62 The building in winterfollowing extensive examination <strong>of</strong> a number <strong>of</strong> buildings <strong>of</strong> various types. Figure 2.15provides a summary which illustrates the order <strong>of</strong> saving in fuel consumption which maybe achieved as a result <strong>of</strong> intermittent operation.Preheat capacityWhen a heating system is operated intermittently, the temperature within the building willfall during the period <strong>of</strong> system shut-down <strong>and</strong>, in order to restore this to the proper levelby the time the occupants arrive, a preheating period is necessary. Since the outsidetemperature varies during the winter nights, so will the time required for preheat increaseor decrease <strong>and</strong> control equipment which provides means for dealing with this variation isdescribed in Chapter 22 (p. 639).OccupancyInternal temperature °C6800 4 8 12 16 20 24Time hBoostperiodOccupancyHeat input percent load100Boostlevel00 4 8 12 16 20 24Time hFigure 2.16 Pr<strong>of</strong>iles <strong>of</strong> temperature <strong>and</strong> load for intermittent heating