632 Automatic controls <strong>and</strong> building management systemswhereN ˆ valve authorityP 1 ˆ pressure drop across the open valveP 2 ˆ pressure drop across the remainder <strong>of</strong> the circuit:The most common applications are represented in Figure 22.13. For stable control, thevalve authority should be not less than the following values.Mixing ˆ 0:3Diverting ˆ 0:5Throttling ˆ 0:5Application <strong>of</strong> the above criteria would normally lead to control valves being selectedat one, or maybe two, pipe sizes smaller than the pipeline diameter (depending upon thefluid temperature difference being used). Three-port valves should always be fitted in themixing mode, that is with two inlets <strong>and</strong> one outlet. As illustrated in Figure 22.13, suchvalves may be applied to either a mixing or a diverting duty but many <strong>of</strong> the patternsavailable are not suitable for use in the diverting mode, that is with one inlet <strong>and</strong> twooutlets.P1P2SourceLoadSourceLoadP2P1(a) 3-port mixing(b) 3-port divertingP2SourceLoad Valve authority =P1P+ 1 P2P1(c) 2-port applicationFigure 22.13 Basic control valve applications