CD 30 ÷ 520The current will not be detected at the first 5 seconds when starting, after that, if the current isexceeds the pre-set protection standard, (18A for both of digital and constant), compressorwill stop, and restart 3 minutes later.3——T4: Outdoor Temperature sensor (failure code E7).T 3B : Condenser B tube Temperature sensor (failure code E6, protection code P7).T 3A : Condenser A tube Temperature sensor (failure code E5, protection code P6). T4If any one system needs to start the outdoor fan, the fan will be started by the unit electriccontroller. The fan has two speed levels: high and low which all depends on the T4Temperature. T 3B 、T 3A When unit electric controller detects the Temperature of T 3B or T 3A are higher than 65℃,the corresponding system will stop, then restart after the Temperature is lower than 60℃or less. Meanwhile the other system keeps running without any influence. T4、T 3B 、T 3AThe alarm will work if the voltage detected by the Temperature sensor is less than 0.05V ormore than 4.95V.• If main unit sensor of fails: all units will stop.• If auxiliary unit sensor fails: this unit will stop while the others keep running.4——System A compressor discharge gas Temperature sensor (failure code E8,protection code P8) is only available for main unit.5——Outlet water Temperature sensor of plate heat exchanger (failure code E4).Capacity output will adjust according to the outlet water Temperature of the plate heatexchanger both in cooling and heating models.(Auxiliary unit) constantly adjusting range: ON and OFF;(Main unit) digitally adjusting range: OFF, 40%, 60%, 80% and 100%.6——Total outlet water Temperature sensor (failure code E3), just valid for main unit.Adjust the Capacity output adjustment according to the outlet water Temperature of theplate heat exchanger both in cooling and heating modesAdjusting range: OFF, 40%, 60%, 80% and 100%.7——CHECK It can be achieved by CHECK to observe the running condition of the outdoor46
CD 30 ÷ 520systems. The corresponding data will be shown as follows:Normal displayRunning modelB compressorcapacityOn line modulesAmbienttemperatureCondenser AtemperatureA system running currentExv B liftExv A liftCondenser Btemperature8——DIGIT Digital compressor selecting switch.“00” presents selectingdigital compressor (asthe main unit.)“11” presents selectingconstant compressor (asthe auxiliary unit.9——ADDRESS0 presents NO. 0 mainunit1~F presents NO 1~15 auxiliary unitsrespectively10——COM(O)485 communication port (failure code E2).11——COM(I) 485 communication port (failure code E2).P, Q, E points of COM (O) and COM (I) are connected with each other for RS-485communication. If failure occurs between the linear controller and main module, all the units stop.47
- Page 1 and 2: R22A I R C O N D I T I O N I N GR40
- Page 3 and 4: CD 30 ÷ 520CONTENTSModular Air-coo
- Page 5 and 6: CD 30 ÷ 520Air-cooled heat-pump mo
- Page 7 and 8: CD 30 ÷ 5203. View (one module 65k
- Page 9 and 10: CD 30 ÷ 5205. SpecificationCooling
- Page 11 and 12: CD 30 ÷ 520CoolingModelCD65 130 19
- Page 13 and 14: CD 30 ÷ 5206.3 Pulse width modulat
- Page 15 and 16: CD 30 ÷ 5207. The capacity control
- Page 17 and 18: CD 30 ÷ 5207.1. Heating and coolin
- Page 19 and 20: CD 30 ÷ 5207.2. Cooling and heatin
- Page 21 and 22: CD 30 ÷ 5207.3 Principle of Digita
- Page 23 and 24: CD 30 ÷ 520 Matched RS485 communic
- Page 25 and 26: CD 30 ÷ 520• Installation founda
- Page 27 and 28: CD 30 ÷ 52011. WiringAll wiring in
- Page 29 and 30: CD 30 ÷ 52012. Debugging• Prepar
- Page 31 and 32: CD 30 ÷ 520 Please turn on the mai
- Page 33 and 34: CD 30 ÷ 52013. MaintenanceTo ensur
- Page 35 and 36: CD 30 ÷ 5202) Vacuum refrigerant p
- Page 37 and 38: CD 30 ÷ 52014. Troubles and soluti
- Page 39 and 40: CD 30 ÷ 520Compressor stopby thelo
- Page 41 and 42: CD 30 ÷ 52016. Electric control fi
- Page 43 and 44: 18. Unit electric control & communi
- Page 45: CD 30 ÷ 520Unit electric controlle
- Page 49 and 50: CD 30 ÷ 52016——System A electr
- Page 51 and 52: CD 30 ÷ 5203. Failure & protection
- Page 53 and 54: CD 30 ÷ 5202. Pattern& buttons des
- Page 55 and 56: CD 30 ÷ 520number, etc. will be se
- Page 57 and 58: CD 30 ÷ 520H) The current setting
- Page 59 and 60: CD 30 ÷ 5207) Online units & runni
- Page 61 and 62: CD 30 ÷ 5207——Communication wi
- Page 63 and 64: CD 30 ÷ 52063
<strong>CD</strong> 30 ÷ 520The current will not be detected at the first 5 seconds when starting, after that, if the current isexceeds the pre-set protection standard, (18A for both of digital and constant), compressorwill stop, and restart 3 minutes later.3——T4: Outdoor Temperature sensor (failure code E7).T 3B : Condenser B tube Temperature sensor (failure code E6, protection code P7).T 3A : Condenser A tube Temperature sensor (failure code E5, protection code P6). T4If any one system needs to start the outdoor fan, the fan will be started by the unit electriccontroller. The fan has two speed levels: high and low which all depends on the T4Temperature. T 3B 、T 3A When unit electric controller detects the Temperature of T 3B or T 3A are higher than 65℃,the corresponding system will stop, then restart after the Temperature is lower than 60℃or less. Meanwhile the other system keeps running without any influence. T4、T 3B 、T 3AThe alarm will work if the voltage detected by the Temperature sensor is less than 0.05V ormore than 4.95V.• If main unit sensor of fails: all units will stop.• If auxiliary unit sensor fails: this unit will stop while the others keep running.4——System A compressor discharge gas Temperature sensor (failure code E8,protection code P8) is only available for main unit.5——Outlet water Temperature sensor of plate heat exchanger (failure code E4).Capacity output will adjust according to the outlet water Temperature of the plate heatexchanger both in cooling and heating models.(Auxiliary unit) constantly adjusting range: ON and OFF;(Main unit) digitally adjusting range: OFF, 40%, 60%, 80% and 100%.6——Total outlet water Temperature sensor (failure code E3), just valid for main unit.Adjust the Capacity output adjustment according to the outlet water Temperature of theplate heat exchanger both in cooling and heating modesAdjusting range: OFF, 40%, 60%, 80% and 100%.7——CHECK It can be achieved by CHECK to observe the running condition of the outdoor46