Spectra Plus - Introduction04Electrical auxiliariesBA bell alarms, AS auxiliary ‘ON/OFF’ switches, ST voltmetric shunt releases and UVundervoltage releases are common to all Spectra circuit breakers. e.g. an AS auxiliary‘ON/OFF’ switch can be installed equally well on an SE 160 or SG 630 circuit breaker.Thus it is not necessary to specify the type of circuit breaker. Only the release voltageand the type of contact (standard or low level) has to be indicated with the order.AssemblyAs this is intended for installation in compartments that are accesssible from thefront, it is not necessary to take off the cover of the circuit breaker.Left-hand compartmentOption of connecting UV or ST releases plus 3 pole BA. 1 or 2 additional AS contactscan be connected to 4 pole SG400 to SG630 circuit breaker (an extra socket isprovided for this).On each circuit breaker, ducts for the wiring are provided enabling the passage of thecables to the right, left, or to the rear side of the device, without increasing its originaldimensions.Right-hand compartmentOption of connecting 1 or 2 AS auxiliary switches.On each circuit breaker, ducts for the wiring are provided enabling the passage of thecables to the right, left, or to the rear side of the device, without increasing its originaldimensions.Maximum possibilities for auxilliariesCircuit Breaker 3P 4PAS 2 2BA 1 1ST or UV 1 1


05 Spectra Plus - AccessoriesElectrical auxiliariesAS auxiliary ‘ON/OFF’ switches.DescriptionIndicates the "open" or "closed" position of the circuit breaker to other auxiliaries suchas logic circuits, relays, displays, etc.. for control, locking, or remote indicator functions.Characteristicsopen close open closeChangeover contacts get activated at the same time as main poles. 2 versions:14221224141 changeover C/O or 2 changeover C/O (in the same volume). 12Standard contactsOperating voltage (V) AC 50-60 Hz DC120 to 240 48 to 125Load - resistive inductiveUninterrupted current (A) 5 0.5 0.25Breaking capacity (A) 5 0.5 0.25Closing capacity (A) 5 0.5 0.2511commonWiring colour code12: BNWH (brown & white)14: RD (red)11: WH (white)22: OGWH (orange-white)24: OG (orange)21: GY (grey)2111commonBA bell alarm contactsDescriptionChangeover contacts signalling the "tripped" status of the circuit breaker caused by afault or opening by voltmetric ST or UV trip devices, or by an earth leakage device.The contact returns to the "normal" position on resetting of the circuit breaker.The BA contact is not activated with a normal closing or opening of the circuit breaker.CharacteristicsStandard contactsOperating voltage (V) AC 50-60 Hz DC120 to 240 48 to 125Load - resistive inductiveUninterrupted current (A) 5 0.5 0.25Breaking capacity (A) 5 0.5 0.25Closing capacity (A) 5 0.5 0.25normal default96 9895commonWiring colour code96: GN (green)98: BN (brown)95: YE (yellow)Earth fault moduleDescriptionEFM250* Earth fault module is a compact and microprocessor based solution usedwith the Spectra Plus range for providing effective Earth fault protection.- Range 5% to 80% of In (In settable)- Delay 50msec to 5 sec.- Suitable for 3Phase 3Wire and 3Phase 4Wire system up to 630A* For 400/630A please contact our nearest office.


Spectra Plus - Accessories06Shunt release STDescriptionShunt release ST causes the remote opening of the circuit breaker as soon as itreceives power (power can be permanent). Operation is guaranteed from 55% ofUn with alternating current and from 70% of Un with direct current.CharacteristicsStandard contactsOperating voltage (V) AC 50-60 Hz AC* 55% of Un for AC - 70% of Un for DCDC50-60 Hz24 48 110/127 220/250 380/415Max. ringing current (mA) 300 300 500 400 400Average current (mA) 10 10 6 5 6Release breaking time (ms)min. (100% Un) 15 12 10 15 15max.* 45 30 35 50 50Wiring colour code:C1 - C2: Black(BK)Undervoltage release UVDescriptionUndervoltage release UV causes opening of the circuit breaker in the event of a dropin voltage (35% to 70% of Un) guaranteed closure of the circuit breaker if Un > 85%.Operating range:0.85 < Uc < 1.1 Un.When the release does not receive power, or voltage is too low, the circuit breakercannot be reclosed; the contacts do not touch.CharacteristicsStandard contactsOperating voltage (V) AC 50-60 Hz/DC24 48 110/127 220/250 (2)Max. calling current (mA) 100 100 200 200Average current (mA) 80 45 45 45Release breaking time (ms)mini (100% Un) 3 45 75 75maxi (1) 85 120 250 250Wiring colour codeD1 - D2: Blue (BL)(1) 55% of Un for AC - 70% of Un for DC.(2) Time release MVR retarder (250, 500, 800, 1000 ms.) at 220V AC 50Hz.Avoids untimely tripping with sudden loss of voltage.


