CD 30 ÷ 520Earthing wire22——High speed of outdoor fan, controlled by T4.23——Low speed of outdoor fan, controlled by T4.24——PWM, used for digital compressor capacity adjustment. (Just valid for main unit).25——Transformer input, 220V/AC.26——Power input by three-phase four-wire system (E1 for failure code).A, B, C phases should be supplied together with the 120 degree angle difference amongthree phases. If it is not qualified, it may cause phases sequence failure or phases absentfailure then the corresponding code will be displayed until the power get right. Notice:phases sequence failure or phases absent failure are just checked at the beginning ofelectrifying. During the running, they will not be detected.27——Transformer output50
CD 30 ÷ 5203. Failure & protection codesFailure & protection codesE0E1E2E3E4E5E6E7E8E9Water flow check failure (main unit)Phases sequence failureCommunication failureTotal outlet water Temperature sensor failurePlate heat exchanger outlet water Temperature sensor failureCondenser A tube Temperature sensor failureCondenser B tube Temperature sensor failureOutdoor Temperature sensor failureSystem A compressor discharge gas Temperature sensor failureWater flow check failure (auxiliary unit)EAECEDEEAuxiliary units decreased detected by main unitLinear controller can’t detect the online unitsCommunication failure between linear controller and modulesCommunication failure between linear controller and computerP0P1P2P3P4P5P6P7P8System A high-pressure protection or discharge gas Temperature protectionSystem A low-pressure protectionSystem B high-pressure protection or discharge gas Temperature protectionSystem B low-pressure protectionSystem A current protectionSystem B current protectionSystem A Condenser high-Temperature protectionSystem B Condenser high-Temperature protectionDischarge Temperature Protection when system A is digital compressorPbSystem anti-freeze protectionPc Digital compressor discharge Temperature protection, when it is above 125℃51
- Page 1 and 2: R22A I R C O N D I T I O N I N GR40
- Page 3 and 4: CD 30 ÷ 520CONTENTSModular Air-coo
- Page 5 and 6: CD 30 ÷ 520Air-cooled heat-pump mo
- Page 7 and 8: CD 30 ÷ 5203. View (one module 65k
- Page 9 and 10: CD 30 ÷ 5205. SpecificationCooling
- Page 11 and 12: CD 30 ÷ 520CoolingModelCD65 130 19
- Page 13 and 14: CD 30 ÷ 5206.3 Pulse width modulat
- Page 15 and 16: CD 30 ÷ 5207. The capacity control
- Page 17 and 18: CD 30 ÷ 5207.1. Heating and coolin
- Page 19 and 20: CD 30 ÷ 5207.2. Cooling and heatin
- Page 21 and 22: CD 30 ÷ 5207.3 Principle of Digita
- Page 23 and 24: CD 30 ÷ 520 Matched RS485 communic
- Page 25 and 26: CD 30 ÷ 520• Installation founda
- Page 27 and 28: CD 30 ÷ 52011. WiringAll wiring in
- Page 29 and 30: CD 30 ÷ 52012. Debugging• Prepar
- Page 31 and 32: CD 30 ÷ 520 Please turn on the mai
- Page 33 and 34: CD 30 ÷ 52013. MaintenanceTo ensur
- Page 35 and 36: CD 30 ÷ 5202) Vacuum refrigerant p
- Page 37 and 38: CD 30 ÷ 52014. Troubles and soluti
- Page 39 and 40: CD 30 ÷ 520Compressor stopby thelo
- Page 41 and 42: CD 30 ÷ 52016. Electric control fi
- Page 43 and 44: 18. Unit electric control & communi
- Page 45 and 46: CD 30 ÷ 520Unit electric controlle
- Page 47 and 48: CD 30 ÷ 520systems. The correspond
- Page 49: CD 30 ÷ 52016——System A electr
- Page 53 and 54: CD 30 ÷ 5202. Pattern& buttons des
- Page 55 and 56: CD 30 ÷ 520number, etc. will be se
- Page 57 and 58: CD 30 ÷ 520H) The current setting
- Page 59 and 60: CD 30 ÷ 5207) Online units & runni
- Page 61 and 62: CD 30 ÷ 5207——Communication wi
- Page 63 and 64: CD 30 ÷ 52063
<strong>CD</strong> 30 ÷ 520Earthing wire22——High speed of outdoor fan, controlled by T4.23——Low speed of outdoor fan, controlled by T4.24——PWM, used for digital compressor capacity adjustment. (Just valid for main unit).25——Transformer input, 220V/AC.26——Power input by three-phase four-wire system (E1 for failure code).A, B, C phases should be supplied together with the 120 degree angle difference amongthree phases. If it is not qualified, it may cause phases sequence failure or phases absentfailure then the corresponding code will be displayed until the power get right. Notice:phases sequence failure or phases absent failure are just checked at the beginning ofelectrifying. During the running, they will not be detected.27——Transformer output50