07 Spectra Plus - Data sheetExtended rotary handleExtended rotary handle ensuring a smooth operation of MCCB. The new extendedhandle has three distinct positions - ON, OFF & TRIP with padlock facility.Seperators / SpreadersSpectra Plus range has been designed for ease of proper termination with help ofspreaders. Seperators are an integral part of MCCB and they help to enhance theinsulation level between live terminals.Technical specificationsCircuit Breakers SG 160 SG 250 SG 400 SG 630S N S N S N S NRated current lth (A) at 40 0 C 160 160 250 250 400 400 630 630Rated operating voltage Ue AC 50/60Hz (V) 690 690 690 690 690 690 690 690Rated insulation voltage Ui (V) 690 690 690 690 690 690 690 690Ultimate short-circuit breaking capacity lcu50/60Hz 380/415V (kA) 36 50 36 50 36 50 36 50Service short-circuit breaking capacity lcs AC50*60 Hz 380/415V (kA) 36 50 36 50 36 50 36 50Rated short-circuit making capacity lcm Ac50/60 Hz 380/415V (kA) 76 110 76 110 76 110 76 110Rated impulse voltage Uimp (kV) 8 8 8 8 8 8 8 8Operational category A A A A A A A ANumber of poles 3-4 3-4 3-4 3-4 3-4 3-4 3-4 3-4EnduranceMechanical operations 15000 15000 15000 15000 10000 10000 10000 10000Electrical operations 4000 4000 4000 4000 3000 3000 3000 3000Total fault elimination time (ms)


Spectra Plus - Dimensions08Spectra Plus SE 160 Frame3PSpectra Plus SF 250 Frame4P3P4PSpectra Plus SG 400/630 Frame3P4P


09 Spectra Plus - DimensionsDoor Drive Details - E FrameDoor Drive Details - F Frame


Spectra Plus - Dimensions10Door Drive Details - G FrameDoor Drilling Details for Mounting Handle on Panel Door


<strong>GE</strong> introduces Spectra TME125, a thermal magnetic MCCB in 3 / 4 pole for overload and shortcircuit protection. Spectra TME125 has been tested for breaking capacities upto 25kA at 415VAC.This MCCB provides protection for transformers, distribution circuits, cables and other equipment.Spectra TME125FeaturesMagnetic instantaneous trip actuates the trip mechanism without any delay in the event of short circuitCurrent limiting, quick make, quick break mechanism that operates independent of manual forcePositive trip indication knob comes to a distinct position when the breaker trips due to overcurrent orshort circuit faultsEffective arc runner pushes the arc in the arc chute thereby reducing the contact tip damage and increasingthe contact’s lifeRed colour ‘PUSH TO TRIP’ button is provided to check the tripping mechanismContacts are made of silver alloy with an anti-welding propertyInternal and external accessories that can be fitted on siteVariable thermal setting from 80 -100%Trip free mechanismThermal memory


Technical ParticularsRated Currents (In) 16A, 20A, 32A, 40A,50A, 63A, 80A, 100A, 125A 16A, 20A, 32A, 40A, 50A, 63A, 80A, 100A, 125ARated Operational VoltageRated Insulation VoltageRated Frequency415VAC690VAC50Hz415VAC690VAC50HzNo. of Poles3 / 4 Pole 3 / 4 PoleUtilization CategoryAARated Ultimate Short Circuit BreakingCapacityRated Service Short Circuit BreakingCapacityOverload Adjustability18kA25kA50% 40%80 - 100% 80 - 100%Reference StandardTerminationIS13947-2 & IEC947-235sqmm Cu cable, or 16 X 6mm linksIS13947-2 & IEC947-235sqmm Cu cable, or 16 X 6mm links112.6110±0.235±0.2 35±0.217.5 17.5147 11.5170±0.2145±0.235±0.2 35±0.217.5 17.535±0.2NEUTRAL152±0.29170±0.283.8 5.578.8PUSH TO TRIPPUSH TO TRIP<strong>GE</strong> India <strong>Industrial</strong> Pvt. Ltd.The Millenia, Level 6, Tower B, #1 & 2, Murphy Road, Ulsoor, Bangalore 560 008Ph: (080) 41434000, Fax: (080) 41434199Email: query@ge.com0910/GR/SP


<strong>GE</strong> introduces Spectra TM200, a thermal magnetic MCCB in 3 / 4 pole for overload and shortcircuit protection. Spectra TM200 has been tested for breaking capacities upto 36kA at 415VAC.This MCCB provides protection for transformers, distribution circuits, cables and other equipment.Spectra TM200FeaturesVariable thermal setting from 80 -100%Current limiting, quick make, quick break mechanism that operates independent of manual forcePositive trip indication knob comes to a distinct position when the breaker trips due to over-current orshort circuit faultsEffective arc runner pushes the arc in the arc chute thereby reducing the contact tip damage andincreasing the contact’s lifeContacts are made of silver alloy with an anti-welding propertyMagnetic instantaneous trip actuates the trip mechanism without any delay in the event of short circuitRed colour ‘PUSH TO TRIP’ button is provided to check the tripping mechanismInternal and external accessories that can be fitted on siteTrip free mechanismThermal memory


Technical ParticularsRated Currents (In) 160A, 200A 160A, 200ARated Operational VoltageRated Insulation VoltageRated Frequency415VAC690VAC50Hz415VAC690VAC50HzNo. of PolesUtilization CategoryRated Ultimate Short Circuit BreakingCapacityRated Service Short Circuit BreakingCapacityOverload Adjustability3 / 4 Pole 3 / 4 PoleAA25kA36kA100% 75%80 - 100% 80 - 100%Reference StandardTerminationIS13947-2 & IEC947-250sqmm Cu cable, or 20 X 6mm linksIS13947-2 & IEC947-250sqmm Cu cable, or 20 X 6mm links9530±0.2 30±0.215±0.115±0.18.615±0.183±0.130±0.2 30±0.230±0.215±0.12-INSERT M4132.8±0.2150±0.225150±0.2256 - Ø9.04 - Ø8.5114.5124.562.067.372.084DIMENSIONAL DETAILS 160A - 200ADIMENSIONAL DETAILS 160A - 200A3 POLE 4 POLE<strong>GE</strong> India <strong>Industrial</strong> Pvt. Ltd.The Millenia, Level 6, Tower B, #1 & 2, Murphy Road, Ulsoor, Bangalore 560 008Ph: (080) 41434000, Fax: (080) 41434199Email: query@ge.com0910/GR/SP


<strong>GE</strong> introduces Spectra TM125, a thermal magnetic MCCB in 3 / 4 pole for overload and shortcircuit protection. Spectra TM125 has been tested for breaking capacities upto 36kA at 415VAC.This MCCB provides protection for transformers, distribution circuits, cables and other equipment.Spectra TM125FeaturesVariable thermal setting from 80 -100%Current limiting, quick make, quick break mechanism that operates independent of manual forcePositive trip indication knob comes to a distinct position when the breaker trips due to over current orshort circuit faultsEffective arc runner pushes the arc in the arc chute thereby reducing the contact tip damage andincreasing the contact’s lifeContacts are made of silver alloy with an anti-welding propertyMagnetic instantaneous trip actuates the trip mechanism without any delay in the event of short circuitRed colour ‘PUSH TO TRIP’ button is provided to check the tripping mechanismInternal and external accessories that can be fitted on siteThermal memoryTrip free mechanism


Technical ParticularsRated Currents (In)16A, 20A, 32A, 40A, 50A, 63A, 80A, 100A, 125A 16A, 20A, 32A, 40A, 50A, 63A, 80A, 100A, 125ARated Operational VoltageRated Insulation VoltageRated Frequency415VAC690VAC50Hz415VAC690VAC50HzNo. of Poles3 / 4 Pole 3 / 4 PoleUtilization CategoryAARated Ultimate Short Circuit BreakingCapacityRated Service Short Circuit BreakingCapacityOverload Adjustability25kA36kA100% 75%80 - 100% 80 - 100%Reference StandardTerminationIS13947-2 & IEC947-250sqmm Cu cable, or 20 X 6mm linksIS13947-2 & IEC947-250sqmm Cu cable, or 20 X 6mm links9530±0.2 30±0.215±0.115±0.18.615±0.183±0.130±0.2 30±0.230±0.215±0.12-INSERT M4132.8±0.2150±0.225150±0.2256 - Ø9.04 - Ø8.5114.5124.562.067.372.084DIMENSIONAL DETAILS 160A - 200A3 POLEDIMENSIONAL DETAILS 16A - 125A4 POLE<strong>GE</strong> India <strong>Industrial</strong> Pvt. Ltd.The Millenia, Level 6, Tower B, #1 & 2, Murphy Road, Ulsoor, Bangalore 560 008Ph: (080) 41434000, Fax: (080) 41434199Email: query@ge.com0910/GR/SP